Page 55

Chapter 2: Installation, Wiring, and Specifications

A Wiring Diagrams and Specifications The remainder of this chapter dedicates two pages to each of the eight versions of DL05 Micro PLCs. Each section contains a basic wiring diagram, equivalent I/O circuits, and 2 specification tables. Please refer to the section which describes the particular DL05 version used in your application. 3 D0–05AR I/O Wiring Diagram The D0–05AR Micro PLC features eight AC inputs and six relay contact outputs. The D following diagram shows a typical field wiring example. The AC external power connection uses four terminals at the left as shown. 5 6 7 8 9 10 11 12 13 14 A The eight AC input channels use terminals in the B middle of the connector. Inputs are organized into two banks of four. Each bank has a common terminal. The wiring example above shows all commons connected C together, but separate supplies and common circuits may be used. The equivalent input circuit shows one D channel of a typical bank. Power input wiring

95-240 VAC

90-120 VAC

Input point wiring

Output point wiring

6-240 VAC or 6-27 VDC

Internal module circuitry

OUTPUT

L

+V

90-120 VAC

COM

To LED

Line

6–27 VDC 6–240 VAC

Equivalent Input Circuit

Equivalent Output Circuit

Derating Chart for Relay Outputs

2–28

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 56

Chapter 2: Installation, Wiring, and Specifications The six relay output channels use terminals on the right side of the connector. Outputs are organized into two banks of three normally-open relay contacts. Each bank has a common terminal. The wiring example on the last page shows all commons connected together, but separate supplies and common circuits may be used. The equivalent output circuit shows one channel of a typical bank. The relay contacts can switch AC or DC voltages. D0-05AR General Specifications External Power Requirements Communication Port 1, 9600 baud (Fixed), 8 data bits, 1 stop bit, odd parity

95 – 240 VAC, 30 VA maximum, K–Sequence (Slave), DirectNET (Slave), Modbus (Slave)

Communication Port 2, 9600 baud (default), 8 data bits, 1 stop bit, odd parity Programming cable type Operating Temperature Storage Temperature Relative Humidity Environmental air Vibration Shock Noise Immunity Terminal Type Wire Gauge

K–Sequence (Slave), DirectNET (Master/Slave), Modbus (Master/Slave) Non-sequence/print D2–DSCBL 32 to 131° F (0 to 55 C) –4 to 158° F (–20 to 70 C) 5 to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 NEMA ICS3–304 Removable One 16AWG or two 18AWG, 24AWG minimum

AC Input Specifications X0-X7 Input Voltage Range (Min. - Max.) Operating Voltage Range Input Current Max. Input Current Input Impedance ON Current/Voltage OFF Current/Voltage OFF to ON Response ON to OFF Response Status Indicators Commons

80 – 132 VAC, 47 - 63 Hz 90 – 120 VAC, 47 -63 Hz 8 mA @ 100 VAC at 50 Hz, 10 mA @ 100 VAC at 60 Hz 12 mA @ 132 VAC at 50 Hz, 15 mA @ 132 VAC at 60 Hz @50 Hz, @60 Hz >6 mA @ 75 VAC <2 mA @ 20 VAC < 40 ms < 40 ms Logic Side 4 channels/common x 2 banks

Relay Output Specifications Y0-Y5 Output Voltage Range Operating Voltage Range Output Current Max. leakage current Smallest Recommended Load OFF to ON Response ON to OFF Response Status Indicators Commons Fuses

(Min. – Max.) 5 – 264 VAC (47 -63 Hz), 5 – 30 VDC 6 – 240 VAC (47 -63 Hz), 6 – 27 VDC 2A/point, 6A/ common 0.1 mA @264VAC 5 mA @5 VDC < 15 ms < 10 ms Logic Side 3 channels/common x 2 banks None (external recommended)

DL05 Micro PLC User Manual, 6th Edition, Rev. A

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

2–29

Page 57

Chapter 2: Installation, Wiring, and Specifications

D0–05DR I/O Wiring Diagram

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

These micro PLCs feature eight DC inputs and six relay contact outputs. The following diagram shows a typical field wiring example. The AC external power connection uses four terminals at the left as shown.

C3

Power input wiring 95-240 VAC

12-24 VDC Source

6-240 VAC or 6-27 VDC

Sink Input point wiring

12-24 VDC

Output point wiring

12-24 VDC Source

Sink

Source

Equivalent Circuit, High-speed Inputs (X0-X2)

Sink

Equivalent Circuit, Standard Inputs (X3-X7)

The eight DC input channels use terminals in the middle of the connector. Inputs are organized into two banks of four. Each bank has an isolated common terminal, and may be wired as either sinking or sourcing inputs. The wiring example above shows all commons connected together, but separate supplies and common circuits may be used. The equivalent circuit for standard inputs and the high-speed input circuit are shown above. Equivalent Output Circuit

The six output channels use terminals on the right side of the connector. Outputs are organized into two banks of three normally-open relay contacts. Each bank has a common terminal. The wiring example above shows all commons connected together, but separate supplies and common circuits may be used. The equivalent output circuit shows one channel of a typical bank. The relay contacts can switch AC or DC voltages. Derating Chart for Relay Outputs

2–30

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 58

Chapter 2: Installation, Wiring, and Specifications

D0-05DR General Specifications External Power Requirements Communication Port 1, 9600 baud (Fixed), 8 data bits, 1 stop bit, odd parity

95 – 240 VAC, 30 VA maximum, K–Sequence (Slave), DirectNET (Slave), Modbus (Slave)

Communication Port 2, 9600 baud (default), 8 data bits, 1 stop bit, odd parity Programming cable type Operating Temperature Storage Temperature Relative Humidity Environmental air Vibration Shock Noise Immunity Terminal Type Wire Gauge

K–Sequence (Slave), DirectNET (Master/Slave), Modbus (Master/Slave) Non-sequence / print D2–DSCBL 32 to 131° F (0 to 55 C) –4 to 158° F (–20 to 70 C) 5 to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 NEMA ICS3–304 Removable One 16AWG or two 18AWG, 24AWG minimum

DC Input Specifications Parameter Min. - Max. Voltage Range Operating Voltage Range Peak Voltage Minimum Pulse Width ON Voltage Level OFF Voltage Level Input Impedance Max. Input Current Minimum ON Current Maximum OFF Current OFF to ON Response ON to OFF Response Status Indicators Commons

High–Speed Inputs, X0 – X2 Standard DC Inputs X3 – X7 10.8 – 26.4 VDC 10.8 – 26.4 VDC 12 -24 VDC 12 -24 VDC 30 VDC (5 kHz maximum frequency) 30 VDC 100 µs N/A > 10 VDC > 10 VDC < 2.0 VDC < 2.0 VDC 1.8 @ 12 – 24 VDC 2.8 @ 12 – 24 VDC 6mA @12VDC, 13mA @24VDC 4mA @12VDC, 8.5mA @24VDC >5 mA >4 mA < 0.5 mA <0.5 mA <100 µs 2 – 8 ms, 4 ms typical < 100 µs 2 – 8 ms, 4 ms typical Logic side Logic side 4 channels/common x 2 bank

Relay Output Specifications Output Voltage Range (Min. - Max.) Operating Voltage Output Current Maximum Voltage Max leakage current Smallest Recommended Load OFF to ON Response ON to OFF Response Status Indicators Commons Fuses

5 -264 VAC (47 -63 Hz), 5 - 30 VDC 6 -240 VAC (47 -63 Hz), 6 - 27 VDC 2A / point, 6A/ common 264 VAC, 30 VDC 0.1 mA @264 VAC 5 mA < 15 ms < 10 ms Logic Side 3 channels/common x 2 banks None (external recommended)

DL05 Micro PLC User Manual, 6th Edition, Rev. A

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

2–31

Page 59

Chapter 2: Installation, Wiring, and Specifications

D0–05AD I/O Wiring Diagram

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

The D0–05AD Micro PLC features eight AC inputs and six DC outputs. The following diagram shows a typical field wiring example. The AC external power connection uses four terminals at the left as shown.

Power input wiring 95-240 VAC

20-28 VDC 6-27 VDC

90-120 VAC Input point wiring

Output point wiring

20-28 VDC

12-24 VDC Source

Sink

Equivalent Input Circuit

Derating Chart for DC Outputs

2–32

Equivalent Output Circuit

The eight AC input channels use terminals in the middle of the connector. Inputs are organized into two banks of four. Each bank has an isolated common terminal. The wiring example above shows all commons connected together, but separate supplies and common circuits may be used. The equivalent input circuit shows one channel of a typical bank. The six current sinking DC output channels use terminals on the right side of the connector. All outputs actually share the same electrical common. Note the requirement for external power on the end (right-most) terminal. The equivalent output circuit shows one channel of the bank of six.

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 60

Chapter 2: Installation, Wiring, and Specifications D0-05AD General Specifications External Power Requirements Communication Port 1, 9600 baud (Fixed), 8 data bits, 1 stop bit, odd parity

95 – 240 VAC, 30 VA maximum, K–Sequence (Slave), DirectNET (Slave), Modbus (Slave)

Communication Port 2, 9600 baud (default), 8 data bits, 1 stop bit, odd parity Programming cable type Operating Temperature Storage Temperature Relative Humidity Environmental air Vibration Shock Noise Immunity Terminal Type Wire Gauge

K–Sequence (Slave), DirectNET (Master/Slave), Modbus (Master/Slave) Non-sequence/print D2–DSCBL 32 to 131° F (0 to 55 C) –4 to 158° F (–20 to 70 C) 5 to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 NEMA ICS3–304 Removable One 16AWG or two 18AWG, 24AWG minimum

AC Input Specifications Input Voltage Range (Min. - Max.) Operating Voltage Range Input Current Max. Input Current Input Impedance ON Current/Voltage OFF Current/Voltage OFF to ON Response ON to OFF Response Status Indicators Commons

80 – 132 VAC, 47 - 63 Hz 90 – 120 VAC, 47 - 63 Hz 8 mA @ 100 VAC (50Hz), 10 mA @ 100 VAC (60Hz) 12 mA @ 132 VAC (50Hz), 15 mA @ 132 VAC (60Hz) @50 Hz, @60 Hz >6 mA @ 75 VAC <2 mA @ 20 VAC < 40 ms < 40 ms Logic Side 4 channels/common x 2 banks

DC Output Specifications Parameter Min. - Max. Voltage Range Operating Voltage Peak Voltage On Voltage Drop Max Current (resistive) Max leakage current Max inrush current External DC power required OFF to ON Response ON to OFF Response Status Indicators Commons Fuses

Pulse Outputs, Y0 – Y1

Standard Outputs, Y2 – Y5

5 – 30 VDC 5 – 30 VDC 6 – 27 VDC 6 – 27 VDC < 50 VDC (7 kHz max. frequency) < 50 VDC 0.3 VDC @ 1A 0.3 VDC @ 1A 0.5 A/pt. (1A/point for standard pt.) 1.0 A/point 15 µA @ 30 VDC 15 µA @ 30 VDC 2 A for 100 mS 2 A for 100 mS 20 - 28 VDC max 150mA 20 - 28 VDC max 150mA <10 µs < 10 µs <30 µs < 60 µs Logic Side Logic Side 6 channels/common x 1 bank None None

DL05 Micro PLC User Manual, 6th Edition, Rev. A

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

2–33

Page 61

Chapter 2: Installation, Wiring, and Specifications

D0–05DD I/O Wiring Diagram

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

These micro PLCs feature eight DC inputs and six DC outputs. The following diagram shows a typical field wiring example. The AC external power connection uses four terminals at the left as shown.

Power input wiring 95-240 VAC

20-28 VDC

12-24 VDC Source

6-27 VDC Sink Input point wiring

Output point wiring

12-24 VDC Source

12-24 VDC

Sink Source

Equivalent Circuit, High Speed Input (X0-X2)

20-28 VDC

Derating Chart for DC Outputs

2–34

Equivalent Circuit, Standard Input (X3-X7)

20-28 VDC

Equivalent Circuit, Standard Output (Y2-Y5)

Sink

The eight DC input channels use terminals in the middle of the connector. Inputs are organized into two banks of four. Each bank has an isolated common terminal, and may be wired as either sinking or sourcing Equivalent Circuit, DC Pulse inputs. The wiring example above Output (Y0-Y1) shows all commons connected together, but separate supplies and common circuits may be used. The equivalent circuits for standard inputs and the high-speed inputs are shown above. The six current sinking DC output channels use terminals on the right side of the connector. All outputs actually share the same electrical common. Note the requirement for external power on the end (right-most) terminal. The equivalent output circuit shows one channel of the bank of six.

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 62

Chapter 2: Installation, Wiring, and Specifications D0-05DD General Specifications External Power Requirements Communication Port 1, 9600 baud (Fixed), 8 data bits, 1 stop bit, odd parity

95 – 240 VAC, 30 VA maximum, K–Sequence (Slave), DirectNET (Slave), Modbus (Slave)

Communication Port 2, 9600 baud (default), 8 data bits, 1 stop bit, odd parity Programming cable type Operating Temperature Storage Temperature Relative Humidity Environmental air Vibration Shock Noise Immunity Terminal Type Wire Gauge

K–Sequence (Slave), DirectNET (Master/Slave), Modbus (Master/Slave) Non-sequence/print D2–DSCBL 32 to 131° F (0 to 55 C) –4 to 158° F (–20 to 70 C) 5 to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 NEMA ICS3–304 Removable One16 AWG or two 18 AWG, 24 AWG minimum

DC Input Specifications Parameter Min. - Max. Voltage Range Operating Voltage Range Peak Voltage Minimum Pulse Width ON Voltage Level OFF Voltage Level Max. Input Current Input Impedance Minimum ON Current Maximum OFF Current OFF to ON Response ON to OFF Response Status Indicators Commons

High–Speed Inputs, X0 – X2

Standard DC Inputs X3 – X7

10.8 – 26.4 VDC 10.8 – 26.4 VDC 12 – 24 VDC 12 – 24 VDC 30 VDC (5 kHz maximum frequency) 30 VDC 100 µs N/A > 9.0 VDC > 9.0 VDC < 2.0 VDC < 2.0 VDC 6mA @12VDC, 13mA @24VDC 4mA @12VDC, 8.5mA @24VDC 1.8 @ 12 – 24 VDC 2.8 @ 12 – 24 VDC >5 mA >4 mA < 0.5 mA <0.5 mA <100 µs 2 – 8 ms 4 ms typical < 100 µs 2 – 8 ms 4 ms typical Logic side Logic side 4 channels/common x 2 banks

DC Output Specifications Parameter Min. - Max. Voltage Range Operating Voltage Peak Voltage On Voltage Drop Max Current (resistive) Max leakage current Max inrush current External DC power required OFF to ON Response ON to OFF Response Status Indicators Commons Fuses

Pulse Outputs Y0 – Y1

Standard Outputs Y3 – Y5

5 – 30 VDC 5 – 30 VDC 6 – 27 VDC 6 – 27 VDC < 50 VDC (7 kHz max. frequency) < 50 VDC 0.3 VDC @ 1 A 0.3 VDC @ 1 A 0.5 A/pt., 1A/pt. as standard pt. 1.0 A/point 15 A @ 30 VDC 15 A @ 30 VDC 2 A for 100 ms 2 A for 100 ms 20 - 28 VDC Max 150mA 20 - 28 VDC Max 150mA < 10µ s < 10 µs < 30 µs < 60 µs Logic Side Logic Side 6 channels/common x 1 bank None (external recommended)

DL05 Micro PLC User Manual, 6th Edition, Rev. A

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

2–35

Page 63

Chapter 2: Installation, Wiring, and Specifications

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D 2–36

D0–05AA I/O Wiring Diagram The D0–05AA Micro PLC features eight AC inputs and six AC outputs. The following diagram shows a typical field wiring example. The AC external power connection uses four terminals at the left as shown.

Power input wiring 95-240 VAC 90-120 VAC

17-240 VAC Input point wiring

Output point wiring

12-24 VDC Source

Sink

Equivalent Input Circuit

Equivalent Output Circuit

The eight AC input channels use terminals in the middle of the connector. Inputs are organized into two banks of four. Each bank has an isolated common terminal. The wiring example above shows all commons connected together, but separate supplies and common circuits may be used. The equivalent input circuit shows one channel of a typical bank. The six output channels use terminals on the right side of the connector. Outputs are organized into two banks of three triac switches. Each bank has a common terminal. The wiring example above shows all commons connected together, but separate supplies and common circuits may be used. The Derating Chart for AC Outputs equivalent output circuit shows one channel of a typical bank.

DL05 Micro PLC User Manual, 6th Edition, Rev. A