DL05 Micro PLC User Manual, Volume 1 of 2: Chapter 2: Installation, Wiring and Specifications, pages 64 to 71

Pages 64 to 71 of 379, from DL05 Micro PLC User Manual, Volume 1 of 2

The original document is the PDF (5.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect D0-05AA

Page 64

Chapter 2: Installation, Wiring, and Specifications D0-05AA General Specifications External Power Requirements Communication Port 1, 9600 baud (Fixed), 8 data bits, 1 stop bit odd parity

95 – 240 VAC, 30 VA maximum, K–Sequence (Slave), DirectNET (Slave), Modbus (Slave)

Communication Port 2, 9600 baud (default) 8 data bits, 1 stop bit odd parity Programming cable type Operating Temperature Storage Temperature Relative Humidity Environmental air Vibration Shock Noise Immunity Terminal Type Wire Gauge

K–Sequence (Slave), DirectNET (Master/Slave), Modbus (Master/Slave) Non-sequence/print D2–DSCBL 32 to 131° F (0 to 55 C) –4 to 158° F (–20 to 70 C) 5 to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 NEMA ICS3–304 Removable One 16AWG or two 18AWG, 24AWG minimum

AC Input Specifications Input Voltage Range (Min. - Max.) Operating Voltage Range

80 – 132 VAC, 47 - 63 Hz 90 – 120 VAC, 47 - 63 Hz 8 mA @100 VAC at 50 Hz 10 mA @100 VAC at 60 Hz

Input Current

12 mA @132 VAC at 50 Hz 15 mA @132 VAC at 60 Hz 14 @ 50 Hz, 12 @ 60Hz > 6 mA @ 75 VAC < 2 mA @ 20 VAC < 40 ms < 40 ms Logic Side 4 channels/common x 2 banks

Max. Input Current Input Impedance ON Current/Voltage OFF Current/Voltage OFF to ON Response ON to OFF Response Status Indicators Commons

AC Output Specifications Output Voltage Range (Min. - Max.) Operating Voltage On Voltage Drop Max Current Max leakage current Max inrush current Minimum Load OFF to ON Response ON to OFF Response Status Indicators Commons Fuses

15 – 264 VAC, 47 – 63 Hz 17 – 240 VAC, 47 – 63 Hz 1.5 VAC (>50mA) 4.0 VAC (<50mA) 0.5 A/point, 1.5 A/common <4 mA @ 264 VAC 10 A for 10 ms 10 mA 1 ms 1 ms +1/2 cycle Logic Side 3 channels/common x 2 banks None (external recommended)

DL05 Micro PLC User Manual, 6th Edition, Rev. A

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

2–37

Page 65

Chapter 2: Installation, Wiring, and Specifications

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

D0–05DA I/O Wiring Diagram The D0–05DA Micro PLC features eight DC inputs and six AC outputs. The following diagram shows a typical field wiring example. The AC external power connection uses four terminals at the left as shown.

Power input wiring 95-240 VAC

12-24 VDC

17-240 VAC Source

Sink Input point wiring

Output point wiring

12-24 VDC Source

12-24 VDC

Sink Source

Equivalent Circuit, High Speed Input (X0-X2)

Equivalent Circuit, Output

Equivalent Circuit, Standard Input (X3-X7)

The eight DC input channels use terminals in the middle of the connector. Inputs are organized into two banks of four. Each bank has an isolated common terminal, and may be wired as sinking or sourcing inputs. The wiring example above shows all commons connected together, but separate supplies and common circuits may be used. The equivalent circuit for standard inputs and the highspeed input circuit are shown above. The six output channels use terminals on the right side of the connector. Outputs are organized into two banks of three triac switches. Each bank has a common terminal. The wiring example above shows all commons connected together, but separate supplies and common circuits may be used. The equivalent output circuit shows one channel of a typical bank.

Derating Chart for AC Outputs

2–38

Sink

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 66

Chapter 2: Installation, Wiring, and Specifications

D0-05DA General Specifications External Power Requirements Communication Port 1, 9600 baud (Fixed), 8 data bits, 1 stop bit, odd parity

95 – 240 VAC, 30 VA maximum, K–Sequence (Slave), DirectNET (Slave), Modbus (Slave)

Communication Port 2, 9600 baud (default), 8 data bits, 1 stop bit, odd parity Programming cable type Operating Temperature Storage Temperature Relative Humidity Environmental air Vibration Shock Noise Immunity Terminal Type Wire Gauge

K–Sequence (Slave), DirectNET (Master/Slave), Modbus (Master/Slave) Non-sequence/print D2–DSCBL 32 to 131° F (0 to 55 C) –4 to 158° F (–20 to 70 C) 5 to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 NEMA ICS3–304 Removable One 16 AWG or two 18 AWG, 24AWG minimum

DC Input Specifications Parameter Input Voltage Range Operating Voltage Range Maximum Voltage Minimum Pulse Width ON Voltage Level OFF Voltage Level Input Impedance Minimum ON Current Maximum OFF Current OFF to ON Response ON to OFF Response Status Indicators Commons

High–Speed Inputs, X0 – X2

Standard DC Inputs X3 – X7

10.8 – 26.4 VDC 10.8 – 26.4 VDC 12 – 24 VDC 12 – 24 VDC 30 VDC (5 kHz maximum frequency) 30 VDC 100 µs N/A > 10 VDC > 10 VDC < 2.0 VDC < 2.0 VDC 1.8 @ 12 – 24 VDC 2.8 @ 12 – 24 VDC >5 mA >4 mA < 0.5 mA <0.5 mA <100 µs 2 – 8 ms, 4 ms typical < 100 µs 2 – 8 ms, 4 ms typical Logic side Logic side 4 channels / common x 2 banks

AC Output Specifications Output Voltage Range (Min. - Max.) Operating Voltage On Voltage Drop Max Current Max leakage current Max inrush current Minimum Load OFF to ON Response ON to OFF Response Status Indicators Commons Fuses

15 – 264 VAC, 47 – 63 Hz 17 – 240 VAC, 47 – 63 Hz 1.5 VAC @> 50mA, 4 VAC @< 50mA 0.5 A/point, 1.5 A/common < 4 mA @ 264 VAC, 60Hz 10 A for 10 ms 10 mA 1 ms 1 ms +1/2 cycle Logic Side 3 channels / common x 2 banks None (external recommended)

DL05 Micro PLC User Manual, 6th Edition, Rev. A

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

2–39

Page 67

Chapter 2: Installation, Wiring, and Specifications

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

D0–05DR-D I/O Wiring Diagram These micro PLCs feature eight DC inputs and six relay contact outputs. The following diagram shows a typical field wiring example. The DC external power connection uses three terminals at the left as shown. 12-24V 20W max.

X0 - X7: Input

C3

Power input wiring 12-24 VDC 12-24 VDC 6-27 VDC Source

Sink Input point wiring

Output point wiring

12-24 VDC Source

12-24 VDC

Sink

Source

Equivalent Circuit, High-speed Input (X0-X2)

Equivalent Circuit, Standard Output

Derating Chart for Relay Outputs

2–40

Y0 - Y5: Output

Sink

Equivalent Circuit, Standard Input (X3-X7)

The eight DC input channels use terminals in the middle of the connector. Inputs are organized into two banks of four. Each bank has an isolated common terminal, and may be wired as either sinking or sourcing inputs. The wiring example above shows all commons connected together, but separate supplies and common circuits may be used. The equivalent circuit for standard inputs and the high-speed input circuit are shown above. The six output channels use terminals on the right side of the connector. Outputs are organized into two banks of three normally-open relay contacts. Each bank has a common terminal. The wiring example above shows all commons connected together, but separate supplies and common circuits may be used. The equivalent output circuit shows one channel of a typical bank. The relay contacts can switch AC or DC voltages.

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 68

Chapter 2: Installation, Wiring, and Specifications D0-05DR-D General Specifications External Power Requirements Communication Port 1, 9600 baud (Fixed), 8 data bits, 1 stop bit, odd parity

12 – 24 VDC, 20 W maximum, K–Sequence (Slave), DirectNET (Slave), Modbus (Slave)

Communication Port 2, 9600 baud (default), 8 data bits, 1 stop bit, odd parity Programming cable type Operating Temperature Storage Temperature Relative Humidity Environmental air Vibration Shock Noise Immunity Terminal Type Wire Gauge

K–Sequence (Slave), DirectNET (Master/Slave), Modbus (Master/Slave) Non-sequence/print D2–DSCBL 32 to 131° F (0 to 55 C) –4 to 158° F (–20 to 70 C) 5 to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 NEMA ICS3–304 Removable One 16AWG or two 18AWG, 24AWG minimum

DC Input Specifications Parameter Min. - Max. Voltage Range Operating Voltage Range Peak Voltage Minimum Pulse Width ON Voltage Level OFF Voltage Level Input Impedance Max. Input Current Minimum ON Current Maximum OFF Current OFF to ON Response ON to OFF Response Status Indicators Commons

High–Speed Inputs, X0 – X2

Standard DC Inputs X3 – X7

10.8 – 26.4 VDC 10.8 – 26.4 VDC 12 -24 VDC 12 -24 VDC 30 VDC (5 kHz maximum frequency) 30 VDC 100 µs N/A > 10 VDC > 10 VDC < 2.0 VDC < 2.0 VDC 1.8 @ 12 – 24 VDC 2.8 @ 12 – 24 VDC 6mA @12VDC ,13mA @24VDC 4mA @12VDC, 8.5mA @24VDC >5 mA >4 mA < 0.5 mA <0.5 mA <100 µs 2 – 8 ms, 4 ms typical < 100 µs 2 – 8 ms, 4 ms typical Logic side Logic side 4 channels / common x 2 banks

Relay Output Specifications Output Voltage Range (Min. - Max.) Operating Voltage Output Current Maximum Voltage Max leakage current Smallest Recommended Load OFF to ON Response ON to OFF Response Status Indicators Commons Fuses

5 -264 VAC (47 -63 Hz), 5 - 30 VDC 6 -240 VAC (47 -63 Hz), 6 - 27 VDC 2A/point 6A/common 264 VAC, 30 VDC 0.1 mA @264 VAC 5 mA < 15 ms < 10 ms Logic Side 3 channels/common x 2 banks None (external recommended)

DL05 Micro PLC User Manual, 6th Edition, Rev. A

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

2–41

Page 69

Chapter 2: Installation, Wiring, and Specifications

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

D0–05DD–D I/O Wiring Diagram These micro PLCs feature eight DC inputs and six DC outputs. The following diagram shows a typical field wiring example. The DC external power connection uses four terminals at the left as shown. Y0 - Y5: Output

Power input wiring 12-24 VDC 20-28 VDC 12-24 VDC Source

6-27 VDC

Sink Input point wiring

Output point wiring

12-24 VDC Source

12-24 VDC

Sink Source

Equivalent Circuit, High Speed Input (X0-X2)

20-28 VDC

Equivalent Circuit, Standard Output (Y2-Y5)

Sink

Equivalent Circuit, Standard Input (X3-X7)

The eight DC input channels use terminals in the middle of the connector. Inputs are organized into two banks of four. Each bank has an isolated common terminal, and may be wired as either sinking or sourcing inputs. The wiring example above shows all commons Equivalent Circuit, Pulse connected together, but separate Output (Y0-Y1) supplies and common circuits may be used. The equivalent circuit for standard inputs and the highspeed input circuit are shown above. The six current sinking DC output channels use terminals on the right side of the connector. All outputs actually share the same electrical common. Note the requirement for external power on the end (right-most) terminal. The equivalent output circuit shows one channel of the bank of six. 20-28 VDC

Derating Chart for DC Outputs

2–42

X0 - X7: Input

12-24V 20W max.

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 70

Chapter 2: Installation, Wiring, and Specifications D0-05DD-D General Specifications External Power Requirements Communication Port 1, 9600 baud (Fixed), 8 data bits, 1 stop bit, odd parity

12 – 24 VDC, 20 W maximum, K–Sequence (Slave), DirectNET (Slave), Modbus (Slave)

Communication Port 2, 9600 baud (default), 8 data bits, 1 stop bit, odd parity Programming cable type Operating Temperature Storage Temperature Relative Humidity Environmental air Vibration Shock Noise Immunity Terminal Type Wire Gauge

K–Sequence (Slave), DirectNET (Master/Slave), Modbus (Master/Slave) Non-sequence/print D2–DSCBL 32 to 131° F (0 to 55 C) –4 to 158° F (–20 to 70 C) 5 to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 NEMA ICS3–304 Removable One 16AWG or two 18AWG, 24AWG minimum

DC Input Specifications Parameter Min. - Max. Voltage Range Operating Voltage Range Peak Voltage Minimum Pulse Width ON Voltage Level OFF Voltage Level Max. Input Current Input Impedance Minimum ON Current Maximum OFF Current OFF to ON Response ON to OFF Response Status Indicators Commons

High–Speed Inputs, X0 – X2

Standard DC Inputs X3 – X7

10.8 – 26.4 VDC 10.8 – 26.4 VDC 12 – 24 VDC 12 – 24 VDC 30 VDC (5 kHz maximum frequency) 30 VDC 100 µs N/A >9.0 VDC > 9.0 VDC < 2.0 VDC < 2.0 VDC 6mA @12VDC, 13mA @24VDC 4mA @12VDC, 8.5mA @24VDC 1.8 @ 12 – 24 VDC 2.8 @ 12 – 24 VDC >5 mA >4 mA < 0.5 mA <0.5 mA <100 µs 2 – 8 ms, 4 ms typical < 100 µs 2 – 8 ms, 4 ms typical Logic side Logic side 4 channels / common x 2 banks

DC Output Specifications Parameter Min. - Max. Voltage Range Operating Voltage Peak Voltage On Voltage Drop Max Current (resistive) Max leakage current Max inrush current External DC power required OFF to ON Response ON to OFF Response Status Indicators Commons Fuses

Pulse Outputs, Y0 – Y1

Standard Outputs, Y3 – Y5

5 – 30 VDC 5 – 30 VDC 6 – 27 VDC 6 – 27 VDC < 50 VDC (7 kHz max. frequency) < 50 VDC 0.3 VDC @ 1 A 0.3 VDC @ 1 A 0.5 A/pt., 1A/pt. as standard pt. 1.0 A/point 15 µA @ 30 VDC 15 µA @ 30 VDC 2 A for 100 ms 2 A for 100 ms 20 - 28 VDC Max 150mA 20 - 28 VDC Max 150mA < 10 µs < 10 µs < 30 µs < 60 µs Logic Side Logic Side 6 channels / common x 1 bank None (external recommended)

DL05 Micro PLC User Manual, 6th Edition, Rev. A

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

2–43

Page 71

Chapter 2: Installation, Wiring, and Specifications

A Glossary of Specification Terms Discrete Input 2 One of eight input connections to the PLC which converts an electrical signal from a field device to a binary status (off or on), which is read by the internal CPU each PLC scan. 3 Discrete Output One of six output connections from the PLC which converts an internal ladder program D result (0 or 1) to turn On or Off an output switching device. This enables the program to turn on and off large field loads. 5 I/O Common A connection in the input or output terminals which is shared by multiple I/O circuits. It 6 usually is in the return path to the power supply of the I/O circuit. Input Voltage Range 7 The operating voltage range of the input circuit. Maximum Voltage 8 Maximum voltage allowed for the input circuit. ON Voltage Level 9 The minimum voltage level at which the input point will turn ON. OFF Voltage Level 10 The maximum voltage level at which the input point will turn OFF. 11 Input Impedance Input impedance can be used to calculate input current for a particular operating voltage. 12 Input Current Typical operating current for an active (ON) input. 13 Minimum ON Current The minimum current for the input circuit to operate reliably in the ON state. 14 Maximum OFF Current The maximum current for the input circuit to operate reliably in the OFF state. A OFF to ON Response The time the module requires to process an OFF to ON state transition. B ON to OFF Response The time the module requires to process an ON to OFF state transition. C Status Indicators The LEDs that indicate the ON/OFF status of an input or output point. All LEDs on DL05 D Micro PLCs are electrically located on the logic side of the input or output circuit.

2–44