Page 37
Chapter 2: Installation, Wiring, and Specifications
A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D
2–10
Environmental Specifications The following table lists the environmental specifications that generally apply to DL05 Micro PLCs. The ranges that vary for the Handheld Programmer are noted at the bottom of this chart. Certain output circuit types may have derating curves, depending on the ambient temperature and the number of outputs ON. Please refer to the appropriate section in this chapter pertaining to your particular DL05 PLC. * Operating temperature for the Handheld Programmer and the DV–1000 is 32° to 122° F (0° to 50° C) Storage temperature for the Handheld Programmer and the DV–1000 is –4° to 158° F (–20° to70° C). ** Equipment will operate down to 5% relative humidity. However, static electricity problems occur much more frequently at low humidity levels (below 30%). Make sure you take adequate precautions when you touch the equipment. Consider using ground straps, antistatic floor coverings, etc. if you use the equipment in low-humidity environments. Environmental Specifications Specification
Rating
Storage temperature Ambient operating temperature* Ambient humidity** Vibration resistance Shock resistance Noise immunity Atmosphere Agency approvals
–4° F to 158° F (–20° C to 70° C) 32° F to 131° F (0° C to 55° C) 5% – 95% relative humidity (non–condensing) MIL STD 810C, Method 514.2 MIL STD 810C, Method 516.2 NEMA (ICS3–304) No corrosive gases UL, CE, FCC class A
Agency Approvals Some applications require agency approvals for particular components. The DL05 Micro PLC agency approvals are listed below: • UL (Underwriters’ Laboratories, Inc.) • CUL (Canadian Underwriters’ Laboratories, Inc.) • CE (European Economic Union)
Marine Use American Bureau of Shipping (ABS) certification requires flame-retarding insulation as per 4-8-3/5.3.6(a). ABS will accept Navy low smoke cables, cable qualified to NEC “Plenum rated” (fire resistant level 4), or other similar flammability resistant rated cables. Use cable specifications for your system that meet a recognized flame retardant standard (i.e. UL, IEEE, etc.), including evidence of cable test certification (i.e. tests certificate, UL file number, etc.). NOTE: Wiring needs to be “low smoke” per the above paragraph. Teflon coated wire is also recommended.
DL05 Micro PLC User Manual, 6th Edition, Rev. A
Page 38
Chapter 2: Installation, Wiring, and Specifications
Wiring Guidelines
A 2 3 D 5 6 7 8 WARNING: Once the power wiring is connected, secure the terminal block cover in the closed 9 position. When the cover is open there is a risk of electrical shock if you accidentally touch the connection terminals or power wiring. 10 Fuse Protection for Input Power There are no internal fuses for the input power circuits, so external circuit protection is 11 needed to ensure the safety of service personnel and the safe operation of the equipment itself. To meet UL/CUL specifications, the input power must be fused. Depending on the type of 12 input power being used, follow these fuse protection recommendations: 208/240 VAC Operation 13 When operating the unit from 208/240 VAC, whether the voltage source is a step-down transformer or from two phases, fuse both the line (L) and neutral (N) leads. The recommended fuse size is 1A, such as AutomationDirect’s AGC1, fast-acting fuse. 14 110/125 VAC Operation When operating the unit from 110/125 VAC, it is only necessary to fuse the line (L) lead; it is A not necessary to fuse the neutral (N) lead. The recommended fuse size is 1.0A. B C D Connect the power input wiring for the DL05. Observe all precautions stated earlier in this manual. Follow the guidelines in this chapter. When the wiring is complete, close the connector covers. Do not apply power at this time. 110/220 VAC Power Input
X0 - X7: Input
12/24 VDC Power Input 12-24 VDC 20 W max
Y0 - Y5: Output
X0 - X7: Input
Y0 - Y5: Output
C3
LGN 95 - 240 VAC
G
DL05 Micro PLC User Manual, 6th Edition, Rev. A
2–11
Page 39
Chapter 2: Installation, Wiring, and Specifications
A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D
12/24 VDC Operation When operating at these lower DC voltages, wire gauge size is just as important as proper fusing techniques. Using large conductors minimizes the voltage drop in the conductor. Each DL05 input power terminal can accommodate one 16 AWG wire or two 18 AWG wires. A DC failure can maintain an arc for much longer time and distance than AC failures. Typically, the main bus is fused at a higher level than the branch device, which in this case is the DL05. The recommended fuse size for the branch circuit to the DL05 is 1A, such as AutomationDirect’s AGC1, fast-acting fuse.
External Power Source The power source must be capable of suppling voltage and current complying with individual Micro PLC specifications, according to the following specifications: Power Source Specifications Item Input Voltage Range Maximum Inrush Current Maximum Power Voltage Withstand (dielectric) Insulation Resistance
DL05 VAC Powered Units
DL05 VDC Powered Units
110/220 VAC (95–240 VAC) 12–24 VDC (10.8–26.4 VDC) 13 A, 1ms (95–240 VAC) 10A < 1ms 15 A, 1ms (240–264 VAC) 30 VA 20 W 1 minute @ 1500 VAC between primary, secondary, field ground > 10 at 500 VDC
NOTE:The rating between all internal circuits is BASIC INSULATION ONLY. NOTE: It is possible to use an uninterruptible power supply (UPS); however, the output must be a sinusoidal waveform for the PLC to perform properly.
Planning the Wiring Routes The following guidelines provide general information on how to wire the I/O connections to DL05 Micro PLCs. For specific information on wiring a particular PLC refer to the corresponding specification sheet further in this chapter. 1. Each terminal connection of the DL05 PLC can accept one 16 AWG wire or two 18 AWG size wires. Do not exceed this recommended capacity. 2. Always use a continuous length of wire. Do not splice wires to attain a needed length. 3. Use the shortest possible wire length. 4. Use wire trays for routing where possible. 5. Avoid running wires near high energy wiring. 6. Avoid running input wiring close to output wiring where possible. 7. To minimize voltage drops when wires must run a long distance, consider using multiple wires for the return line. 8. Avoid running DC wiring in close proximity to AC wiring where possible. 9. Avoid creating sharp bends in the wires. 10. Install the recommended powerline filter to reduce power surges and EMI/RFI noise.
2–12
DL05 Micro PLC User Manual, 6th Edition, Rev. A
Page 40
Chapter 2: Installation, Wiring, and Specifications
Fuse Protection for Input and Output Circuits
A 2 3 D 5 6 7 8 9 10 11 12 13 I/O Point Numbering 14 All DL05 Micro PLCs have a fixed I/O configuration. It follows the same octal numbering system used on other DirectLogic family PLCs, starting at X0 and Y0. The letter X is always used to indicate inputs and the letter Y is always used for outputs. A The I/O numbering always starts at zero and does not include the digits 8 or 9. The reference addresses are typically assigned in groups of 8 or 16, depending on the number of points in B an I/O group. For the DL05 the eight inputs use reference numbers X0 – X7. The six output points use references Y0 – Y5. C If an optional input module is installed in the option slot, the reference numbers are X100 – X107. A typical output module installed in the option slot will have references Y100 – Y107. D See the DL05/06 Options Modules User Manual (D0-OPTIONS-M) for addressing other Input and Output circuits on DL05 Micro PLCs do not have internal fuses. In order to protect your Micro PLC, we suggest you add external fuses to your I/O wiring. A fast-blow fuse, with a lower current rating than the I/O bank’s common current rating can be wired to each common. Or, a fuse with a rating of slightly less than the maximum current per output point can be added to each output. Refer to the Micro PLC specification tables further in this chapter to find the maximum current per output point or per output common. Adding the external fuse does not guarantee the prevention of Micro PLC damage, but it will provide added protection.
External Fuses (shown with DIN Rail, Fuse Blocks)
optional modules.
DL05 Micro PLC User Manual, 6th Edition, Rev. A
2–13
Page 41
Chapter 2: Installation, Wiring, and Specifications
A System Wiring Strategies The DL05 Micro PLC is very flexible and will work in many different wiring configurations. By studying this section before actual installation, you can probably find the best wiring 2 strategy for your application. This will help to lower system cost, wiring errors, and avoid safety problems. 3 PLC Isolation Boundaries PLC circuitry is divided into three main regions separated by isolation boundaries, shown in D the drawing below. Electrical isolation provides safety, so that a fault in one area does not damage another. A powerline filter will provide isolation between the power source and the power supply. A transformer in the power supply provides magnetic isolation between the 5 primary and secondary sides. Opto-couplers provide optical isolation in Input and Output circuits. This isolates logic circuitry from the field side, where factory machinery connects. 6 Note that the discrete inputs are isolated from the discrete outputs, because each is isolated from the logic side. Isolation boundaries protect the operator interface (and the operator) from power input faults or field wiring faults. When wiring a PLC, it is extremely important to 7 avoid making external connections which connect to the logic side of the PLC circuits. 8 Primary Side Secondary,or Field Side Logic side PLC 9 Input Circuit Main Power CPU 10 Output Supply Circuit 11 12 13 The next figure shows the internal layout of DL05 PLCs, as viewed from the front panel. To programming device 14 or operator interface DL05 PLC A 2 Comm. CPU Ports B Main Power Supply C Output Circuit Input Circuit D Discrete inputs
Power input
Filter
Discrete outputs
Isolation Boundary
Power Input
2–14
Filter
8 discrete inputs
Programming Device or Operator Interface
Commons 6 discrete outputs
DL05 Micro PLC User Manual, 6th Edition, Rev. A
Isolation Boundary
Commons
Page 42
Chapter 2: Installation, Wiring, and Specifications
Connecting Operator Interface Devices
A 2 3 D 5 6 Operator interface panels require separate power and communications connections. Connect the DL05 with the proper cable and power supply for your application. 7 8 9 Connecting Programming Devices 10 DL05 Micro PLCs are programmed using DirectSOFT 5 programming software on a PC. Limited programming can be accomplished with a handheld programmer. The DL05 can be 11 interfaced to the PC with either a serial cable shown below or a Ethernet cable (Ethernet requires either an H0-ECOM or H0-ECOM100 module installed in the option slot). See the AutomationDirect catalog to chose the cable or Ethernet card for whichever method will 12 meet your system requirements. 13 14 A The D2-HPP Handheld Programmer comes with a communications cable. For a replacement B cable, order a DV-1000CBL. C D Operator interfaces require data and power connections. Operator interfaces with a large CRT usually require separate AC power. However, some small operator interface devices, such as the DV-1000 Data Access Unit, may be powered directly from the DL05 Micro PLC. Connect the DV-1000 to communication port 1 on the DL05 Micro PLC with a DV1000CBL. A single cable contains transmit/receive data wires and +5V power. DL05 Micro PLC
RJ12 phone style
DL05 Micro PLC
DL05 Micro PLC
DL05 Micro PLC
RJ12 phone style
RJ12 phone style
RJ12 phone style
RJ12 phone style
DV-1000
15-pin D-shell male
9-pin D-shell female
RJ12 phone style
D2–HPP
(cable comes with HPP)
DL05 Micro PLC User Manual, 6th Edition, Rev. A
2–15
Page 43
Chapter 2: Installation, Wiring, and Specifications
A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D 2–16
Sinking/Sourcing Concepts Before going further in our study of wiring strategies, we must have a solid understanding of “sinking” and “sourcing” concepts. Use of these terms occurs frequently in input or output circuit discussions. It is the goal of this section to make these concepts easy to understand, further ensuring your success in installation. First we give the following short definitions, followed by practical applications. Sinking = Path to supply ground (–) Sourcing = Path to supply source (+) First you will notice that these are only associated with DC circuits and not AC, because of the reference to (+) and (–) polarities. Therefore, sinking and sourcing terminology only applies to DC input and output circuits. Input and output points that are either sinking or sourcing can conduct current in only one direction. This means it is possible to connect the external supply and field device to the I/O point with current trying to flow in the wrong direction, and the circuit will not operate. However, we can successfully connect the supply and field device every time by understanding “sourcing” and “sinking”. For example, the figure to the right depicts a “sinking” input. To properly connect the external supply, we just have to connect it so the PLC Input input provides a path to ground (–). So, we start at (sinking) the PLC input terminal, follow through the input sensing circuit, exit at the common terminal, and + Input connect the supply (–) to the common terminal. Sensing – By adding the switch, between the supply (+) and the input, we have completed the circuit. Current Common flows in the direction of the arrow when the switch is closed. By applying the circuit principle above to the four possible combinations of input/output sinking/sourcing types, we have the four circuits as shown below. DL05 Micro PLCs provide all except the sourcing output I/O circuit types. Sinking Input
Sinking Output Input
PLC
PLC
Output
Load
+ –
+ Common
Input Sensing
Sourcing Input
–
Common
Sourcing Output
Common + –
Output Switch
Input
PLC Input Sensing
PLC
Common +
Output Switch
DL05 Micro PLC User Manual, 6th Edition, Rev. A
Output
– Load
Page 44
Chapter 2: Installation, Wiring, and Specifications
I/O “Common” Terminal Concepts
A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B The following label is for DC output versions. One common is provided for all of the outputs and the terminal on the bottom right accepts power for the output stage. C D PLC
In order for a PLC I/O circuit to operate, Field Main Path current must enter at one terminal and exit I/O Device (I/O point) Circuit at another. This means at least two terminals + are associated with every I/O point. In the – figure to the right, the Input or Output Return Path terminal is the main path for the current. One additional terminal must provide the return path to the power supply. PLC If we had unlimited space and budget for I/O terminals, then every I/O point could Input Sensing have two dedicated terminals just as the Input 1 figure above shows. However, providing this level of flexibility is not practical or Input 2 even necessary for most applications. So, Input 3 most Input or Output point groups on PLCs share the return path among two or Input 4 more I/O points. The figure to the right + shows a group (or bank) of 4 input points which share a common return path. In – Common this way, the four inputs require only five terminals instead of eight. Note: In the circuit above, the current in the common path is 4 times any channel’s input current when all inputs are energized. This is especially important in output circuits, where heavier gauge wire is sometimes necessary on commons. Most DL05 input and output circuits are grouped into banks that share a common return path. The best indication of I/O The I/O common grouping bar, labeled at the right, occurs in the section of wiring label below it. It indicates X0, X1, X2, and X3 share the common terminal located to the left of X1. The following complete label shows two banks of four inputs and two banks of three outputs. One common is provided for each bank.
AC(L) AC(N)
+V
DL05 Micro PLC User Manual, 6th Edition, Rev. A
2–17
Page 45
Chapter 2: Installation, Wiring, and Specifications
A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D
Connecting DC I/O to Solid State Field Devices In the previous section on Sourcing and Sinking concepts, we explained that DC I/O circuits sometimes will only allow current to flow one way. This is also true for many of the field devices which have solid-state (transistor) interfaces. In other words, field devices can also be sourcing or sinking. When connecting two devices in a series DC circuit, one must be wired as sourcing and the other as sinking.
Solid State Input Sensors The DL05’s DC inputs are flexible in that they detect current flow in either direction, so they can be wired as either sourcing or sinking. In the following circuit, a field device has an opencollector NPN transistor output. It sinks current from the PLC input point, which sources current. The power supply can be the FA-24PS +24 VDC power supply or another supply (+12 VDC or +24VDC), as long as the input specifications are met. Field Device
PLC DC Input Input (sourcing)
Output (sinking) Supply Ground
–
+
Common
In the next circuit, a field device has an open-emitter PNP transistor output. It sources current to the PLC input point, which sinks the current back to ground. Since the field device is sourcing current, no additional power supply is required. Field Device =>
PLC DC Input Input (sinking) Output (sourcing) Ground
Common
Solid State Output Loads Sometimes an application requires connecting a PLC output point to a solid state input on a device. This type of connection is usually made to carry a low-level signal, not to send DC power to an actuator. The DL05’s DC outputs are sinking-only. This means that each DC output provides a path to ground when it is energized. Also, remember that all six outputs have the same electrical common, even though there are two common terminal screws. Finally, recall that the DC output circuit requires power (20 – 28 VDC) from an external power source. In the following circuit, the PLC output point sinks current to the output common when energized. It is connected to a sourcing input of a field device input. PLC DC Output +DC Power
Field Device Power
=>
Output (sinking)
+
Common
–
Input (sourcing) 20-28 VDC
2–18
DL05 Micro PLC User Manual, 6th Edition, Rev. A
Ground