Page 28

INSTALLATION, WIRING, AND SPECIFICATIONS

C HAPTER HAPTER

2

In This Chapter: Safety Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2–2 Orientation to DL05 Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . .2–5 Mounting Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2–7 Wiring Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2–11 System Wiring Strategies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2–14 Wiring Diagrams and Specifications . . . . . . . . . . . . . . . . . . . . . . . .2–28 Glossary of Specification Terms . . . . . . . . . . . . . . . . . . . . . . . . . . .2–44

Page 29

Chapter 2: Installation, Wiring, and Specifications

A Safety Guidelines NOTE: Products with CE marks perform their required functions safely and adhere to relevant standards as 2 specified by CE directives provided they are used according to their intended purpose and that the instructions in this manual are adhered to. The protection provided by the equipment may be impaired if this equipment 3 is used in a manner not specified in this manual. A listing of our international affiliates is available on our Web site: http://www.automationdirect.com D WARNING: Providing a safe operating environment for personnel and equipment is your responsibility and should be your primary goal during system planning and installation. Automation 5 systems can fail and may result in situations that can cause serious injury to personnel or damage to equipment. Do not rely on the automation system alone to provide a safe operating environment. You should use external electromechanical devices, such as relays or limit switches, that are 6 independent of the PLC application to provide protection for any part of the system that may cause personal injury or damage. Every automation application is different, so there may be special 7 requirements for your particular application. Make sure you follow all national, state, and local government requirements for the proper installation and use of your equipment. 8 Plan for Safety The best way to provide a safe operating environment is to make personnel and equipment 9 safety part of the planning process. You should examine every aspect of the system to determine which areas are critical to operator or machine safety. If you are not familiar with PLC system installation practices, or your company does not have established installation 10 guidelines, you should obtain additional information from the following sources. • NEMA, The National Electrical Manufacturers Association, located in Washington, D.C., 11 publishes many different documents that discuss standards for industrial control systems. You can order these publications directly from NEMA. Some of these include: 12 ICS 1, General Standards for Industrial Control and Systems ICS 3, Industrial Systems ICS 6, Enclosures for Industrial Control Systems 13 • NEC, The National Electrical Code provides regulations concerning the installation and use of various types of electrical equipment. Copies of the NEC Handbook can often be obtained from your local electrical equipment distributor or your local library. 14 • Local and State Agencies, many local governments and state governments have additional requirements above and beyond those described in the NEC Handbook. Check with your local A Electrical Inspector or Fire Marshall office for information. B C D 2–2

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 30

Chapter 2: Installation, Wiring, and Specifications

Three Levels of Protection

A 2 • Emergency stop switch for disconnecting system power • Mechanical disconnect for output module power 3 • Orderly system shutdown sequence in the PLC control program D Emergency Stops 5 It is recommended that emergency stop circuits be incorporated into the system for every machine controlled by a PLC. For maximum safety in a PLC system, these circuits must not be wired into the controller, but should be hardwired external to the PLC. The emergency 6 stop switches should be easily accessed by the operator and are generally wired into a master control relay (MCR) or a safety control relay (SCR) that will remove power from the PLC 7 I/O system in an emergency. MCRs and SCRs provide a convenient means for removing power from the I/O system 8 during an emergency situation. By de-energizing an MCR (or SCR) coil, power to the input (optional) and output devices is removed. This event occurs when any emergency stop switch opens. However, the PLC continues to receive power and operate even though all its inputs 9 and outputs are disabled. The MCR circuit could be extended by placing a PLC fault relay (closed during normal PLC 10 operation) in series with any other emergency stop conditions. This would cause the MCR circuit to drop the PLC I/O power in case of a PLC failure (memory error, I/O 11 communications error, etc.). 12 13 14 A B C D The publications mentioned provide many ideas and requirements for system safety. At a minimum, you should follow these regulations. Also, you should use the following techniques, which provide three levels of system control.

Use E-Stop and Master Relay

E STOP

Guard Line Switch

Emergency Stop

Power On

Guard ? Link

Master Relay

MCR

L1 to Output Commons

Saw Arbor

MCR

L1 to Input Commons (optional)

DL05 Micro PLC User Manual, 6th Edition, Rev. A

2–3

Page 31

Chapter 2: Installation, Wiring, and Specifications

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D 2–4

Emergency Power Disconnect A properly rated emergency power disconnect should be used to power the PLC controlled system as a means of removing the power from the entire control system. It may be necessary to install a capacitor across the disconnect to protect against a condition known as “outrush”. This condition occurs when the output Triacs are turned off by powering off the disconnect, thus causing the energy stored in the inductive loads to seek the shortest distance to ground, which is often through the Triacs. After an emergency shutdown or any other type of power interruption, there may be requirements that must be met before the PLC control program can be restarted. For example, there may be specific register values that must be established (or maintained from the state prior to the shutdown) before operations can resume. In this case, you may want to use retentive memory locations, or include constants in the control program to insure a known starting point.

Orderly System Shutdown Ideally, the first level of fault detection is the PLC control program, which can identify machine problems. Certain shutdown sequences should be performed. The types of problems are usually things such as jammed parts, etc. that do not pose a risk of personal injury or equipment damage. Jam Detect

WARNING: The control program must not be the only form of protection for any problems that may result in a risk of personal injury or equipment damage.

Turn off Saw RST RST Retract

Class 1, Division 2 Approval This equipment is suitable for use in Class 1, Division 2, groups A, B, C and D or nonhazardous locations only. WARNING: - Explosion Hazard! Substitution of components may impair suitability for Class 1, Division 2. WARNING: - Do not disconnect equipment unless power has been switched off or area is known to be non-hazardous.

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 32

Chapter 2: Installation, Wiring, and Specifications

Orientation to DL05 Front Panel

A 2 3 D 5 6 7 8 9 10 The upper section of the connector accepts external power connections on the two left-most 11 terminals. From left to right, the next five terminals are one of the input commons (C0) and input connections X1, X3, X4, and X6. The remaining four connections are an output 12 common (C2) and output terminals Y1, Y3, and Y5. The lower section of the connector has the chassis ground (G) and the logic ground (LG) on the two left-most terminals. The next two terminals are for the inputs X0 and X2. Next is the 13 other input common (C1) followed by inputs X5 and X7. The last four terminals are for outputs Y0, Y2, Y4, and the second output common (C3). On DC output units, the end 14 terminal on the right accepts power for the output stage. An option slot is located on the right end of the PLC. This is where the simulator module can A be installed for testing. Option module descriptions available for the DL05 can be found either in the DL05/DL06 Options Modules User Manual, D0-OPTIONS-M, in our catalog or on our website. B WARNING: For some applications, field device power may still be present on the terminal block even though the Micro PLC is turned off. To minimize the risk of electrical shock, check all field C device power before you expose or remove either connector wire from under a terminal block, or two 18 AWG wires (one on each side of the screw). D Most connections, indicators, and labels on the DL05 Micro PLCs are located on its front panel. The communication ports are located on the top side of the PLC. Please refer to the drawing below. Mode Switch

Mounting tab

Communication Ports

Output Status Indicators

Input Status Indicators

Status Indicators

Mounting tab

External Power Inputs

Discrete Input Discrete Output Output Circuit Power Input Terminals Terminals (for DC output versions only)

DL05 Micro PLC User Manual, 6th Edition, Rev. A

2–5

Page 33

Chapter 2: Installation, Wiring, and Specifications

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D 2–6

Connector Removal All of the terminals for the DL05 are contained on one connector block. In some instances, it may be desirable to remove the connector block for easy wiring. The connector is designed for easy removal with just a small screwdriver. The drawing below shows the procedure for removal at one end. Connector Removal 1. Loosen the retention screws on each end of the connector block.

2. From the center of the connector block, pry upward with the screwdriver until the connector is loose. The terminal block connector on DL05 PLCs has regular screw terminals, which will accept either standard blade-type or #1 Philips screwdriver tips. Use No. 16 to 18 AWG solid/stranded wire. The maximum torque is 0.343Nm (3.036 inch-lbs). Spare terminal block connectors and connector covers may be ordered by individual part numbers: Spare Parts -Terminal Block and Cover Part Number

Qty Per Package

Description

F0-IOCON

2

D0-AAC-1

1 each

DL05 I/O Terminal Block DL05 I/O Terminal Block, I/O Terminal Block Cover, and Option Slot Cover

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 34

Chapter 2: Installation, Wiring, and Specifications

Mounting Guidelines In addition to the panel layout guidelines, other specifications can affect the definition and installation of a PLC system. Always consider the following: • Environmental Specifications • Power Requirements • Agency Approvals • Enclosure Selection and Component Dimensions

Unit Dimensions The following diagram shows the outside dimensions and mounting hole locations for all versions of the DL05. Make sure you follow the installation guidelines to allow proper spacing from other components. 0.39" 10mm 3.94" 100mm 0.39" 10mm

2.56" 65mm 0.47" 12mm

3.34" 85mm

0.71" 18mm 1.46" 37mm

4.72" 120mm

3.74" 95mm

0.24" mounting tab 6mm 2.68" 68mm (DIN Rail)

Enclosures Your selection of a proper enclosure is important to ensure safe and proper operation of your DL05 system. Applications of DL05 systems vary and may require additional features. The minimum considerations for enclosures include: • Conformance to electrical standards • Protection from the elements in an industrial environment • Common ground reference • Maintenance of specified ambient temperature • Access to equipment • Security or restricted access

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

• Sufficient space for proper installation and maintenance of equipment

DL05 Micro PLC User Manual, 6th Edition, Rev. A

2–7

Page 35

Chapter 2: Installation, Wiring, and Specifications

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D 2–8

Panel Layout & Clearances There are many things to consider when designing the panel layout. The following items correspond to the diagram shown. Note: there may be additional requirements, depending on your application and use of other components in the cabinet. 1. Mount the PLCs horizontally as shown below to provide proper ventilation. You cannot mount the DL05 units vertically, upside down, or on a flat horizontal surface. If you place more than one unit in a cabinet, there must be a minimum of 7.2” (183mm) between the units. 2. Provide a minimum clearance of 2” (50mm) between the unit and all sides of the cabinet. Note, remember to allow for any operator panels or other items mounted in the door.

OK

AirFlow

3. There should also be at least 3” (78mm) of clearance between the unit and any wiring ducts that run parallel to the terminals. 4. The ground terminal on the DL05 base must be connected to a single point ground. Use copper stranded wire to achieve a low impedance. Copper eye lugs should be crimped and soldered to the ends of the stranded wire to ensure good surface contact. Remove anodized finishes and use copper lugs and star washers at termination points. NOTE: There is a minimum clearance requirement of 2” (51cm) between the panel door (or any devices mounted in the panel door) and the nearest DL05 component.

Panel

Temperature Probe

2" 50mm min

Ground braid copper lugs

Power Source 2" 50mm min

Star Washers

Star Washers

Panel or single point ground

2" 50mm min

BusB ar

Pane 5. There must be a single point ground (i.e. l Gro und Term copper bus bar) for all devices in the panel requiring an inal earth ground return. The single point of ground must be connected to the panel ground termination. The panel ground termination must be connected to earth ground. Minimum wire sizes, color coding, and general safety practices should comply with appropriate electrical codes and standards for your area.

6. A good common ground reference (Earth ground) is essential for proper operation of the DL05. One side of all control and power circuits and the ground lead on flexible shielded cable must be properly connected to common ground reference. Methods which provide a good common ground reference, include: a) Installing a ground rod as close to the panel as possible. b) Connection to incoming power system ground.

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 36

Chapter 2: Installation, Wiring, and Specifications 7. Evaluate any installations where the ambient temperature may approach the lower or upper limits of the specifications. If you suspect the ambient temperature will not be within the operating specification for the DL05 system, measures such as installing a cooling/heating source must be taken to get the ambient temperature within the range of specifications.

A 2 8. The DL05 systems are designed to be powered by 95-240 VAC or 12–24 VDC normally available throughout an industrial environment. Electrical power in some areas where the PLCs are installed is not always stable and storms can cause power surges. Due to this, powerline filters are recommended 3 for protecting the DL05 PLCs from power surges and EMI/RFI noise. The Automation Powerline Filter, for use with 120 VAC and 240 VAC, 1–5 Amps (part number APF120N05), is an excellent D choice, however, you can use a filter of your choice. These units install easily between the power source and the PLC. 5 NOTE: If you are using other components in your system, make sure you refer to the appropriate manual to determine how those units can affect mounting dimensions. 6 Using DIN Rail Mounting Rails DL05 Micro PLCs can be secured to a panel by using mounting rails. We recommend rails 7 that conform to DIN EN standard 50 022. They are approximately 35mm high, with a depth of 7mm. If you mount the Micro PLC on a rail, do consider using end brackets on each side 8 of the PLC. The end bracket helps keep the PLC from sliding horizontally along the rail, reducing the possibility of accidentally pulling the wiring loose. On the bottom of the PLC is a small retaining clip. To secure the PLC to a DIN rail, place it onto the rail and gently push 9 up on the clip to lock it onto the rail. To remove the PLC, pull down on the retaining clip, lift up on the PLC slightly, then pulling it away from the rail. 10 11 12 13 14 A NOTE: Refer to our catalog for a complete listing of DINnector connection systems. B C D Din Rail Dimensions 7mm

Din Rail Slot Use 35mm x 7mm rail conforming to DIN EN 50022

35mm

Retaining clip

DL05 Micro PLC User Manual, 6th Edition, Rev. A

2–9