DL05 Micro PLC User Manual, Volume 1 of 2: Chapter 5: Standard RLL and Intelligent Box Instructions, pages 354 to 363
Pages 354 to 363 of 379, from DL05 Micro PLC User Manual, Volume 1 of 2
The original document is the PDF (5.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect D0-05AA
Page 354
Chapter 5: Intelligent Box (IBox) - Counter
1 2 3 4 5 CTREDRL Example 6 Rung 1: This sets up the CTRIO card in slot 2 of the local base. Each CTRIO in the system will need a separate CTRIO I-box before any CTRxxxx I-boxes can be used for them. The 7 CTRIO has been configured to use V2000 through V2025 for its input data, and V2030 through V2061 for its output data. 8 9 10 11 12 13 (example continued on next page) 14 A B C D Parameter
CTRIO# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Output# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Table# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Entry# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Entry Type . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Pulse Time . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Preset Count . . . . . . . . . . . . . . . . . . . . . . . . . V,K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B
DL05 Range
K0-255 K0-3 K0-255; See DL05 V-memory map - Data Words K0-255; See DL05 V-memory map - Data Words K0-5; See DL05 V-memory map - Data Words K0-65535; See DL05 V-memory map - Data Words K0-2147434528; See DL05 V-memory map See DL05 V-memory map - Data Words See DL05 V-memory map See DL05 V-memory map
DL05 Micro PLC User Manual, 6th Edition, Rev. A
5–231
Page 355
Chapter 5: Intelligent Box (IBox) - Counter
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
CTREDRL Example (cont’d)
5–232
Rung 2: This rung is a sample method for enabling the CTREDRL command. A C-bit is used to allow the programmer to control the command from Data View for testing purposes. Turning on C0 will cause the CTREDRL instruction to change the second preset in file 1 from a reset at a value of 20 to a reset at a value of 30. Operating procedure for this example code is to load the CTREDRL_ex1.cwb file to your CTRIO, then enter the code shown here, change to RUN mode, enable output #0 by turning on C2 in Data View, turn encoder on CTRIO to value above 10 and output #0 light will come on, continue to a count above 20 and the output #0 light will turn off. Now reset the counter with C1, enable C0 to execute CTREDRL command to change the second preset count value to 30, then turn encoder to value of 10+ (output #0 should turn on) and continue on to a value of 30+ and the output #0 light will turn off. Note that it is not necessary to reload this file seperately, however, the command can only change one value at a time.
DL05 Micro PLC User Manual, 6th Edition, Rev. A
Page 356
Chapter 5: Intelligent Box (IBox) - Counter
CTREDRL Example Rung 3: This rung allows the programmer to reset the counter from the ladder logic.
Rung 4: This rung allows the operator to enable output #0 from the ladder code.
DL05 Micro PLC User Manual, 6th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–233
Page 357
Chapter 5: Intelligent Box (IBox) - Counter
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
CTRIO Initialize Preset Table (CTRINPT) (IB-1004) DS5
Used
HPP
N/A
5–234
CTRIO Initialize Preset Table, on a leading edge transition to this IBox, will create a single entry Preset Table in memory but not as a file, on a specific CTRIO Output resource. This IBox will take more than 1 PLC scan to execute. Either the Success or Error bit will turn on when the command is complete. If the Error Bit is on, you can use the CTRIO Read Error Code (CTRRDER) IBox to get extended error information. Entry Type: K0: Set K1: Reset K2: Pulse On (uses Pulse Time) K3: Pulse Off (uses Pulse Time) K4: Toggle K5: Reset Count Note that the Pulse Time parameter is ignored by some Entry Types. The Workspace register is for internal use by this IBox instruction and MUST NOT be used anywhere else in your program. CTRINPT Parameters • CTRIO#: specifies a specific CTRIO module based on a user defined number (see CTRIO Config Ibox) • Output#: specifies a CTRIO output to be used by the instruction • Entry Type: specifies the Entry Type to add during the edit • Pulse Time: specifies a pulse time for the Pulse On and Pulse Off Entry Types • Preset Count: specifies an initial count value to begin at after Reset • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the instruction has successfully completed • Error: specifies a bit that will turn on if the instruction does not complete successfully
DL05 Micro PLC User Manual, 6th Edition, Rev. A
Page 358
Chapter 5: Intelligent Box (IBox) - Counter Parameter
DL05 Range
1 2 3 4 CTRINPT Example 5 Rung 1: This sets up the CTRIO card in slot 2 of the local base. Each CTRIO in the system will need a separate CTRIO I-box before any CTRxxxx I-boxes can be used for them. The 6 CTRIO has been configured to use V2000 through V2025 for its input data, and V2030 through V2061 for its output data. 7 8 9 10 11 12 (example continued on next page) 13 14 A B C D CTRIO# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Output# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Entry Type . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Pulse Time . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Preset Count . . . . . . . . . . . . . . . . . . . . . . . . . V,K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B
K0-255 K0-3 K0-5; See DL05 V-memory map - Data Words K0-65535; See DL05 V-memory map - Data Words K0-2147434528; See DL05 V-memory map See DL05 V-memory map - Data Words See DL05 V-memory map See DL05 V-memory map
DL05 Micro PLC User Manual, 6th Edition, Rev. A
5–235
Page 359
Chapter 5: Intelligent Box (IBox) - Counter
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
CTRINPT Example (cont’d)
5–236
Rung 2: This rung is a sample method for enabling the CTRINPT command. A C-bit is used to allow the programmer to control the command from Data View for testing purposes. Turning on C0 will cause the CTRINPT instruction to create a single entry preset table, but not as a file, and use it for the output #0. In this case the single preset will be a set at a count of 15 for output #0. Operating procedure for this example code is to load the CTRINPT_ex1.cwb file to your CTRIO, then enter the code shown here, change to RUN mode, enable output #0 by turning on C2 in Data View, turn encoder on CTRIO to value above 15 and output #0 light will not come on. Now reset the counter with C1, enable C0 to execute CTRINPT command to create a single preset table with a preset to set output#0 at a count of 15, then turn encoder to value of 15+ (output #0 should turn on).
DL05 Micro PLC User Manual, 6th Edition, Rev. A
Page 360
Chapter 5: Intelligent Box (IBox) - Counter
CTRINPT Example Rung 3: This rung allows the programmer to reset the counter from the ladder logic.
Rung 4: This rung allows the operator to enable output #0 from the ladder code.
DL05 Micro PLC User Manual, 6th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–237
Page 361
Chapter 5: Intelligent Box (IBox) - Counter
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
CTRIO Initialize Preset Table (CTRINTR) (IB-1010) DS5
Used
HPP
N/A
5–238
CTRIO Initialize Preset Table, on a leading edge transition to this IBox, will create a single entry Preset Table in memory but not as a file, on a specific CTRIO Output resource.This IBox will take more than 1 PLC scan to execute. Either the Success or Error bit will turn on when the command is complete. If the Error Bit is on, you can use the CTRIO Read Error Code (CTRRDER) IBox to get extended error information. Entry Type: K0: Set K1: Reset K2: Pulse On (uses Pulse Time) K3: Pulse Off (uses Pulse Time) K4: Toggle K5: Reset Count Note that the Pulse Time parameter is ignored by some Entry Types. The Workspace register is for internal use by this IBox instruction and MUST NOT be used anywhere else in your program. CTRINTR Parameters • CTRIO#: specifies a specific CTRIO module based on a user defined number (see CTRIO Config Ibox) • Output#: specifies a CTRIO output to be used by the instruction • Entry Type: specifies the Entry Type to add during the edit • Pulse Time: specifies a pulse time for the Pulse On and Pulse Off Entry Types • Preset Count: specifies an initial count value to begin at after Reset • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the instruction has successfully completed • Error: specifies a bit that will turn on if the instruction does not complete successfully
DL05 Micro PLC User Manual, 6th Edition, Rev. A
Page 362
Chapter 5: Intelligent Box (IBox) - Counter
1 2 3 4 5 CTRINTR Example Rung 1: This sets up the CTRIO card in slot 2 of the local base. Each CTRIO in the system 6 will need a separate CTRIO I-box before any CTRxxxx I-boxes can be used for them. The CTRIO has been configured to use V2000 through V2025 for its input data, and V2030 through V2061 for its output data. 7 8 9 10 11 12 (example continued on next page) 13 14 A B C D Parameter
CTRIO# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Output# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Entry Type . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Pulse Time . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Preset Count . . . . . . . . . . . . . . . . . . . . . . . . . V,K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B
DL05 Range
K0-255 K0-3 K0-5; See DL05 V-memory map - Data Words K0-65535; See DL05 V-memory map - Data Words K0-2147434528; See DL05 V-memory map See DL05 V-memory map - Data Words See DL05 V-memory map See DL05 V-memory map
DL05 Micro PLC User Manual, 6th Edition, Rev. A
5–239
Page 363
Chapter 5: Intelligent Box (IBox) - Counter
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
CTRINTR Example (cont’d)
5–240
Rung 2: This rung is a sample method for enabling the CTRINTR command. A C-bit is used to allow the programmer to control the command from Data View for testing purposes. Turning on C0 will cause the CTRINTR instruction to create a single entry preset table, but not as a file, and use it for output #0, the new preset will be loaded when the current count is reset. In this case the single preset will be a set at a count of 25 for output #0. Operating procedure for this example code is to load the CTRINTR_ex1.cwb file to your CTRIO, then enter the code shown here, change to RUN mode, enable output #0 by turning on C2 in Data View, turn encoder on CTRIO to value above 10 and output #0 light will come on. Now turn on C0 to execute the CTRINTR command, reset the counter with C1, then turn encoder to value of 25+ (output #0 should turn on).
DL05 Micro PLC User Manual, 6th Edition, Rev. A