The text of a manual · part 37 of 40
DL05 Micro PLC User Manual, Volume 1 of 2: Chapter 5: Standard RLL and Intelligent Box Instructions, pages 344 to 353
Pages 344 to 353 of 379, from DL05 Micro PLC User Manual, Volume 1 of 2
The original document is the PDF (5.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect D0-05AA
Page 344
Chapter 5: Intelligent Box (IBox) - Counter
CTRADPT Example
1 2 3 4 5 6 Rung 2: This rung is a sample method for enabling the CTRADPT command. A C-bit is used to allow the programmer to control the command from Data View for testing purposes. 7 Turning on C0 will cause the CTRADPT instruction to add a new preset to the preset table for output #0 on the CTRIO in slot 2. The new preset will be a command to RESET (entry 8 type K1=reset), pulse time is left at zero as the reset type does not use this, and the count at which it will reset will be 20. 9 Operating procedure for this example code is to load the CTRADPT_ex1.cwb file to your CTRIO, then enter the code shown here, change to RUN mode, enable output #0 by turning on C2 in dataview, turn encoder on CTRIO to value above 10 and output #0 light will come 10 on and stay on for all counts past 10. Now reset the counter with C1, enable C0 to execute CTRADPT command to add a reset for output #0 at a count of 20, turn on C2 to enable 11 output #0, then turn encoder to value of 10+ (output #0 should turn on) and then continue on to count of 20+ (output #0 should turn off ). 12 13 14 A B C (example continued on next page) D Rung 1: This sets up the CTRIO card in slot 2 of the local base. Each CTRIO in the system will need a separate CTRIO I-box before any CTRxxxx I-boxes can be used for them. The CTRIO has been configured to use V2000 through V2025 for its input data, and V2030 through V2061 for its output data.
DL05 Micro PLC User Manual, 6th Edition, Rev. A
5–221
Page 345
Chapter 5: Intelligent Box (IBox) - Counter
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
CTRADPT Example (cont’d)
5–222
Rung 3: This rung allows the programmer to reset the counter from the ladder logic.
Rung 4: This rung allows the operator to enable output #0 from the ladder code.
DL05 Micro PLC User Manual, 6th Edition, Rev. A
Page 346
Chapter 5: Intelligent Box (IBox) - Counter
CTRIO Clear Preset Table (CTRCLRT) (IB-1007) DS5
Used
HPP
N/A
1 2 3 4 5 6 CTRCLRT Parameters • CTRIO#: specifies a specific CTRIO module based on a user defined number (see CTRIO Config) 7 • Output#: specifies a CTRIO output to be used by the instruction • Workspace: specifies a V-memory location that will be used by the instruction 8 • Success: specifies a bit that will turn on once the instruction has successfully completed • Error: specifies a bit that will turn on if the instruction does not complete successfully 9 Parameter DL05 Range 10 11 12 13 14 A B C D CTRIO Clear Preset Table will clear the RAM based Preset Table on a leading edge transition to this IBox. This IBox will take more than 1 PLC scan to execute. Either the Success or Error bit will turn on when the command is complete. If the Error Bit is on, you can use the CTRIO Read Error Code (CTRRDER) IBox to get extended error information. The Workspace register is for internal use by this IBox instruction and MUST NOT be used anywhere else in your program.
CTRIO# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Output# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B
K0-255 K0-3 See DL05 V-memory map - Data Words See DL05 V-memory map See DL05 V-memory map
DL05 Micro PLC User Manual, 6th Edition, Rev. A
5–223
Page 347
Chapter 5: Intelligent Box (IBox) - Counter
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
CTRCLRT Example
5–224
Rung 1: This sets up the CTRIO card in slot 2 of the local base. Each CTRIO in the system will need a separate CTRIO I-box before any CTRxxxx I-boxes can be used for them. The CTRIO has been configured to use V2000 through V2025 for its input data, and V2030 through V2061 for its output data.
Rung 2: This rung is a sample method for enabling the CTRCLRT command. A C-bit is used to allow the programmer to control the command from Data View for testing purposes. Turning on C0 will cause the CTRCLRT instruction to clear the preset table for output #0 on the CTRIO in slot 2. Operating procedure for this example code is to load the CTRCLRT_ex1.cwb file to your CTRIO, then enter the code shown here, change to RUN mode, enable output #0 by turning on C2 in Data View, turn encoder on CTRIO to value above 10 and output #0 light will come on and stay on until a count of 20 is reached, where it will turn off. Now reset the counter with C1, enable C0 to execute CTRCLRT command to clear the preset table, turn on C2 to enable output #0, then turn encoder to value of 10+ (output #0 should NOT turn on).
DL05 Micro PLC User Manual, 6th Edition, Rev. A
Page 348
Chapter 5: Intelligent Box (IBox) - Counter
CTRCLRT Example Rung 3: This rung allows the programmer to reset the counter from the ladder logic.
Rung 4: This rung allows the operator to enable output #0 from the ladder code.
DL05 Micro PLC User Manual, 6th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–225
Page 349
Chapter 5: Intelligent Box (IBox) - Counter
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
CTRIO Edit Preset Table Entry (CTREDPT) (IB-1003) DS5
Used
HPP
N/A
5–226
CTRIO Edit Preset Table Entry, on a leading edge transition to this IBox, will edit a single entry in a Preset Table on a specific CTRIO Output resource. This IBox is good if you are editing more than one entry in a file at a time. If you wish to do just one edit and then reload the table immediately, see the CTRIO Edit and Reload Preset Table Entry (CTREDRL) IBox. This IBox will take more than 1 PLC scan to execute. Either the Success or Error bit will turn on when the command is complete. If the Error Bit is on, you can use the CTRIO Read Error Code (CTRRDER) IBox to get extended error information. Entry Type: K0: Set K1: Reset K2: Pulse On (uses Pulse Time) K3: Pulse Off (uses Pulse Time) K4: Toggle K5: Reset Count Note that the Pulse Time parameter is ignored by some Entry Types. The Workspace register is for internal use by this IBox instruction and MUST NOT be used anywhere else in your program. CTREDPT Parameters • CTRIO#: specifies a specific CTRIO module based on a user defined number (see CTRIO Config Ibox) • Output#: specifies a CTRIO output to be used by the instruction • Table#: specifies the Table number of which an Entry is to be edited • Entry#: specifies the Entry location in the Preset Table to be edited • Entry Type: specifies the Entry Type to add during the edit • Pulse Time: specifies a pulse time for the Pulse On and Pulse Off Entry Types • Preset Count: specifies an initial count value to begin at after Reset • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the instruction has successfully completed • Error: specifies a bit that will turn on if the instruction does not complete successfully
DL05 Micro PLC User Manual, 6th Edition, Rev. A
Page 350
Chapter 5: Intelligent Box (IBox) - Counter Parameter
DL05 Range
1 2 3 4 5 CTREDPT Example 6 Rung 1: This sets up the CTRIO card in slot 2 of the local base. Each CTRIO in the system will need a separate CTRIO I-box before any CTRxxxx I-boxes can be used for them. The 7 CTRIO has been configured to use V2000 through V2025 for its input data, and V2030 through V2061 for its output data. 8 9 10 11 12 (example continued on next page) 13 14 A B C D CTRIO# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Output# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Table# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Entry# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Entry Type . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Pulse Time . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Preset Count . . . . . . . . . . . . . . . . . . . . . . . . . V,K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B
K0-255 K0-3 K0-255; See DL05 V-memory map - Data Words K0-255; See DL05 V-memory map - Data Words K0-5; See DL05 V-memory map - Data Words K0-65535; See DL05 V-memory map - Data Words K0-2147434528; See DL05 V-memory map See DL05 V-memory map - Data Words See DL05 V-memory map See DL05 V-memory map
DL05 Micro PLC User Manual, 6th Edition, Rev. A
5–227
Page 351
Chapter 5: Intelligent Box (IBox) - Counter
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
CTREDPT Example (cont’d)
5–228
Rung 2: This rung is a sample method for enabling the CTREDPT command. A C-bit is used to allow the programmer to control the command from Data View for testing purposes. Turning on C0 will cause the CTREDPT instruction to change the second preset from a reset at a count of 20 to a reset at a count of 30 for output #0 on the CTRIO in slot 2. Operating procedure for this example code is to load the CTREDPT_ex1.cwb file to your CTRIO, then enter the code shown here, change to RUN mode, enable output #0 by turning on C2 in Data View, turn encoder on CTRIO to value above 10 and output #0 light will come on and stay on until a count of 20 is reached, where it will turn off. Now reset the counter with C1, enable C0 to execute CTREDPT command to change the second preset, turn on C2 to enable output #0, then turn encoder to value of 10+ (output #0 should turn on) and then continue past a count of 30 (output #0 should turn off ). Note that we must also reload the profile after changing the preset(s), this is why the CTRLDPR command follows the CTREDPT command in this example.
DL05 Micro PLC User Manual, 6th Edition, Rev. A
Page 352
Chapter 5: Intelligent Box (IBox) - Counter
CTREDPT Example Rung 3: This rung allows the programmer to reset the counter from the ladder logic.
Rung 4: This rung allows the operator to enable output #0 from the ladder code.
DL05 Micro PLC User Manual, 6th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–229
Page 353
Chapter 5: Intelligent Box (IBox) - Counter
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
CTRIO Edit Preset Table Entry and Reload (CTREDRL) (IB-1002) DS5
Used
HPP
N/A
5–230
CTRIO Edit Preset Table Entry and Reload, on a leading edge transition to this IBox, will perform this dual operation to a CTRIO Output resource in one CTRIO command. This IBox will take more than 1 PLC scan to execute. Either the Success or Error bit will turn on when the command is complete. If the Error Bit is on, you can use the CTRIO Read Error Code (CTRRDER) IBox to get extended error information. Entry Type: K0: Set K1: Reset K2: Pulse On (uses Pulse Time) K3: Pulse Off (uses Pulse Time) K4: Toggle K5: Reset Count Note that the Pulse Time parameter is ignored by some Entry Types. The Workspace register is for internal use by this IBox instruction and MUST NOT be used anywhere else in your program. CTREDRL Parameters • CTRIO#: specifies a specific CTRIO module based on a user defined number (see CTRIO Config Ibox) • Output#: specifies a CTRIO output to be used by the instruction • Table#: specifies the Table number of which an Entry is to be edited • Entry#: specifies the Entry location in the Preset Table to be edited • Entry Type: specifies the Entry Type to add during the edit • Pulse Time: specifies a pulse time for the Pulse On and Pulse Off Entry Types • Preset Count: specifies an initial count value to begin at after Reset • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the instruction has successfully completed • Error: specifies a bit that will turn on if the instruction does not complete successfully
DL05 Micro PLC User Manual, 6th Edition, Rev. A