Page 154

Chapter 5: Standard RLL - Immediate Instructions

Immediate Instructions Store Immediate (STRI) DS5

Used

HPP

Used

The Store Immediate instruction begins a new rung or additional branch in a rung. The status of the contact will be the same as the status of the associated input point at the time the instruction is executed. The image register is not updated.

X aaa

Store Not Immediate (STRNI) DS5

Used

HPP

Used

The Store Not Immediate instruction begins a new rung or additional branch in a rung. The status of the contact will be opposite the status of the associated input point at the time the instruction is executed. The image register is not updated.

X aaa

Operand Data Type

DL05 Range aaa

Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X

0–377

In the following example when X1 is on, Y2 will energize. DirectSOFT 5

DirectSOFT32 X1

Handheld Programmer Keystrokes Y2

$ STR

B

I

SHFT

8

1

ENT

OUT GX OUT

C 2

ENT

In the following example when X1 is off, Y2 will energize. DirectSOFT 5 DirectSOFT32 X1

Handheld Programmer Keystrokes Y2 OUT

SP STRN GX OUT

SHFT

I

B 8

C 2

1 ENT

Or Immediate (ORI) DS5 Implied HPP

Used

The Or Immediate connects two contacts in parallel. The status of the contact will be the same as the status of the associated input point at the time the instruction is executed. The image register is not updated.

X aaa

Or Not Immediate (ORNI) DS5 Implied HPP

Used

The Or Not Immediate connects two contacts in parallel. The status of the contact will be opposite the status of the associated input point at the time the instruction is executed. The image register is not updated.

X aaa

DL05 Micro PLC User Manual, 6th Edition, Rev. A

ENT

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–31

Page 155

Chapter 5: Standard RLL - Immediate Instructions

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

OR Immediate Instructions (cont’d) Operand Data Type

DL05 Range aaa

Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X

0–377

In the following example, when X1 or X2 is on, Y5 will energize. DirectSOFT DirectSOFT32 5

Handheld Programmer Keystrokes Y5

X1

$

B STR

OUT

I

SHFT

OR

X2

ENT

1

Q

C 8

GX OUT

ENT

2

F

ENT

5

In the following example, when X1 is on or X2 is off, Y5 will energize. DirectSOFT 5 DirectSOFT32

Handheld Programmer Keystrokes Y5

X1

B

$ STR

OUT X2

ENT

1

R ORN

I

SHFT

C 8

ENT

2

F

GX OUT

ENT

5

And Immediate (ANDI) DS5 Implied HPP

Used

The And Immediate connects two contacts in series. The status of the contact will be the same as the status of the associated input point at the time the instruction is executed. The image register is not updated.

X aaa

And Not Immediate (ANDNI) DS5 Implied HPP

Used

The And Not Immediate connects two contacts in series. The status of the contact will be opposite the status of the associated input point at the time the instruction is executed. The image register is not updated. Operand Data Type

DL05 Range aaa

Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X

0–377

In the following example, when X1 and X2 are on, Y5 will energize. DirectSOFT DirectSOFT32 5 X1

Handheld Programmer Keystrokes X2

Y5 OUT

B

$ STR V AND

1 SHFT

GX OUT

ENT

I

C 8

F 5

2

ENT

ENT

In the following example, when X1 is on and X2 is off, Y5 will energize. DirectSOFT DirectSOFT325 X1

Handheld Programmer Keystrokes X2

Y5 OUT

$

B 1

STR W ANDN GX OUT

5–32

X aaa

DL05 Micro PLC User Manual, 6th Edition, Rev. A

SHFT

ENT

I

C 8

F 5

2 ENT

ENT

Page 156

Chapter 5: Standard RLL - Immediate Instructions

Out Immediate (OUTI) DS5 HPP

DS5 HPP

1 2 3 4 Or Out Immediate (OROUTI) 5 The Or Out Immediate instruction has been designed to use more than 1 rung of discrete logic to control a single output. Multiple Or Out Immediate instructions 6 referencing the same output coil may be used, since all contacts controlling the output are ored together. If the 7 status of any rung is on at the time the instruction is executed, the output will also be on. 8 Operand Data Type DL05 Range aaa 9 10 In the following example, when X1 is on, output point Y2 on the output module will turn on. For instruction entry on the Handheld Programmer, you can use the instruction number (#350) as shown, or type each letter of the command. 11 12 13 14 In the following example, when X1 or X4 is on, Y2 will energize. A B C D The Out Immediate instruction reflects the status of the Used rung (on/off ) and outputs the discrete (on/off ) status to the specified module output point and the image register at the time the instruction is executed. If multiple Out Immediate instructions referencing the same discrete point are used it is possible for the module output status to change multiple times in a CPU scan. See Or Out Immediate. Used

Y aaa OUTI

Used Used

Y aaa OROUTI

Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Y

0–377

DirectSOFT 5 DirectSOFT32

Handheld Programmer Keystrokes

Y2

X1

$

B

STR

OUTI

1

O INST#

D

F

5

X1

ENT

ENT

Handheld Programmer Keystrokes

Y2

OR OUTI

X4

0

ENT

2

DirectSOFT 5 DirectSOFT32

A

3

C

ENT

B

$

O INST#

D

F

3

C

Y2

OR OUTI

1

STR

2

$

A

5

E

4

D

F

3 C 2

0

ENT

ENT

ENT

ENT

ENT

STR

O INST#

ENT

ENT

A

5

0

ENT

DL05 Micro PLC User Manual, 6th Edition, Rev. A

5–33

Page 157

Chapter 5: Standard RLL - Immediate Instructions

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Set Immediate (SETI) DS5

Used

HPP

Used

The Set Immediate instruction immediately sets, or turns on an output or a range of outputs in the image register and the corresponding output point(s) at the time the instruction is executed. Once the outputs are set it is not necessary for the input to remain on. The Reset Immediate instruction can be used to reset the outputs.

Y aaa aaa SETI

Reset Immediate (RSTI) DS5

Used

HPP

Used

The Reset Immediate instruction immediately resets, or turns off an output or a range of outputs in the image register and the output point(s) at the time the instruction is executed. Once the outputs are reset it is not necessary for the input to remain on.

Y aaa aaa RSTI

Operand Data Type

DL05 Range aaa

Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Y

0–377

In the following example, when X1 is on, Y2 through Y5 will be set on in the image register and on the corresponding output points. DirectSOFT 5 DirectSOFT32 X1

Handheld Programmer Keystrokes Y2

$

Y5

B STR

SETI

ENT

1

X SET

SHFT

C

I 8

F 2

ENT

5

In the following example, when X1 is on, Y5 through Y22 will be reset (off ) in the image register and on the corresponding output module(s). DirectSOFT 5 DirectSOFT32

5–34

Handheld Programmer Keystrokes X1

Y5

Y22 RSTI

$

B STR

S RST

1 SHFT

I

DL05 Micro PLC User Manual, 6th Edition, Rev. A

ENT C

F 8

5

C 2

2

ENT

Page 158

Chapter 5: Standard RLL - Timer, Counter and Shift Register Instructions

Timer, Counter and Shift Register Instructions

1 Using Timers Timers are used to time an event for a desired length of time. The single input timer will time 2 as long as the input is on. When the input changes from on to off the timer current value is reset to 0. There is a tenth of a second and a hundredth of a second timer available with a 3 maximum time of 999.9 and 99.99 seconds respectively. There is a discrete bit associated with each timer to indicate that the current value is equal to or greater than the preset value. The 4 timing diagram below shows the relationship between the timer input, associated discrete bit, current value, and timer preset. 5 6 7 Timer Preset 8 9 10 There are those applications that need an accumulating timer, meaning it has the ability to time, stop, and then resume from where it previously stopped. The accumulating timer works similarly to the regular timer, but two inputs are required. The start/stop input starts and 11 stops the timer. When the timer stops, the elapsed time is maintained. When the timer starts again, the timing continues from the elapsed time. When the reset input is turned on, the 12 elapsed time is cleared and the timer will start at 0 when it is restarted. There is a tenth of a second and a hundredth of a second timer available with a maximum time of 9999999.9 and 999999.99 seconds respectively. The timing diagram below shows the relationship between 13 the timer input, timer reset, associated discrete bit, current value, and timer preset. 14 A B C D 0

1

2

3

Seconds 4

5

6

7

8

X1

TMR

T1

K30

X1

T1

T1

Current Value

0

0

10

20

1

2

3

30 40 1/10 Seconds

Seconds 4

5

50

60

6

7

Y0 OUT

0

8

X1

TMRA

T0

K30

Enable

X1

X2

X2

Reset Input

T0

Current Value

0

10

10

20 30 1/10 Seconds

40

50

0

DL05 Micro PLC User Manual, 6th Edition, Rev. A

5–35

Page 159

Chapter 5: Standard RLL - Timer, Counter and Shift Register Instructions

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Timer (TMR) and Timer Fast (TMRF) DS5

Used

HPP

Used

5–36

The Timer instruction is a 0.1 second single input timer that T aaa TMR times to a maximum of 999.9 seconds. The Timer Fast B bbb instruction is a 0.01 second single input timer that times up to a maximum of 99.99 seconds. These timers will be Preset Timer# enabled if the input logic is true (on) and will be reset to 0 if the input logic is false (off ). Instruction Specifications TMRF T aaa Timer Reference (Taaa): Specifies the timer number. B bbb Preset Value (Bbbb): Constant value (K) or a V-memory location. Timer# Preset Current Value: Timer current values (BCD) are accessed by The timer discrete status bit and the referencing the associated V or T memory location*. For example, the timer current value for T3 physically resides current value are not specified in the timer instruction in V-memory location V3 as a BCD value. Discrete Status Bit: The discrete status bit is referenced by the associated T memory location. Operating as a “timer done bit”, it will be on if the current value is equal to or greater than the preset value. For example, the discrete status bit for Timer 2 is TA2. NOTE: Timer preset constants (K) may be changed by using a handheld programmer, even when the CPU is in Run Mode. Therefore, a V-memory preset is required only if the ladder program must change the preset.

Operand Data Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A/B Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T

DL05 Range aaa bbb

0–177

V-memory for preset values . . . . . . . . . . . . . . . V Pointers (preset only) . . . . . . . . . . . . . . . . . . . . P Constants (preset only) . . . . . . . . . . . . . . . . . . K Timer discrete status bits . . . . . . . . . . . . . . . T/V Timer current values . . . . . . . . . . . . . . . . . V /T**

–– 1200–7377 –– 7400–7577* 1200–7377 –– 7400–7577 –– 0–9999 0–177 or V41100–41107 0–177

NOTE: * May be non-volatile if MOV instruction is used. ** With the HPP, both the Timer discrete status bits and current value are accessed with the same data reference. DirectSOFT 5 uses separate references, such as “T2” for discrete status bit for Timer T2, and “TA2” for the current value of Timer T2.

You can perform functions when the timer reaches the specified preset using the discrete status bit. Or, use comparative contacts to perform functions at different time intervals, based on one timer. The examples on the following page show these two methods of programming timers.

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 160

Chapter 5: Standard RLL - Timer, Counter and Shift Register Instructions

Timer Example Using Discrete Status Bits

1 2 3 4 5 6 7 8 Timer Example Using Comparative Contacts In the following example, a single input timer is used with a preset of 4.5 seconds. 9 Comparative contacts are used to energize Y3, Y4, and Y5 at one second intervals respectively. When X1 is turned off the timer will be reset to 0 and the comparative contacts will turn off 10 Y3, Y4, and Y5. 11 12 13 14 A B C D In the following example, a single input timer is used with a preset of 3 seconds. The timer discrete status bit (T2) will turn on when the timer has timed for 3 seconds. The timer is reset when X1 turns off, turns off the discrete status bit and resets the timer current value to 0.

DirectSOFT 5

Timing Diagram

Direct SOFT32 X1

TMR

T2

0

K30

2

3

Seconds 4

5

6

7

0

10

20

30

40

50

60

8

X1

Y0

T2

1

OUT

T2

Y0

Handheld Programmer Keystrokes $

B

STR

1

N TMR

Current Value

ENT

C

STR

GX OUT

A

D

3

2

$

SHFT

T MLR

A

ENT

0

ENT

0

C

ENT

2

DirectSOFT Direct SOFT32 5

Timing Diagram

X1

TMR

Seconds

T20

0

K45

TA20

2

3

4

5

6

7

0

10

20

30

40

50

60

8

Y3

Y4

K20

1

X1

Y3

K10

OUT

TA20

0

Y4

OUT

Y5

TA20

Y5

K30

T2

OUT

Current Value

0

Handheld Programmer Keystrokes $

B

1

STR

N TMR

C

ENT

A

E

2

0

SHFT

T MLR

GX OUT

D

ENT

$

SHFT

T MLR

GX OUT

E

ENT

$

SHFT

T MLR

F

ENT

$

STR

STR

STR

GX OUT

3

4

5

F

4

C

2

2

2

A

1

C

0

A

C

ENT

0

A

C

5

B

A

A

2

0

A

D

0

0

3

0

ENT

ENT

ENT

DL05 Micro PLC User Manual, 6th Edition, Rev. A

5–37

Page 161

Chapter 5: Standard RLL - Timer, Counter and Shift Register Instructions

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Accumulating Timer (TMRA) DS5

Used

HPP

Used

Enable

The Accumulating Timer is a 0.1 second two input timer that will time to a maximum of 9999999.9.

T aaa TMRA B bbb

Reset

Accumulating Fast Timer (TMRAF) DS5

Used

HPP

Used

5–38

The Accumulating Fast Timer is a 0.01 second two-input Timer# Preset timer that will time to a maximum of 99999.99. Each one uses two timer registers in V-memory. These timers have two inputs, an enable and a reset. The timer starts timing when the enable is on and stops when the enable is off (without resetting the T aaa Enable TMRAF count). The reset will reset the timer when on and allow the B bbb timer to time when off. Reset Instruction Specifications Timer Reference (Taaa): Specifies the timer number. Timer# Preset Preset Value (Bbbb): Constant value (K) or a V-memory location. The timer discrete status bit Current Value: Timer current values (BCD) are accessed by and the current value are not referencing the associated V or T memory location*. For specified in the timer example, the timer current value for T3 resides in V-memory instruction location V3 as a BCD value. Discrete Status Bit: The discrete status bit is accessed by referencing the associated T memory location. Operating as a “timer done bit”, it will be on if the current value is equal to or greater than the preset value. For example the discrete status bit for timer 2 would be T2. NOTE: The accumulating type timer uses two consecutive V-memory locations for the 8-digit value, and therefore two consecutive timer locations. For example, if TMR 1 is used, the next available timer number is TMR 3.

Operand Data Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A/B Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T V-memory for preset values . . . . . . . . . . . . . . . V Pointers (preset only) . . . . . . . . . . . . . . . . . . . . P Constants (preset only) . . . . . . . . . . . . . . . . . . K Timer discrete status bits . . . . . . . . . . . . . . . T/V Timer current values . . . . . . . . . . . . . . . . . V /T**

DL05 Range aaa 0–176 –– –– –– bbb –– 1200–7377/7400–7577* 1200–7377/7400–7577 0–99999999 0–176 or V41100–41107 0–176

NOTE: * May be non-volatile if MOV instruction is used. ** With the HPP, both the Timer discrete status bits and current value are accessed with the same data reference. DirectSOFT 5 uses separate references, such as “T2” for discrete status bit for Timer T2, and “TA2” for the current value of Timer T2.

The following examples show two methods of programming timers. One performs functions when the timer reaches the preset value using the discrete status bit, or use comparative contacts to perform functions at different time intervals.

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 162

Chapter 5: Standard RLL - Timer, Counter and Shift Register Instructions

Accumulating Timer Example using Discrete Status Bits In the following example, a two input timer (accumulating timer) is used with a preset of 3 seconds. The timer discrete status bit (T6) will turn on when the timer has timed for 3 seconds. Notice in this example that the timer times for 1 second, stops for one second, then resumes timing. The timer will reset when C10 turns on, turning the discrete status bit off and resetting the timer current value to 0. DirectSOFT Direct SOFT32 5

Timing Diagram

X1 TMRA

0

T6

1

2

3

Seconds 4

5

6

7

0

10

10

20

30

40

50

8

X1

K30 C10

C10

Y7

T6

OUT

Current Value

T6

Handheld Programmer Keystrokes $

B

3 B

2

A 1

A

SHFT

A

D

C

SHFT

STR N TMR

Handheld Programmer Keystrokes (cont)

ENT

1

STR $

0

ENT

0

STR

G 0

ENT

0

$ GX OUT

6

SHFT

T MLR

G

B

A

ENT

0

1

ENT

6

Accumulator Timer Example Using Comparative Contacts In the following example, a single input timer is used with a preset of 4.5 seconds. Comparative contacts are used to energized Y3, Y4, and Y5 at one second intervals respectively. The comparative contacts will turn off when the timer is reset. Contacts DirectSOFT

Timing Diagram

X1 TMRA

0

T20 K45

1

2

3

0

10

10

Seconds 4

5

6

7

20

30

40

50

8

X1

C10 C10 TA20

K10 TA21

Y3

K0

Y3

OUT Y4

TA21

K1

TA20

K20 TA21

TA21

K1

TA20

K30 TA21

Y5 Y4

K0

T20

OUT Current Value

0

1/10 Seconds

Y5

K1

OUT

Handheld Programmer Keystrokes $

B 1

STR $

SHFT

STR N TMR

SHFT

$ V AND

SHFT

Q OR

SHFT

GX OUT

C

$ A 1

2 C

0

E 4 E 4 D 3

0

ENT

C

V AND

SHFT

ENT

Q OR

SHFT

ENT

GX OUT

ENT

A 2

T MLR

SHFT

STR B

A

SHFT

STR

Handheld Programmer Keystrokes (cont’d)

ENT

E 0

F 5

4

A

B

2

0

SHFT

T MLR

C

SHFT

T MLR

C

A 1

B 2

A 0

1 B

2

0

B 1

1

ENT

$

ENT

V AND GX OUT

4 E 4 E 4 SHFT

STR SHFT

T MLR

E

T MLR

4 5

A

C

2

0

SHFT

T MLR

C

SHFT

T MLR

C

C

A

A 0

2 B 2

ENT A 0

1 B

2

B 1

1

ENT ENT

ENT

E F

C

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

D

2

0

SHFT

T MLR

A 3

0

B

C 2

ENT B

1

1

ENT

ENT

DL05 Micro PLC User Manual, 6th Edition, Rev. A

5–39

Page 163

Chapter 5: Standard RLL - Timer, Counter and Shift Register Instructions

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–40

Using Counters Counters are used to count events. The counters available are up counters, up/down counters, and stage counters (used with RLLPLUS programming). The up counter has two inputs, a count input and a reset input. The maximum count value is 9999. The timing diagram below shows the relationship between the counter input, counter reset, associated discrete bit, current value, and counter preset. X1

CNT

X1

CT1 K3

Up X2

X2

Reset CT1 Current alue

1

2

3

4

0

Counter preset

Counts

The up down counter has three inputs, a count up input, count down input and reset input. The maximum count value is 99999999. The timing diagram below shows the relationship between the counter input, counter reset, associated discrete bit, current value, and counter preset.

X1

UDC

X1 X2

X2

Down

X3

X3

CT2 Current Value

CT2 K3

Up

Reset 1

2

1 Counts

2

3

0

Counter Preset

The stage counter has a count input and is reset by the RST instruction. This instruction is useful when programming using the RLLPLUS structured programming. The maximum count value is 9999. The timing diagram below shows the relationship between the counter input, associated discrete bit, current value, counter preset and reset instruction.

X1

X1

SGCNT

CT2 K3

CT2 Current Value

1

2

3

4

0

Counts

RST CT2

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Counter preset