Page 141

Chapter 3: CPU Specifications and Operations System V-memory

Description of Contents

V7753 I/O Configuration Error, stores the correct module ID code. V7754 I/O Configuration Error, identifies the base and slot number. V7755 Error code, stores the fatal error code. V7756 Error code, stores the major error code. V7757 Error code, stores the minor error code. V7760–V7764 Module Error, stores the slot number and error code where an I/O error occurs. V7765 Scan - stores the number of scan cycles that have occurred since the last Program to Run Mode transition. V7766 Contains the number of seconds on the clock. (00 to 59). V7767 Contains the number of minutes on the clock. (00 to 59). V7770 Contains the number of hours on the clock. (00 to 23). V7771 Contains the day of the week. (Mon, Tue, etc.). V7772 Contains the day of the month (1st, 2nd, etc.). V7773 Contains the month. (01 to 12) V7774 Contains the year. (00 to 99) V7775 Scan, stores the current scan time (milliseconds). Scan, stores the minimum scan time that has occurred since the last Program Mode to Run Mode transition V7776 (milliseconds). Scan, stores the maximum scan time that has occurred since the last Program Mode to Run Mode transition V7777 (milliseconds).

DL205 User Manual, 4th Edition, Rev. D

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 3-45

Page 142

Chapter 3: CPU Specifications and Operations

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

DL250–1 System V-memory (DL250 also) System V-memory

Description of Contents

V3710–V3767 V3770–V3777

The default location for multiple preset values for UP/DWN and UP counter 1 or pulse N/A output function The default location for multiple preset values for UP/DWN and UP counter 2. N/A Not used N/A

V7620–V7627 V7620 V7621 V7622 V7623 V7624 V7625 V7626 V7627

Locations for DV–1000 operator interface parameters Sets the V-memory location that contains the value Sets the V-memory location that contains the message Sets the total number (1 – 32) of V-memory locations to be displayed Sets the V-memory location that contains the numbers to be displayed Sets the V-memory location that contains the character code to be displayed Sets the bit control pointer Sets the power up mode Change Preset Value password

V3630–V3707

V7630 V7631 V7632 V7633

V7634 V7635 V7636

3-46

Starting location for the multi–step presets for channel 1. Since there are 24 presets available, the default range is V3630 – V3707. You can change the starting point if necessary. Starting location for the multi–step presets for channel 2. Since there are 24 presets available, the default range is V3710– V3767. You can change the starting point if necessary. Reserved Sets the desired mode for the high-speed counter, interrupt, pulse catch, pulse train, and input filter (see the D2-CTRINT manual, D2-CTRIF-M, for more information). Location is also used for setting the with/without battery option, enable/disable CPU mode change, and power-up in Run Mode option.

Default Values/ Ranges

V0 – V3760 V0 – V3760 1 – 32 V0 – V3760 V0 – V3760 V-memory for X, Y, or C 0,1,2,3,12 Default=0000 Default: V3630 Range: V0 – V3710 Default: V3710 Range: V0 – V3710 Default: 0060 Lower Byte Range: Range: 0 – None 10 – Up 20 – Up/Dwn. 30 – Pulse Out 40 – Interrupt 50 – Pulse Catch 60 – Filtered Dis. Upper Byte Range: Bits 8 – 11, 14–15 Unused Bit 12: With Batt. installed: 0 = disable BATT LED 1 = enable BATT LED Bit 13: Power-up in Run

Contains set-up information for high-speed counter, interrupt, pulse catch,pulse train Default: 1006 output, and input filter for X0 (when D2–CTRINT is installed). Contains set-up information for high-speed counter, interrupt, pulse catch, pulse train Default: 1006 output, and input filter for X1 (when D2–CTRINT is installed). Contains set-up information for high-speed counter, interrupt, pulse catch, pulse train Default: 1006 output, and input filter for X2 (when D2–CTRINT is installed).

DL205 User Manual, 4th Edition, Rev. D

Page 143

Chapter 3: CPU Specifications and Operations

System V-memory

Description of Contents

1 Default Values/Ranges 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

V7637

Contains set-up information for high-speed counter, interrupt, pulse catch, pulse train output, and input filter for X3 (when D2–CTRINT is installed).

V7640

Loop Table Beginning address.

V7641 V7642 V7643–V7647 V7650 V7651 V7652 V7653 V7654 V7655 V7656 V7657 V7660–V7717 V7720–V7722 V7720 V7721 V7722 V7740 V7741 V7747 V7750

Number of Loops Enabled Error Code – V–memory Error Location for Loop Table. Reserved. Port 2 End–code setting Setting (A55A), Non–procedure communications start. Port 2 Data format – Non–procedure communications format setting. Port 2 Format Type setting – Non–procedure communications type code setting. Port 2 Terminate–code setting – Non–procedure communications Termination code setting. Port 2 Store v–mem address – Non–procedure communication data store V–Memory address Port 2 Setup area –0–7 Comm protocol (flag 0) 8–15 Comm time out/response delay time (flag 1). Port 2 Setup area – 0–15 Communication (flag 2, flag 3). Port 2: Setup completion code. Set–up Information – Locations reserved for set-up information used with future options. Locations for DV–1000 operator interface parameters. Titled Timer preset value pointer. Title Counter preset value pointer. HiByte-Titled Timer preset block size, LoByte-Titled Counter preset block size. Port 2 Communication Auto Reset Timer setup. Output Hold or reset setting: Expansion bases 1 and 2 (DL250–1). Location contains a 10ms counter. This location increments once every 10ms. Reserved.

V7751 V7752 V7753 V7754 V7755 V7756 V7757 V7760–V7764 V7765

Default: 1006

V1400–V7340 V10000– V17740 1–4

Fault Message Error Code, stores the 4-digit code used with the FAULT instruction when the instruction is executed. If you’ve used ASCII messages (DL240 only), then the data label (DLBL) reference number for that message is stored here. I/O configuration Error, stores the module ID code for the module that does not match the current configuration. I/O Configuration Error, stores the correct module ID code. I/O Configuration Error, identifies the base and slot number. Error code, stores the fatal error code. Error code, stores the major error code. Error code, stores the minor error code. Module Error, stores the slot number and error code where an I/O error occurs. Scan, stores the total number of scan cycles that have occurred since the last Program Mode to Run Mode transition.

DL205 User Manual, 4th Edition, Rev. D

3-47

Page 144

Chapter 3: CPU Specifications and Operations

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

System V-memory

V7766 V7767 V7770 V7771 V7772 V7773 V7774 V7775 V7776 V7777

V36000–36057 V36100–36157 V36400–36427 V37700–37737

System CRs C740 C741 C743 C750 to C757 C760 to C767

3-48

Description of Contents Contains the number of seconds on the clock. (00 to 59) Contains the number of minutes on the clock. (00 to 59) Contains the number of hours on the clock. (00 to 23) Contains the day of the week. (Mon, Tue, etc.) Contains the day of the month (1st, 2nd, etc.) Contains the month. (01 to 12) Contains the year. (00 to 99) Scan, stores the current scan time (milliseconds) Scan, stores the minimum scan time that has occurred since the last Program Mode to Run Mode transition (milliseconds) Scan, stores the maximum scan time that has occurred since the last Program Mode to Run Mode transition (milliseconds) Analog pointer method for expansion base 1 (DL250–1) Analog pointer method for expansion base 2 (DL250–1) Analog pointer method for local base Port 2: Setup register for Koyo Remote I/O

Description of Contents Completion of setups – ladder logic must turn this relay on when it has finished writing to the Remote I/O setup table. Erase received data – turning on this flag will erase the received data during a communication error. Re-start – Turning on this relay will resume after a communications hang-up on an error. Setup Error – The corresponding relay will be ON if the setup table contains an error. (C750 = master, C751 = slave 1 C757 = slave 7) Communications Ready – The corresponding relay will be ON if the set-up table data is valid. (C760 = master, C761 = slave 1 C767 = slave 7)

DL205 User Manual, 4th Edition, Rev. D

Page 145

Chapter 3: CPU Specifications and Operations

DL260 System V-memory System V-memory

Description of Contents

Default Values/Ranges

V3630–V3707

The default location for multiple preset values for UP/DWN and UP counter 1 or pulse output function

N/A

V3710–V3767

The default location for multiple preset values for UP/DWN and UP counter 2

N/A

V3770–V3777 V7620–V7627 V7620 V7621 V7622 V7623 V7624 V7625 V7626 V7627

Not used

N/A

Locations for DV–1000 operator interface parameters Sets the V-memory location that contains the value Sets the V-memory location that contains the message Sets the total number (1 – 32) of V-memory locations to be displayed Sets the V-memory location that contains the numbers to be displayed Sets the V-memory location that contains the character code to be displayed Sets the bit control pointer Sets the power up mode Change Preset Value password

V0 – V3760 V0 – V3760 1 – 32 V0 – V3760 V0 – V3760 V-memory for X, Y, or C 0,1,2,3,12 Default=0000

V7630

Starting location for the multi–step presets for channel 1. Since there are 24 presets available, the default range is V3630 – V3707. You can change the starting point if necessary.

Default: V3630 Range: V0 – V3710

V7631

Starting location for the multi–step presets for channel 2. Since there are 24 Default: V3710 presets available, the default range is V3710– V3767. You can change the starting Range: V0 – V3710 point if necessary.

V7632 V7633

Reserved Sets the desired mode for the high-speed counter, interrupt, pulse catch, pulse train, and input filter (see the D2-CTRINT manual, D2-CTRIF-M, for more information). Location is also used for setting the with/without battery option, enable/disable CPU mode change, and power-up in Run Mode option.

V7634

Contains set-up information for high-speed counter, interrupt, pulse catch, pulse train output, and input filter for X0 (when D2–CTRINT is installed) Contains set-up information for high-speed counter, interrupt, pulse catch, pulse train output, and input filter for X1 (when D2–CTRINT is installed) Contains set-up information for high-speed counter, interrupt, pulse catch, pulse train output, and input filter for X2 (when D2–CTRINT is installed)

V7635 V7636

Default: 0060 Lower Byte Range: Range: 0 – None 10 – Up 20 – Up/Dwn 30 – Pulse Ou 40 – Interrupt 50 – Pulse Catch 60 – Fltered Dis. Upper Byte Range Bits 8 – 11, 14–15 Unused Bit 12: With Batt. installed: 0 = disable BATT LED 1 = enable BATT LED Bit 13: Power-up in Run Default: 1006 Default: 1006 Default: 1006

DL205 User Manual, 4th Edition, Rev. D

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

3-49

Page 146

Chapter 3: CPU Specifications and Operations

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

System V-memory

Description of Contents

Default Values/ Ranges

V7637

Contains set up information for high speed counter, interrupt, pulse catch, pulse train output, and input filter for X3 (when D2–CTRINT is installed).

V7640

PID Loop Table Beginning address.

V7641 V7642 V7643 - V7647 V7650 V7651 V7652 V7653 V7654 V7655 V7656 V7657 V7660–V7717 V7720–V7722 V7720 V7721 V7722 V7740 V7741 V7742 V7747 V7750

Number of Loops Enabled. Error Code – V–memory Error Location for Loop Table. Reserved. Port 2 End–code Setting (A55A), Non-procedure communications start. Port 2 Data format - Non-procedure communications format setting. Port 2 Format Type setting – Non–procedure communications type code setting. Port 2 Terminate–code setting – Non–procedure communications Termination code setting Port 2 Store v–mem address – Non–procedure communication data store V–Memory address. Port 2 Setup area –0–7 Comm protocol (flag 0) 8–15 Comm time out/response delay time (flag 1) Port 2 Setup area – 0–15 Communication (flag 2, flag 3) Port 2: Setup completion code. Set–up Information – Locations reserved for set up information used with future options. Locations for DV-1000 operator interface parameters. Titled Timer preset value pointer. Title Counter preset value pointer. HiByte-Titled Timer preset block size, LoByte-Titled Counter preset block size.

V7751 V7752 V7753 V7754 V7755 V7756 V7757 V7763–V7764 V7765

3-50

Default: 1006 V400–640 V1400–V7340 V10000–V35740 1–16

Port 2 Communication Auto Reset Timer setup. Output Hold or reset setting: Expansion bases 1 and 2. Output Hold or reset setting: Expansion bases 3 and 4. Location contains a 10ms counter. This location increments once every 10ms. Reserved. Fault Message Error Code, stores the 4-digit code used with the FAULT instruction when the instruction is executed. If you’ve used ASCII messages (DL240 only), then the data label (DLBL) reference number for that message is stored here. I/O configuration Error, stores the module ID code for the module that does not match the current configuration. I/O Configuration Error, stores the correct module ID code. I/O Configuration Error, identifies the base and slot number. Error code, stores the fatal error code. Error code, stores the major error code. Error code, stores the minor error code. Module Error, stores the slot number and error code where an I/O error occurs. Scan, stores the total number of scan cycles that have occurred since the last Program Mode to Run Mode transition.

DL205 User Manual, 4th Edition, Rev. D

Page 147

Chapter 3: CPU Specifications and Operations System V-memory

Description of Contents

1 2 3 4 5 6 7 8 The following system control relays are used for Koyo Remote I/O setup on Communications 9 Port 2. 10 System CRs Description of Contents 11 12 13 14 A B C D

V7766 V7767 V7770 V7771 V7772 V7773 V7774 V7775 V7776 V7777

V36000–36057 V36100–36157 V36200–36257 V36300–36357 V36400–36427 V37700–37737

C740 C741 C743

C750 to C757 C760 to C767

Contains the number of seconds on the clock. (00 to 59). Contains the number of minutes on the clock. (00 to 59). Contains the number of hours on the clock. (00 to 23). Contains the day of the week. (Mon, Tue, etc.). Contains the day of the month (1st, 2nd, etc.). Contains the month. (01 to 12) Contains the year. (00 to 99) Scan, stores the current scan time (milliseconds). Scan, stores the minimum scan time that has occurred since the last Program Mode to Run Mode transition (milliseconds). Scan, stores the maximum scan time that has occurred since the last Program Mode to Run Mode transition (milliseconds). Analog pointer method for expansion base 1 Analog pointer method for expansion base 2 Analog pointer method for expansion base 3 Analog pointer method for expansion base 4 Analog pointer method for local base Port 2: Set-up register for Koyo Remote I/O

Completion of setups – ladder logic must turn this relay on when it has finished writing to the Remote I/O setup table. Erase received data – turning on this flag will erase the received data during a communication error. Re-start – Turning on this relay will resume after a communications hang-up on an error. Setup Error – The corresponding relay will be ON if the set-up table contains an error. (C750 = master, C751 = slave 1... C757= slave 7 Communications Ready – The corresponding relay will be ON if the set-up table data is valid. (C760 = master, C761 = slave 1...C767 = slave 7

DL205 User Manual, 4th Edition, Rev. D

3-51

Page 148

Chapter 3: CPU Specifications and Operations

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

DL205 Aliases

3-52

An alias is an alternate way of referring to certain memory types, such as timer/counter current values, V-memory locations for I/O points, etc., which simplifies understanding the memory address. The use of the alias is optional, but some users may find the alias to be helpful when developing a program. The table below shows how the aliases can be used. DL205 Aliases Address Start

Alias Start

Example

V0

TA0

V1000

CTA0

V40000

VGX

V40200

VGY

V40400

VX0

V40500

VY0

V40600

VC0

V41000

VS0

V41100

VT0

V41140

VCT0

V41200

VSP0

V0 is the timer accumulator value for timer 0, therefore, its alias is TA0. TA1 is the alias for V1, etc. V1000 is the counter accumulator value for counter 0, therefore, its alias is CTA0. CTA1 is the alias for V1001, etc. V40000 is the word memory reference for discrete bits GX0 through GX17, therefore, its alias is VGX0. V40001 is the word memory reference for discrete bits GX20 through GX37, therefore, its alias is VGX20. V40200 is the word memory reference for discrete bits GY0 through GY17, therefore, its alias is VGY0. V40201 is the word memory reference for discrete bits GY20 through GY37, therefore, its alias is VGY20. V40400 is the word memory reference for discrete bits X0 through X17, therefore, its alias is VX0. V40401 is the word memory reference for discrete bits X20 through X37, therefore, its alias is VX20. V40500 is the word memory reference for discrete bits Y0 through Y17, therefore, its alias is VY0. V40501 is the word memory reference for discrete bits Y20 through Y37, therefore, its alias is VY20. V40600 is the word memory reference for discrete bits C0 through C17, therefore, its alias is VC0. V40601 is the word memory reference for discrete bits C20 through C37, therefore, its alias is VC20. V41000 is the word memory reference for discrete bits S0 through S17, therefore, its alias is VS0. V41001 is the word memory reference for discrete bits S20 through S37, therefore, its alias is VS20. V41100 is the word memory reference for discrete bits T0 through T17, therefore, its alias is VT0. V41101 is the word memory reference for discrete bits T20 through T37, therefore, its alias is VT20. V41140 is the word memory reference for discrete bits CT0 through CT17, therefore, its alias is VCT0. V41141 is the word memory reference for discrete bits CT20 through CT37, therefore, its alias is VCT20. V41200 is the word memory reference for discrete bits SP0 through SP17, therefore, its alias is VSP0. V41201 is the word memory reference for discrete bits SP20 through SP37, therefore, its alias is VSP20.

DL205 User Manual, 4th Edition, Rev. D

Page 149

Chapter 3: CPU Specifications and Operations

DL230 Memory Map

1 2 X0 3 Y0 4 C0 C0 5 SP0 6 7 TMR T0 K100 8 V0 K100 9 T0 10 CNT CT0 K10 11 V1000 K100 12 13 CT0 14 A SG S0 B S001 C D NOTE 1: The DL230 systems are limited to 256 discrete I/O points (total) with the present system hardware

Memory Type Input Points

Output Points

Control Relays

Special Relays

Timers

Qty. Decimal

Discrete Memory Reference (octal)

Word Memory Reference (octal)

X0 – X177

V40400 – V40407

1281

Y0 – Y177

V40500 – V40507

1281

C0 – C377

V40600 – V40617

256

SP0 – SP117 SP540 – SP577

V41200 – V41204 V41226 – V41227

112

T0 – T77

Symbol

64

Timer Current Values

None

V0 – V77

64

Timer Status Bits

T0 – T77

V41100 – V41103

64

Counters

CT0 – CT77

64

Counter Current Values

None

V1000 – V1077

64

Counter Status Bits

CT0 – CT77

V41140 – V41143

64

Data Words

None

V2000 – V2377

256

None specific, used with many instructions

Data Words Non–volatile None

V4000 – V4177

128

None specific, used with many instructions

Stages

S0 – S377

V41000 – V41017

256

None

V7620 – V7647 V7750–V7777

48

System parameters

None specific, used for various purposes available. These can be mixed between inputs and output points as necessary.

DL205 User Manual, 4th Edition, Rev. D

3-53

Page 150

Chapter 3: CPU Specifications and Operations

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

DL240 Memory Map Discrete Memory Reference (octal)

Word Memory Qty. Decimal Reference(octal)

Input Points

X0 – X477

V40400 – V40423

3201

Output Points

Y0 – Y477

V40500 – V40523

3201

Control Relays

C0 – C377

V40600 – V40617

256

Special Relays

SP0 – SP137 SP540 – SP617

V41200 – V41205 V41226 – V41230

144

Timers

T0 – T177

Timer Current Values

None

V0 – V177

128

Timer Status Bits

T0 – T177

V41100 – V41107

128

Counters

CT0 – CT177

Counter Current Values

None

V1000 – V1177

128

Counter Status Bits

CT0 – CT177

V41140 – V41147

128

Data Words

None

V2000 – V3777

1024

None specific, used with many instructions

Data Words Non–volatile None

V4000 – V4377

256

None specific, used with many instructions

Stages

S0 – S777

V41000 – V41037

512

System parameters

None

V7620 – V7737 V7746–V7777

106

Memory Type

3-54

128

Symbol X0

Y0 C0

C0

SP0

TMR

T0 K100

V0 K100

T0

CNT CT0 K10

128

V1000 K100

CT0

SG

S001

S0

None specific, used for various purposes

NOTE 1: The DL240 systems are limited to 256 discrete I/O points (total) with the present system hardware available. These can be mixed between inputs and output points as necessary.

DL205 User Manual, 4th Edition, Rev. D