Chapter 5: Standard RLL Instructions
Interrupt Instructions
1 The Interrupt instruction allows a section of ladder logic to 2 be placed outside the main body of the program and executed when needed. Interrupts can be called from the program or by external interrupts via the counter interface module (D2– 3 CTRINT), which provides 4 interrupts. 4 The software interrupt uses interrupt #00 which means the hardware interrupt #0 and the software interrupt cannot be used together. 5 Typically, interrupts will be used in an application where a fast response to an input is needed or a program section needs to execute faster than the normal CPU scan. The interrupt label 6 and all associated logic must be placed after the End statement in the program. When the interrupt routine is called from the interrupt module or software interrupt, the CPU will complete execution of the instruction it is currently processing in ladder logic, then execute the 7 designated interrupt routine. Interrupt module interrupts are labeled in octal to correspond with the hardware input signal (X1 will initiate interrupt INT1). There is only one software 8 interrupt, and it is labeled INT 0. The program execution will continue from the point it was before the interrupt occurred once the interrupt is serviced. 9 The software interrupt is set up by programming the interrupt time in V7634. The valid range is 3 to 999 ms. The value must be a BCD value. The interrupt will not execute if the value is 10 out of range. NOTE: See the example program of a software interrupt. 11 Operand Data Type DL240 Range DL250-1 Range DL260 Range 12 aaa aaa aaa 13 DL240/250-1/260 Software DL240/250-1/260 Hardware 14 Interrupt Input Interrupt Routine Interrupt Input Interrupt Routine A B C D
Interrupt (INT)
230 240 250-1 260 DS Used HPP Used
O aaa
INT
Constant
0
0-3
0-3
0-3
V7634 sets interrupt time
INT 0
INT 0
-
-
X0 (cannot be used along with s/w interrupt) X1 X2 X3
INT 1 INT 2 INT 3
DL205 User Manual, 4th Edition, Rev. D
5-187
Page 412
Chapter 5: Standard RLL Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Interrupt Return (IRT) When an Interrupt Return is executed in the interrupt routine, the
230 CPU will return to the point in the main body of the program from 240 which it was called. The Interrupt Return is programmed as the last 250-1 instruction in an interrupt routine and is a stand alone instruction (no 260 input contact on the rung).
IRT
Interrupt Return Conditional (IRTC) The Interrupt Return Conditional instruction is a optional instruction with an input contact to implement a conditional return from the 240 used interrupt routine. The Interrupt Return is required to terminate the 250-1 interrupt routine. 260 230
IRTC
Enable Interrupts (ENI)
230 The Enable Interrupt instruction is programmed in the main body of 240 the application program (before the End instruction) to enable hardware software interrupts. Once the coil has been energized, interrupts will 250-1 or be enabled until they are disabled by the Disable Interrupt instruction. 260
ENI
Disable Interrupts (DISI)
The Disable Interrupt instruction is programmed in the main body of
230 the application program (before the End instruction) to disable both 240 hardware or software interrupts. Once the coil has been energized, 250-1 interrupts will be disabled until they are enabled by the Enable Interrupt 260 instruction.
5-188
DL205 User Manual, 4th Edition, Rev. D
DISI
DS Used HPP Used
Page 413
Chapter 5: Standard RLL Instructions
Interrupt Example for Interrupt Module In the following example, when X40 is on, the interrupts will be enabled. When X40 is off, the interrupts will be disabled. When an interrupt signal X1 is received, the CPU will jump to the interrupt label INT O 1. The application ladder logic in the interrupt routine will be performed. The CPU will return to the main body of the program after the IRT instruction is executed. DirectSOFT
Handheld Programmer Keystrokes $
X40 ENI
E
STR
SHFT
E
4
SP STRN X40 DISI
. . . END
INT
O1
X20
Y5 SETI
X21
Y10
4
N TMR
I
E
A
D
SHFT
E
SHFT
I
$
SHFT
I
X SET
SHFT
I
$
SHFT
I
X SET
SHFT
I
SHFT
I
R ORN
STR
STR
I
4
SHFT
3
A
8
ENT
8
ENT
0
S RST
4
N TMR
D
8
N TMR
T MLR
8
ENT
0
3
I
8
ENT B C
8
F
8
C
8
B
8 T MLR
ENT
2 5 2 1
A
1 0
ENT ENT
ENT B A
1 0
ENT
SETI
IRT
DL205 User Manual, 4th Edition, Rev. D
ENT ENT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
5-189
Page 414
Chapter 5: Standard RLL Instructions
In the following example, when X1 is on, the value 10 is copied to V7634. This value sets the software interrupt to 10ms. When X20 turns on, the interrupt will be enabled. When X20 turns off, the interrupt will be disabled. Every 10ms the CPU will jump to the interrupt label INT O 0. The application ladder logic in the interrupt routine will be performed. If X35 is not on, Y0–Y17 will be reset to off and then the CPU will return to the main body of the program. DirectSOFT
Handheld Programmer Keystrokes SP0
$
LD K40
V7633 X1
SHFT GX OUT $
ENI
X20 DISI
. . . END
O0
L ANDST
STR
SHFT
X20
INT
B
STR
E
4
SP STRN
D
0
SHFT
B
H
G
D
7
SHFT
K JMP
B
SHFT
H
G
D
C
A
ENT
2
N TMR
I
C
A
I
2
E
SHFT
I
$
SHFT
I
X SET
SHFT
I
SP STRN
SHFT
I
S RST
SHFT
I
SHFT
I
R ORN
8
0
3
A D
0 3
ENT ENT
4
D
8
N TMR
T MLR
3
I
8
D
8
A
8 T MLR
0 4
E
4
ENT
ENT
ENT
A
F
8
E
ENT
C
8
3
A
ENT
0
N TMR
6
1
ENT
8
S RST
7
2 5 3 0
A
0 0
ENT ENT
ENT F
5
ENT B
1
H
7
ENT
ENT
Y5 SETI
Y0
Y17 RSTI
5-190
6
4
* The value entered, 3-999, must be followed by the digit 4 to complete the instruction.
X20
X35
ENT K JMP
V AND
SHFT
8
A
ENT
3
SHFT
STR
V
1
D
3
SP STRN
3
$ K104*
Copy the value in the lower 16 bits of the accumulator to V7634
D
SHFT
Load the constant value (K10) into the lower 16 bits of the accumulator *
V7634
L ANDST
GX OUT
LD
OUT
SHFT
STR
SHFT OUT
Standard RLL Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Interrupt Example for Software Interrupt
IRT
NOTE: Only one software interrupt is allowed and it must be Int0.
DL205 User Manual, 4th Edition, Rev. D
Page 415
Chapter 5: Standard RLL Instructions
Intelligent I/O Instructions
1 The Read from Intelligent Module instruction reads a block of data 2 (1 to 128 bytes maximum) from an intelligent I/O module into the CPU’s V-memory. It loads the function parameters into the first and second level of the accumulator stack, and the accumulator by three 3 additional instructions. Listed below are the steps to program the Read from Intelligent module function. 4 Step 1: L oad the base number (0 to 3) into the first byte and the slot number (0 to 7) into the second byte of the second level of the accumulator stack. 5 Step 2: L oad the number of bytes to be transferred into the first level of the accumulator stack (maximum of 128 bytes). 6 Step 3: L oad the address from which the data will be read into the accumulator. This parameter must be a HEX value. Step the RD instruction that specifies the starting V-memory location (Vaaa) into which the 7 data will be read. Helpful hint: Use the LDA instruction to convert an octal address to its HEX equivalent and 8 load it into the accumulator when the hex format is required. 9 Operand Data Type DL230 Range DL240 Range DL250-1 Range DL260 Range aaa aaa aaa aaa 10 Discrete Bit Flags Description 11 NOTE: Status flags are valid only until another instruction uses the same flag. 12 In the following example, when X1 is on, the RD instruction will read six bytes of data from an intelligent module in base 1, slot 2 starting at address 0 in the intelligent module and copy 13 the information into V-memory locations V1400–V1402. 14 A B C D
Read from Intelligent Module (RD)
230 240 250-1 260 DS Used HPP Used
RD
V aaa
V-memory
V
All (See page 3-53)
SP54
All (See page 3-54)
All (See page 3-55)
All (See page 3-56)
On when RX, WX, RD, WT instructions are executed with the wrong parameters.
DirectSOFT X1
CPU
LD
K0102
LD
K6
The constant value K0102 specifies the base number (01) and the base slot number (02) The constant value K6 specifies the number of bytes to be read
K0
RD
V1400
The constant value K0 specifies the starting address in the intelligent module
V1400 is the starting location in the CPU where the specified data will be stored
Data 12
Address 0
34
Address 1
56 90
Address 2 Address 3 Address 4
01
Address 5
V1402 0 1 9 0
V1403 X X X X
78
V1404 X X X X
Handheld Programmer Keystrokes $
LD
Intelligent Module
V1400 3 4 1 2 V1401 7 8 5 6
B
STR
SHFT
L ANDST
D
SHFT
L ANDST
D
SHFT
L ANDST
D
SHFT
R ORN
D
1
3 3 3
3
ENT
PREV
A
PREV
G
PREV
A
B
E
1
0
6
0
4
B
1
A
0
C
2
ENT
ENT
ENT
A
0
A
0
DL205 User Manual, 4th Edition, Rev. D
ENT
5-191
Page 416
Chapter 5: Standard RLL Instructions
Write to Intelligent Module instruction writes a block of data (1 WT 230 The V aaa to 128 bytes maximum) to an intelligent I/O module from a block 240 of V-memory in the CPU. The function parameters are loaded into 250-1 the first and second level of the accumulator stack and the accumulator by three additional 260 instructions. Listed below are the steps necessary to program the Read from Intelligent module function.
DS Used HPP Used
5-192
Step the base number (0 to 3) into the first byte and the slot number (0 to 7) into the second byte of the second level of the accumulator stack. Step the number of bytes to be transferred into the first level of the accumulator stack (maximum of 128 bytes). Step the intelligent module address which will receive the data into the accumulator. This parameter must be a HEX value. Step the WT instruction which specifies the starting V-memory location (Vaaa) where the data will be written from in the CPU.
Helpful hint: Use the LDA instruction to convert an octal address to its HEX equivalent and load it into the accumulator when the hex format is required. Operand Data Type V-memory
V
DL230 Range
DL240 Range
DL250-1 Range aaa aaa aaa aaa
All (See page 3-53)
All (See page 3-54)
All (See page 3-55)
All (See page 3-56)
Discrete Bit Flags SP54
DL260 Range
Description On when RX, WX, RD, WT instructions are executed with the wrong parameters.
NOTE: Status flags are valid only until another instruction uses the same flag.
In the following example, when X1 is on, the WT instruction will write six bytes of data to an intelligent module in base 1, slot 2 starting at address 0 in the intelligent module and copy the information from V-memory locations V1400–V1402. Standard
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Write to Intelligent Module (WT)
DirectSOFT X1
LD K0102
LD K6
LD K0
CPU
The constant value K0102 specifies the base number (01) and the base slot number (02) The constant value K6 specifies the number of bytes to be written
The constant value K0 specifies the starting address in the intelligent module
V1400
V1400 is the starting location in the CPU where the specified data will be written from
DL205 User Manual, 4th Edition, Rev. D
Data
V1377
X
X
X
X
V1400
3
4
1
2
V1401
7
8
5
6
V1402
0
1
9
0
V1403
X
X
X
X
V1404
X
X
X
X
12
Address 0
34
Address 1
56
Address 2
78
Address 3
90
Address 4
01
Address 5
Handheld Programmer Keystrokes $
WT
Intelligent Module
B
STR
1
SHFT
L ANDST
D
SHFT
L ANDST
D
SHFT
L ANDST
D
SHFT
W ANDN
T MLR
3 3 3
ENT PREV
A
PREV
G
PREV
A
B
E
1
0 6 0 4
B
1
A
0
C
2
ENT ENT A
0
A
0
ENT
ENT
Page 417
Chapter 5: Standard RLL Instructions
Network Instructions
1 The Read from Network instruction is used by the master device 2 on a network to read a block of data from another CPU. The function parameters are loaded into the first and second levels of the accumulator stack and the accumulator by three additional 3 instructions. Listed below are the steps necessary to program the Read from Network function. 4 Step 1: L oad the slave address (0 to 90 BCD) into the first byte, and load the PLC internal port (KF1) or slot number of the master DCM or ECOM (0 to 7) into the second byte of the 5 second level of the accumulator stack. Step the number of bytes (0 to 128 BCD, multiple of 2) to be transferred into the first level of the accumulator stack. 6 Step the address of the data to be read into the accumulator. This parameter requires a HEX value. 7 Step the RX instruction which specifies the starting V-memory location (Aaaa) where the data will be read from in the slave. 8 Helpful hint: For parameters that require HEX values, the LDA instruction can be used to convert an octal address to the HEX equivalent and load the value into the accumulator. 9 Operand Data Type DL240 Range DL250-1 Range DL260 Range A aaa aaa aaa 10 11 12 13 14 A B C D
Read from Network (RX)
230 240 250-1 260 DS Used HPP Used
RX
A aaa
V-memory
V
Pointer
P
Inputs Outputs Control Relays Stage Timer Counter Global I/O Special Relay
X Y C S T CT GX/GY SP
All (See page 3 - 54) All V-memory (See page 3 - 54) 0-477 0-477 0-377 0-777 0-177 0-177 0-137 540-617
All (See page 3 - 55) All V-memory (See page 3 - 55) 0-777 0-777 0-1777 0-1777 0-377 0-177 0-777
All (See page 3 - 56) All V-memory (See page 3 - 56) 0-1777 0-1777 0-3777 0-1777 0-377 0-377 0-3777 0-777
DL205 User Manual, 4th Edition, Rev. D
5-193
Page 418
Chapter 5: Standard RLL Instructions
DirectSOFT X1
SP124
LD
5-194
LD
–or–
K0205
The constant value K0205 specifies the ECOM/DCM slot number (2) and the slave address (5) LD
KF105 The constant value KF105 specifies the bottom port and the slave address (5) (DL250–1 and DL260 only)
K10 The constant value K10 specifies the number of bytes to be read LDA O 2300 Octal address 2300 is converted to 4C0 HEX and loaded into the accumulator. V2300 is the starting location for the Master CPU where the specified data will be read into
Master CPU
Slave CPU
V2277
X
X
X
X
X
X
X
X V1777
V2300
3
4
5
7
3
4
5
7
V2000
V2301
8
5
3
4
8
5
3
4
V2001
V2302
1
9
3
6
1
9
3
6
V2002
V2303
9
5
7
1
9
5
7
1
V2003
V2304
1
4
2
3
1
4
2
3
V2004
V2305
X
X
X
X
X
X
X
X V2005
RX V2000 V2000 is the starting location in the Slave CPU where the specified data will be read from
Handheld Programmer Keystrokes $
B
STR
W ANDN
1
SHFT
SHFT
L ANDST
D
SHFT
L ANDST
D
SHFT
L ANDST
D
SHFT
R ORN
X SET
ENT SP STRN
3 3 3
A
B
1
C
2
E
SHFT
K JMP
C
SHFT
K JMP
B
C
D
0 C
Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
In the following example, when X1 is on and the module busy relay SP124 (see special relays) is not on, the RX instruction will access an ECOM or DCM operating as a master in slot 2. Ten consecutive bytes of data (V2000 – V2004) will be read from a CPU at station address 5 and copied into V-memory locations V2300–V2304 in the CPU with the master DCM or ECOM.
DL205 User Manual, 4th Edition, Rev. D
2
A
2 0
A
4 2 1 3 0
ENT A A A A
0 0 0 0
F
5
ENT
ENT A
0
ENT
ENT
Page 419
Chapter 5: Standard RLL Instructions
Write to Network (WX)
1 2 Write to Network function. 3 Step 1: L oad the slave address (0 to 90 BCD) into the first byte and the PLC internal port (KF1) or slot number of the master DCM or ECOM (0 to 7) into the second byte of the second level 4 of the accumulator stack. Step 2: L oad the number of bytes (0 to 128 BCD, multiple of 2) to be transferred into the first level of the accumulator stack. 5 Step 3: L oad the address of the data in the master that is to be written to the network into the accumulator. This parameter requires a HEX value. 6 Step 4: nsert the WX instruction which specifies the starting V-memory location (Aaaa) where the data will be written to the slave. 7 Helpful hint:, For parameters that require HEX values, the LDA instruction can be used to convert an octal address to the HEX equivalent and load the value into the accumulator. 8 Operand Data Type DL240 Range DL250-1 Range DL260 Range A aaa aaa aaa 9 10 11 12 13 14 A B C D
Write to Network instruction is used to write a block of data 230 The from the master device to a slave device on the same network. The 240 function parameters are loaded into the first and second levels of 250-1 the accumulator stack and the accumulator by three additional 260 instructions. Listed below are the steps necessary to program the DS Used HPP Used
V-memory
V
Pointer
P
Inputs Outputs Control Relays Stage Timer Counter Global I/O Special Relay
X Y C S T CT GX/GY SP
All (See page 3 - 54) All V-memory (See page 3 - 54) 0-477 0-477 0-377 0-777 0-177 0-177 0-137 540-617
All (See page 3 - 55) All V-memory (See page 3 - 55) 0-777 0-777 0-1777 0-1777 0-377 0-177 0-777
WX
A aaa
All (See page 3 - 56) All V-memory (See page 3 - 56) 0-1777 0-1777 0-3777 0-1777 0-377 0-377 0-3777 0-777
DL205 User Manual, 4th Edition, Rev. D
5-195
Page 420
Chapter 5: Standard RLL Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5-196
In the following example when X1 is on and the module busy relay SP124 (see special relays) is not on, the WX instruction will access a DCM or ECOM operating as a master in slot 2. Ten consecutive bytes of data is read from the CPU at station address 5 and copied to V-memory locations V2000–V2004 in the slave CPU. DirectSOFT X1
SP124
LD
LD
–or–
K0205
KF105
The constant value K0205 specifies the ECOM/DCM slot number (2) and the slave address (5)
The constant value KF105 specifies the bottom port and the slave address (5) (DL250–1 and DL260 only)
LD K10 The constant value K10 specifies the number of bytes to write LDA
Master CPU
Slave CPU
O 2300
V2277
X
X
X
X
X
X
X
X V1777
Octal address 2300 is converted to 4C0 HEX and loaded into the accumulator. V2300 is the starting location for the Master CPU where the specified data will be written from.
V2300
3
4
5
7
3
4
5
7
V2000
V2301
8
5
3
4
8
5
3
4
V2001
V2302
1
9
3
6
1
9
3
6
V2002
V2303
9
5
7
1
9
5
7
1
V2003
V2304
1
4
2
3
1
4
2
3
V2004
V2305
X
X
X
X
X
X
X
X V2005
WX V2000 V2000 is the starting location in the Slave CPU where the specified data will be written to.
Handheld Programmer Keystrokes $
B
STR
W ANDN
1
SHFT
SHFT
L ANDST
D
SHFT
L ANDST
D
SHFT
L ANDST
D
SHFT
W ANDN
X SET
ENT SP STRN
3 3 3
A
B
1
C
2
E
4
ENT
SHFT
K JMP
C
SHFT
K JMP
B
SHFT
O INST#
C
V AND
C
A
0 SHFT
2 1
2
DL205 User Manual, 4th Edition, Rev. D
A A
0 0 2 0
F
5
ENT
ENT D A
3 0
A A
0 0
A
0
ENT
ENT