Page 511
Chapter 5: Standard RLL Instructions
ECEMRDS Example
1 2 3 4 5 6 7 8 NOTE: An ECOM100 IBox instruction is used without a permissive contact. The top line will be identified in BOLD italics, and the instruction name and ID will be in BOLD characters. 9 Rung 2: Whenever an EStop is pushed, ensure that the president of the company gets copies 10 of all Emails being sent. The ECOM100 EMail Setup IBox allows you to set/change the SMTP Email settings stored in the ECOM100. 11 12 13 14 A B C D Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module.V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130-byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module. ECOM100 Config
1
ECOM100 ECOM100# Slot Status Workspace Msg Buffer (65 WORDs)
IB-710 K0 K1 V400 V401 V402-502
(Example continued on next page)
DL205 User Manual, 4th Edition, Rev. D
5-287
Page 512
Chapter 5: Standard RLL Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5-288
ECEMRDS Example (cont’d) Rung 3: Once the EStop is pulled out, take the president off the cc: list by restoring the default EMail setup in the ECOM100. The ECEMRDS is leading edge triggered, not power-flow driven (similar to a counter input leg). The ROM-based EMail configuration stored in the ECOM100 will be copied over the “working copy” whenever the power flow into the IBox goes from OFF to ON (the working copy can be changed by using the ECEMSUP IBox). If successful, turn on C102. If there is a failure, turn on C103. If it fails, you can look at V2001 for the specific error code.
DL205 User Manual, 4th Edition, Rev. D
Page 513
Chapter 5: Standard RLL Instructions
ECOM100 E-mail Setup (ECEMSUP) (IB-712)
240 250-1 260 230
DS5
Used
HPP
N/A
1 2 3 4 5 6 7 8 9 10 11 12 ECEMSUP Parameters • this is a logical number associated with this specific ECOM100 module in the 13 specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number. 14 • specifies a V-memory location that will be used by the instruction. • specifies a bit that will turn on once the request is completed successfully. A • specifies a bit that will turn on if the instruction is not completed successfully. • Code: specifies the location where the Error Code will be written. • Server IP Addr: optional parameter that specifies the IP Address of the SMTP Server on the B ECOM100’s network. • Name: optional parameter that specifies the sender name that will appear in the “From:” C field to those who receive the e-mail. • EMail: optional parameter that specifies the sender EMail address that will appear in the D “From:” field to those who receive the e-mail. ECOM100 EMail Setup, on a leading edge transition, will modify the working copy of the EMail setup currently in the ECOM100 based on the specified ECOM100#, which corresponds to a specific unique ECOM100 Configuration (ECOM100) at the top of your program. You may pick and choose any or all fields to be modified using this instruction. Note that these changes are cumulative: if you execute multiple ECOM100 EMail Setup IBoxes, then all of the changes are made in the order they are executed. Also note that you can restore the original ECOM100 EMail Setup that is stored in the ECOM100 to the working copy by using the ECOM100 Restore Default EMail Setup (ECEMRDS) IBox. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Either the Success or Error bit parameter will turn on once the command is complete. If there is an error, the Error Code parameter will report an ECOM100 error code (less than 100), or a PLC logic error (greater than 1000). You are limited to approximately 100 characters/bytes of setup data for the entire instruction. So if needed, you could divide the entire setup across multiple ECEMSUP IBoxes on a fieldby-field basis, for example do the Carbon Copy (cc:) field in one ECEMSUP IBox and the remaining setup parameters in another. In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the ECOM100 circuit board.
DL205 User Manual, 4th Edition, Rev. D
5-289
Page 514
Chapter 5: Standard RLL Instructions ECEMSUP Parameters (cont’d)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5-290
• Number: optional parameter that specifies the TCP/IP Port Number to send SMTP requests; usually this does not need to be configured (see your network administrator for information on this setting). • (sec): optional parameter that specifies the number of seconds to wait for the SMTP Server to send the EMail to all the recipients. • optional parameter that specifies a list of “carbon copy” Email addresses to send all EMails to.
Parameter ECOM100# ⸠ ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ K Workspace ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ V Success ⸠ ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ X,Y,C,GX,GY,B Error ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ X,Y,C,GX,GY,B Error Code⸠ ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ V
DL205 User Manual, 4th Edition, Rev. D
DL205 Range K0-255 See DL205 V-memory map - Data Words See DL205 V-memory map See DL205 V-memory map See DL205 V-memory map - Data Words
Page 515
Chapter 5: Standard RLL Instructions
ECEMSUP Example
1 2 3 4 5 6 7 8 NOTE: An ECOM100 IBox instruction is used without a permissive contact. The top line will be identified in 9 BOLD italics, and the instruction name and ID will be in BOLD characters. 10 11 12 13 14 A B C D
Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module.V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130-byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module. ECOM100 Config
1
ECOM100 ECOM100# Slot Status Workspace Msg Buffer (65 WORDs)
IB-710 K0 K1 V400 V401 V402-502
(Example continued on next page)
DL205 User Manual, 4th Edition, Rev. D
5-291
Page 516
Chapter 5: Standard RLL Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5-292
ECEMSUP Example (cont’d) Rung 2: Whenever an EStop is pushed, ensure that president of the company gets copies of all EMails being sent.The ECOM100 EMail Setup IBox allows you to set/change the SMTP EMail settings stored in the ECOM100. The ECEMSUP is leading edge triggered, not power-flow driven (similar to a counter input leg). At power-up, the ROM-based EMail configuration stored in the ECOM100 is copied to a RAM-based “working copy”. You can change this working copy by using the ECEMSUP IBox. To restore the original ROM-based configuration, use the Restore Default EMail Setup ECEMRDS IBox. If successful, turn on C100. If there is a failure, turn on C101. If it fails, you can look at V2000 for the specific error code.
Rung 3: Once the EStop is pulled out, take the president off the cc: list by restoring the default EMail setup in the ECOM100.
DL205 User Manual, 4th Edition, Rev. D
Page 517
Chapter 5: Standard RLL Instructions
ECOM100 IP Setup (ECIPSUP) (IB-717)
240 250-1 260 230
DS5
Used
HPP
N/A
ECOM100 IP Setup will configure the three TCP/IP parameters in the ECOM100: IP Address, Subnet Mask, and Gateway Address, on a leading edge transition to the IBox. The ECOM100 is specified by the ECOM100#, which corresponds to a specific unique ECOM100 Configuration (ECOM100) IBox at the top of your program. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Either the Success or Error bit parameter will turn on once the command is complete. If there is an error, the Error Code parameter will report an ECOM100 error code (less than 100), or a PLC logic error (greater than 1000). This setup data is stored in Flash-ROM in the ECOM100 and will disable the ECOM100 module for at least a half second until it writes the Flash-ROM. Therefore, it is HIGHLY RECOMMENDED that you only execute this IBox ONCE on the second scan. Since it requires a LEADING edge to execute, use a NORMALLY CLOSED SP0 (NOT First Scan) to drive the power flow to the IBox. In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the ECOM100 circuit board. ECIPSUP Parameters • this is a logical number associated with this specific ECOM100 module in the specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number. • specifies a V-memory location that will be used by the instruction. • specifies a bit that will turn on once the request is completed successfully. • specifies a bit that will turn on if the instruction is not completed successfully. • Code: specifies the location where the Error Code will be written. • Address: specifies the module’s IP Address. • Mask: specifies the Subnet Mask for the module to use. • Address: specifies the Gateway Address for the module to use.
Parameter
DL205 Range
ECOM100# ⸠ ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ K Workspace ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ V Success ⸠ ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ X,Y,C,GX,GY,B Error ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ X,Y,C,GX,GY,B Error Code⸠ ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ V IP Address⸠ ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠IP Address Subnet Mask Address⸠ ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠IP Address Mask Gateway Address⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠IP Address
K0-255 See DL205 V-memory map - Data Words See DL205 V-memory map See DL205 V-memory map See DL205 V-memory map - Data Words 0.0.0.1. to 255.255.255.254 0.0.0.1. to 255.255.255.254 0.0.0.1. to 255.255.255.254
DL205 User Manual, 4th Edition, Rev. D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
5-293
Page 518
Chapter 5: Standard RLL Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5-294
ECIPSUP Example Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module. V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130-byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module. ECOM100 Config ECOM100 ECOM100# Slot Status Workspace Msg Buffer (65 WORDs)
1
IB-710 K0 K1 V400 V401 V402-502
NOTE: An ECOM100 IBox instruction is used without a permissive contact. The top line will be identified in BOLD italics, and the instruction name and ID will be in BOLD characters.
Rung 2: On the second scan, configure all of the TCP/IP parameters in the ECOM100: IP Address: 192.168.12.100 Subnet Mask: 255.255.0.0 Gateway Address: 192.168.0.1 The ECIPSUP is leading edge triggered, not power-flow driven (similar to a counter input leg). The command to write the TCP/IP configuration parameters will be sent to the ECOM100 whenever the power flow into the IBox goes from OFF to ON. If successful, turn on C100. If there is a failure, turn on C101. If it fails, you can look at V2000 for the specific error code.
DL205 User Manual, 4th Edition, Rev. D
Page 519
Chapter 5: Standard RLL Instructions
ECOM100 Read Description (ECRDDES) (IB-726)
230 240 250-1 260 DS5
Used
HPP
N/A
1 2 3 4 5 6 ECRDDES Parameters • this is a logical number associated with this specific ECOM100 module in the 7 specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number 8 • specifies a V-memory location that will be used by the instruction • specifies a bit that will turn on once the request is completed successfully 9 • specifies a bit that will turn on if the instruction is not successfully completed • specifies the starting buffer location where the ECOM100’s Description will be placed • Chars: specifies the number of characters (bytes) to read from the ECOM100’s Description 10 field 11 Parameter DL205 Range 12 13 14 A B C D ECOM100 Read Description will read the ECOM100’s Description field up to the number of specified characters on a leading edge transition to the IBox. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Either the Success or Error bit parameter will turn on once the command is complete. In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the ECOM100 circuit board.
ECOM100# ⸠ ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ K Workspace ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ V Success ⸠ ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ X,Y,C,GX,GY,B Error ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ X,Y,C,GX,GY,B Description ⸠ ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ V Num Chars⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ K
K0-255 See DL205 V-memory map - Data Words See DL205 V-memory map See DL205 V-memory map See DL205 V-memory map - Data Words K1-128
DL205 User Manual, 4th Edition, Rev. D
5-295
Page 520
Chapter 5: Standard RLL Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5-296
ECRDDES Example Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module. V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130-byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module. ECOM100 Config ECOM100 ECOM100# Slot Status Workspace Msg Buffer (65 WORDs)
1
IB-710 K0 K1 V400 V401 V402-502
NOTE: An ECOM100 IBox instruction is used without a permissive contact. The top line will be identified in BOLD italics, and the instruction name and ID will be in BOLD characters.
Rung 2: On the 2nd scan, read the Module Description of the ECOM100 and store it in V3000 thru V3007 (16 characters). This text can be displayed by an HMI. The ECRDDES is leading edge triggered, not power-flow driven (similar to a counter input leg). The command to read the module description will be sent to the ECOM100 whenever the power flow into the IBox goes from OFF to ON. If successful, turn on C100. If there is a failure, turn on C101.
DL205 User Manual, 4th Edition, Rev. D