DL305 User Manual: Chapter 3: DL330/DL330P/DL340 CPU Specifications, pages 64 to 69

Pages 64 to 69 of 359, from DL305 User Manual

The original document is the PDF (4.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect D3-08TD2, AutomationDirect D3-16TD2, Konnect-It D3-08TD2, Koyo D3-08TD2, Konnect-It D3-16TD2 and Koyo D3-16TD2

Page 64

3--17

DL330/DL330P/DL340 CPU Specifications

Many CPU tasks involve the use of predefined functions. These are often called Auxiliary (AUX) Functions. The AUX Functions perform many different operations, ranging from simple operating mode changes to determining the firmware revision number. You can access all of the AUX Functions from DirectSOFT menu options, but not from the DL305 Handheld Programmer. You can still perform some of the operations with the Handheld Programmer, but they are accomplished by using a certain series of keystrokes rather than by entering a specific AUX function. NOTE: Neither DirectSOFT or the Handheld Programmer utilize the numbers shown for the AUX functions. These numbers have been included because many of you may already have existing software packages that can be used with these CPUs. If you do already have an existing software package, remember that any additional features (such as added I/O, CRs, etc. available with the DL340 CPU) may not be accessible. AUX Function and Description

DL330, DL330P, DL340

AUX 1*, Diagnostics and PLC Modes

Software

HP

10

Program Syntax Check (Grammar check)

P

P

Compare PLC to Disk

P

PLC Operational Mode

P

P

13

Revision Number

P

Software

HP

AUX 3*, Clear PLC Memory 31

Ladders

P

P

32

Data Registers

P

33

Timer / Counter Accumulators

AUX 6*, Save Data from PLC

P

Software

HP

Ladders

P

P

62

Data Registers

P

AUX 9*, Load Data to PLC 91

Ladders

P

P

92

Data Registers

P

P

P

Password Operations None

Password, Function or keystrokes available X, Not available P

DL330/DL330P/DL340 CPU Specifications

61

DL330/DL330P/DL340 CPU Specifications

11 12

DL330/DL330P/DL340 Specifications

What are Auxiliary Functions?

DL330/DL330P/DL340 Specifications

DL305 User Manual, Rev. D

Page 65

DL330/DL330P/DL340 CPU Specifications

Connecting the Programming Devices

You can mount the Handheld directly to the port of the CPU, or you can use a cable. The cable, part number D3--HPCBL, is approximately 4.5 feet (1.5m) in length and provides more flexibility. There are two different handheld programmers for the DL305 CPUs. The D3--HP can be used with either the DL330 or the DL340. The D3--HPP can only be used with the DL330P. The D3--HPP supports the RLL PLUS features. If you’re using a Personal Computer with the DirectSOFT programming package, a Data Communications Unit (either RS232C or RS422) must be used to interface to the DL330/DL330P CPUs. DCUs may also be used to establish a connection between the DL305 and an operator interface or a network. The DL340 CPU provides two built-in RS232C ports which can be used to directly connect to a personal computer, operator interface or network. The DCU may also be used with the DL340 if the built-in ports are otherwise occupied.

DL330/DL330P/DL340 Specifications

DL330/DL330P/DL340 CPU Specifications

DL330/DL330P/DL340 CPU Specifications

DL330/DL330P/DL340 Specifications

3--18

DL305 User Manual, Rev. D

Page 66

DL330/DL330P/DL340 CPU Specifications

Handheld Programmer

DL340 CPU with 2 Built-in RS232C Communication Ports

DL330/DL330P/DL340 Specifications

Programming the DL340 CPU with either the Handheld programmer or the PC

3--19

RS232C Connect to either port

DL330 or DL330P

DCU RS232C or RS422 Handheld Programmer

DL330/DL330P/DL340 CPU Specifications

RS232C or RS422

DL330/DL330P/DL340 CPU Specifications

Programming the DL330 CPU with either the Handheld programmer or the PC (using a Data Communication Unit)

DL330/DL330P/DL340 Specifications

DL305 User Manual, Rev. D

Page 67

DL330/DL330P/DL340 CPU Specifications

Changing the CPU There are two modes of operation for the DL305 CPUs: Mode of Operation S RUN, executes the application program and updates I/O modules S PGM, allows program entry, does not execute the application program or update I/O modules The CPU modes for all DL305 CPUs can be changed by using either a Handheld Programmer or DirectSOFT. The DL330 and DL330P require a Data Communications Unit when using DirectSOFT. This is discussed later in this chapter. Since the DL340 has the possibility of being accessed through multiple ports at the same time, the Handheld Programmer and DCU have priority over the built-in RS232C ports during mode change operations. If no Handheld Programmer or DCU is online, DirectSOFT can perform mode changes through either of the built-in ports. When the Handheld Programmer or DCU is online and a mode change is attempted with DirectSOFT, the Handheld Programmer or DCU will immediately change the mode back to the original mode. This forces the CPU mode to always correspond with the keyswitch position on the Handheld Programmer. WARNING: The CPU will automatically change modes when you connect the Handheld Programmer if the keyswitch is set for a different mode of operation. For example, if the CPU is in Run mode and the Handheld Programmer keyswitch is set to the PRG (Program) position, the CPU will automatically enter Program mode when the Handheld is connected.

DL330/DL330P/DL340 CPU Specifications

DL330/DL330P/DL340 CPU Specifications

DL330/DL330P/DL340 Specifications

3--20

RUN PRG LOAD TAPE

DL330/DL330P/DL340 Specifications

The LOAD position is used for uploading a program from CPU memory to a cassette tape, or downloading a program from cassette tape to CPU memory.

DL305 User Manual, Rev. D

Page 68

DL330/DL330P/DL340 CPU Specifications

Before you enter a new program, you should always clear the CPU memory. Only a few keystrokes are required. The next few steps show how to clear the CPU memory using the handheld programmer. Put the handheld programmer’s key switch in the PRG position. Attach the handheld programmer directly to the front of the CPU making sure that the port on the back of the programmer aligns properly with the port on the CPU and the programmer’s latches connect with the slots in the base power supply. Apply power to the base. LED’s on the programmer will display indicating a good connection. Handheld Programmer

You can clear the memory by using the PLC/Clear PLC sub-menu from within DirectSOFT, or you can use the following Handheld Programmer keystrokes.

CLR ADDRESS/DATA ON/OFF

RUN BATT

CLR

SHF

3

4

8

4 OUT 5 TMR 6 CNT 7 SR

DEL

0 MCS 1 MCR 2 SET 3 RST

NXT

4 ADR 5 SHF 6 DATA 7 REG

(Clears the CPU memory)

NOTE: This Handheld Programmer operation only clears the program memory. Any values stored in data registers are not cleared. You do have an additional menu option within DirectSOFT that allows you to clear the data registers. CPU Checklist

DL305 User Manual, Rev. D

DL330/DL330P/DL340 Specifications

Before you proceed with the I/O configuration or programming information, make sure you have: S set the CPU dipswitches S selected and installed the EEPROM/UVPROM (if chosen.) S a good understanding of the various system functions needed to setup the CPU.

DL330/DL330P/DL340 CPU Specifications

PWR CPU

0 AND 1 OR 2 STR 3 NOT

DL330/DL330P/DL340 CPU Specifications

Key switch in PRG mode

DL330/DL330P/DL340 Specifications

Clearing the CPU Memory

3--21

Page 69