Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 11 of 42

DL305 User Manual: Chapter 4: Bases, Expansion Bases, and I/O Configuration, pages 70 to 77

Pages 70 to 77 of 359, from DL305 User Manual

The original document is the PDF (4.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect D3-08TD2, AutomationDirect D3-16TD2, Konnect-It D3-08TD2, Koyo D3-08TD2, Konnect-It D3-16TD2 and Koyo D3-16TD2

Page 70

Bases, Expansion Bases, and I/O Configuration

14

In This Chapter. . . ., Understanding I/O Numbering and Module Placement Rules, Base Specifications and Wiring, Using Bases for Local or Expansion I/O Systems, Setting the Base Switches, Example I/O Configurations, I/O Configurations with a 5 Slot Local CPU Base, I/O Configurations with an 8 Slot Local CPU Base, I/O Configurations with a 10 Slot Local CPU Base, Calculating the Power Budget

Page 71

Bases, Expansion Bases, and I/O Configuration

Understanding I/O Numbering and Module Placement Rules Before you install any I/O modules or begin installing or using the bases, it is very helpful to understand how the DL305 I/O numbering and module placement restrictions can sometimes dictate how your system is put together. DL305 I/O Configuration History

The DL305 product family has had several enhancements over the years. Each time the product family has grown or has been enhanced, compatibility with the earlier products has been of the utmost concern. Some of these enhancements such as increasing the I/O count and supporting 16 point modules have impacted the numbering system. To help you understand our numbering scheme we have provided the following account of how the numbering system has been affected.

Bases and Expansion Bases

Bases and Expansion Bases

4--2

When the 16 point I/O modules were introduced to the standard line of 8 point modules, the I/O numbering system was not modified to count in 16 consecutive units. This was done to maintain compatibility with the 8 point systems. This means each 16 point module uses two groups of eight consecutive numbers such as 000 through 007 and 100 through 107. When the I/O count was increased from the original 112 maximum to 176 maximum (for the DL330/DL330P CPU) and 184 maximum (for the DL340 CPU), most of the new I/O addresses were not set up to be consecutive with the the original 112 I/O. This means you will see a large jump in the I/O number ranges.

S

S

Bases, Expansion Bases and I/O Configuration

Octal Numbering System

The DL305 I/O points are numbered in octal (base 8.) The octal numbering system does not include the numbers 8 and 9. The following table lists the first few octal numbers with the equivalent decimal numbers so you can see the numbering pattern.

Octal Numbers

0

1

2

3

4

5

6

7

10

11

12

13

14

15

16

17

20

21

22

23

24

...

Decimal Numbers

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

...

Fixed I/O Numbering

The DL305 base I/O numbering is fixed, you cannot choose the I/O address of specific points since the system allocates the addresses for each slot. The I/O number ranges are 0--177 and 700--767. The I/O numbering for each slot in the base depends on two things: 1. The base configuration, which is determined by the size of the base and whether you are using an expansion base. 2. The number of I/O points per module and the location of the I/O modules in the base.

DL305 User Manual, Rev. D

Page 72

4--3

Bases, Expansion Bases, and I/O Configuration

I/O numbering begins with address “000” which is the slot adjacent to the CPU. Each module uses increments of eight I/O points. For 8 point modules the I/O addresses are made up of eight contiguous points for each module. For 16 point modules the I/O addresses are made up of two groups of eight contiguous points, the first group follows the same scheme as the 8 point module and the second group adds 100 to the values of the first group. The examples below show the I/O numbering for a 5 slot local CPU base with 8 point I/O and a 5 slot local CPU base with 16 point I/O. 5 Slot Base Using 8 Point I/O Modules 5 Slot Base Using 16 Point I/O Modules 020 to 027

Slot Number: 3 2

010 to 017

000 to 007

C P U

DL305

1 0

030 to 037

020 to 027

010 to 017

000 to 007

130 to 137

120 to 127

110 to 117

100 to 107

Slot Number: 3 2

C P U

Bases and Expansion Bases

030 to 037

Bases and Expansion Bases

I/O Numbering Guidelines

DL305

1 0

Number of I/O Points Required for Each Module DC Input Modules

Relay Output Modules

DC Output Modules

D3--08ND2 D3--16ND2--1 D3--16ND2--2 D3--16ND2F

8 16 16 16

D3--08TD1 D3--08TD2 D3--16TD1--1 D3--16TD1--2

8 8 16 16

D3--08TR F3--08TRS--1 F3--08TRS--2 D3--16TR

F3--16ND3

16

D3--16TD2

16

Analog Modules

AC Input Modules

AC Output Modules 8

D3--08NA--2 D3--16NA

8 16

F3--04DA--1 F3--04DA--2 F3--04DAS

16 16 16

ASCII BASIC Modules F3--AB128--R

16

D3--04AD

16

F3--AB128--T

16 16 16

D3--04TAS F3--08TAS

8* 8

F3--04ADS F3--08AD

16 16

F3--AB128 F3--AB64

D3--08TA--1

8

F3--08TEMP

16

Specialty Modules

AC/DC Input Modules

D3--08TA--2

8

F3--08THM--n

16

D3--08NE3

8

D3--16NE3

16

F3--16TA--1 D3--16TA--2

16 16

F3--16AD D3--02DA

16 16

D3--08SIM D3--HSC

* This is a 4-point module, but each slot is assigned a minimum of 8 I/O points.

DL305 User Manual, Rev. D

8 16

Bases, Expansion Bases and I/O Configuration

D3--08NA--1

8 8 8 16

Analog Modules (cont.)

Page 73

Bases and Expansion Bases

Bases and Expansion Bases

4--4

Bases, Expansion Bases, and I/O Configuration

I/O Module Placement Rules

There are some limitations that determine where you can place certain types of modules. Some modules require certain locations and may limit the number or placement of other modules. We have tried to give clearly written explanations of the rules governing module placement, but we realize a picture can sometimes be worth a thousand words. If you have difficulty with some of our explanations, please look ahead to the illustrations in this chapter. They should clear up any gray areas in the explanation and you will probably find the configuration you intend to use in your installation. In all of the configurations mentioned the number of slots from the CPU that are to be used can roll over into an expansion base if necessary. For example if a rule states a module must reside in one of the six slots adjacent to the CPU, and the system configuration is comprised of two 5 slot bases, slots 1 and 2 of the expansion base are valid locations. The following table provides the general placement rules for the DL305 components. Module CPU

Bases, Expansion Bases and I/O Configuration

16 Point I/O Modules

Analog Modules ASCII Basic Modules High Speed Counter

DL305 User Manual, Rev. D

Restriction The CPU must reside in the first slot of the local CPU base. The first slot is the closest slot to the power supply. There can be a maximum of eight 16 point modules installed in a system depending on the CPU type and I/O modules used. The 16 point modules must be in the first 8 slots adjacent to the CPU rolling over into an expansion base if necessary. If any of the eight slots adjacent to the CPU are not used for 16 point modules, they can be used for 8 point modules. Analog modules must reside in any valid 16 point I/O slot. ASCII Basic modules must reside in any valid 16 point I/O slot. High Speed Counters may be used in one of the first 4 slots in the local CPU base.

Page 74

Bases, Expansion Bases, and I/O Configuration

The DL330 CPU can address up to seven 16 point modules as long as they reside in the seven slots adjacent to the CPU, however; there is one circumstance where the number of 16 point modules can be limited. S Only six 16 point modules can be used if High Speed Counter modules are installed in the system. The 16 point modules must reside in the six slots adjacent to the CPU. NOTE: The High Speed Counter module is considered to be a 16 point module.

020 to 027

010 to 017

000 to 007

130 to 137

120 to 127

110 to 117

100 to 107

060 to 067

050 to 057

040 to 047

160 to 167

150 to 157

140 to 147

C P U

DL305

Bases and Expansion Bases

030 to 037

Bases and Expansion Bases

DL330/DL330P Rules for 16 Point Modules

4--5

DL305

Addresses 160 -- 167 are not available as I/O if High Speed Counter modules are used in the system NOTE: Addresses 160--167 are normally used as CRs, but they can also be used as I/O for 16 point modules. You cannot use the points as both CRs and I/O. Also, when you use these as I/O points, you still enter them as C160--C167 in DirectSOFT. Bases, Expansion Bases and I/O Configuration

DL305 User Manual, Rev. D

Page 75

Bases, Expansion Bases and I/O Configuration

Bases and Expansion Bases

Bases and Expansion Bases

4--6

Bases, Expansion Bases, and I/O Configuration

DL340 Rules for 16 Point Modules

The DL340 CPU can address up to eight 16 point modules as long as they reside in the eight slots adjacent to the CPU, however; there are circumstances where the number of 16 point modules can be limited. 1. Only seven 16 point modules can be used if a Thumbwheel Interface module is installed in the system. The 16 point modules must reside in the seven slots adjacent to the CPU. 2. Only seven 16 point modules can be used if High Speed Counter modules are installed in the system. The 16 point modules must reside in the six slots adjacent to the CPU, skipping one slot, and using the 8th slot from the CPU for the last of the 16 point modules. 3. Only six 16 point modules can be used if a High Speed Counter and a Thumbwheel Interface module are installed in the system. The 16 point modules must reside in in the six slots adjacent to the CPU . NOTE: Both High Speed Counter and Thumbwheel Interface modules are considered to be 16 point modules.

030 to 037

020 to 027

010 to 017

000 to 007

130 to 137

120 to 127

110 to 117

100 to 107

070 to 077

060 to 067

050 to 057

040 to 047

170 to 177

160 to 167

150 to 157

140 to 147

C P U

DL305

DL305

Addresses 170 -- 177 are not available as I/O if a Thumbwheel Interface module is used in the system Addresses 160 -- 167 are not available as I/O if High Speed Counter modules are used in the system Addresses 160 -- 167 and 170 -- 177 are not available as I/O if both High Speed Counters and a Thumbwheel interface module are used in the system. NOTE: Addresses 160 -- 177 are normally used as CRs, but they can also be used as I/O points if you are using 16 point modules. Remember, if you use these locations as I/O points you cannot use them as CRs. Also, when you use these as I/O points, you still enter them as C160--C177 in DirectSOFT.

DL305 User Manual, Rev. D

Page 76

Bases, Expansion Bases, and I/O Configuration

4--7

Three Sizes of Bases

There are three base sizes available to hold your I/O modules: 5, 8 and 10 slot. The 5 and 10 slot bases can be used as either a local CPU base or an expansion base. The 8 slot base can only be used as a local CPU base. The 5, 8, and 10 slot bases are available with a built-in 110/220 VAC power supply. The 5 slot base is also available with a built-in 24 VDC power supply. Remote I/O is not offered in the DL305 product family. All DL305 products, with the exception of the DL340 CPU, are compatible with remote I/O systems previously offered by GE FANUC® and TEXAS INSTRUMENTS®

AC Neutral

Bases and Expansion Bases

AC Line

Bases and Expansion Bases

Base Specifications and Wiring

5 Slot I/O Base Bases, Expansion Bases and I/O Configuration

8 Slot I/O Base

10 Slot I/O Base

DL305 User Manual, Rev. D

Page 77

Bases, Expansion Bases, and I/O Configuration

Bases and Maximum I/O Supported

Bases and Expansion Bases

Bases and Expansion Bases

4--8

Base Mounting Dimensions

The maximum I/O for the base combinations is shown below. The number of I/O points supported also depends on the which CPU is used in the system. Base Configuration

DL330 / DL330P CPU

DL340 CPU

5 slot local CPU base system

64 I/O max.

64 I/O max

5 slot local CPU base system with a 5 slot expansion base

120 I/O max.

128 I/O max.

5 slot local CPU base system with two 5 slot expansion bases

120 I/O max.

128 I/O max.

8 slot local CPU base system

112 I/O max.

112 I/O max.

8 slot local CPU base system with a 5 slot expansion base

152 I/O max.

152 I/O max.

10 slot local CPU base system

128 I/O max.

136 I/O max.

10 slot local CPU base system with a 5 slot expansion base

168 I/O max.

176 I/O max.

10 slot local CPU base system with a 10 slot expansion base

176 I/O max.

184 I/O max.

Use these mounting dimensions when you install the DL305 bases. Make sure you have followed the installation guidelines shown in Chapter 2 for proper spacing. 5 slot base

11.41” 290mm

.94” 24mm

10.63” 270mm

Handheld Programer on side view of Base 3.54” 90mm

Bases, Expansion Bases and I/O Configuration

4.84” 123mm

8 slot base

14.76” 375mm

3.54” 90mm

4.84” 123mm

10 slot base

4.41” 112mm 5.35” 136mm

15.55” 395mm

18.30” 465mm 17.51” 445mm

4.84” 123mm

DL305 User Manual, Rev. D

3.54” 90mm