Spec sheet · AutomationDirect
DL305 PLCs: DC Output Modules, D3-16TD2 DC Output
Spec sheet6 pagesPDF 1.6 MB
Spec sheet for the D3-16TD2 16-point sourcing DC output module for DL305 PLCs, with power budget tables and ZIPLink wiring options.
Covers · 3 models
The models it covers
Summary
What is in it
Catalog pages for the DL305 PLC family centered on the D3-16TD2 DC output module: its specifications, derating chart and wiring diagram, followed by how to calculate a DL305 power budget, the power supplied by each base and used by each DL305 device, and ZIPLink wiring solutions with a selector table of ZIPLink connector modules and cables for DL305 I/O modules.
Its parts
- Output Modules
- Power Budget
- Power Requirements
- Wiring Solutions
- ZIPLink Connector Modules
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Pages from the AutomationDirect DL305 PLC catalog: the specification sheet for the D3-16TD2 16-point DC output module, followed by the DL305 power budget and power requirement charts and the ZIPLink wiring pages. It lets the reader check the module's ratings and work out whether a DL305 base can power it.
- Device
- DL305 PLC DC output module, NPN transistor (emitter follower) p. 1
- Outputs
- 16 (current sourcing), 2 isolated commons p. 1
- Voltage
- 5–24 VDC operating; 40VDC peak p. 1
- Max. current
- 0.5 A per point, 3A per common p. 1
- Base power
- 9V (180mA max), 7.5 mA per ON point; 24V not used p. 1
- Fuses
- 2 (one 5A per common), non-replaceable p. 1
- ON voltage drop
- 1.5 V @ 0.5 A p. 1
- Leakage and min. load
- Max leakage 0.01 mA @ 40VDC; minimum load 1mA p. 1
- Inrush current
- 3A for 20ms, 1A for 100ms p. 1
- Response time
- 0.1 ms OFF to ON and ON to OFF p. 1
- Terminals and indicators
- Removable connector; logic side status indicators p. 1
- Weight
- 7.1 oz. (210g) p. 1
What this sheet walks you through
- Calculating the power budget of a DL305 base p. 2
- Looking up the power each DL305 device draws and each base supplies p. 3
- Choosing a ZIPLink wiring solution for DirectLOGIC I/O modules p. 4, 5
- Selecting ZIPLink connector modules and cables for DL305 modules p. 6
Good to know
- Exceeding the base power budget can make the system operate unpredictably. p. 2
- Current drawn from a base's 24 VDC output terminals should stay under 100 mA, and the D3-05BDC and D3-10BDC have no such output. p. 3
- If the chosen I/O needs more power than the supply gives, some modules can be moved to an expansion base. p. 2
Questions this sheet answers
Is the D3-16TD2 a sinking or sourcing output module?
It is current sourcing: 16 NPN transistor (emitter follower) outputs on 2 isolated commons. p. 1
How much current can each D3-16TD2 output switch?
0.5 A per point and 3A per common, at 5–24 VDC. p. 1
Can the fuses on the D3-16TD2 be replaced?
No. It has two 5A fuses, one per common, and they are non-replaceable. p. 1
How much base power does the D3-16TD2 use?
9V (180mA max), at 7.5 mA per ON point; it uses no 24V base power. p. 1
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 1 part
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file