DL405 User Manual: Chapter 3: CPU Specifications and Operation, pages 85 to 94

Pages 85 to 94 of 608, from DL405 User Manual

The original document is the PDF (8.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect D4-08B-1, AutomationDirect D4-08ND3S, AutomationDirect D4-16TA, PLC Direct D4-16TD2, AutomationDirect D4-32ND3-1, Konnect-It D4-08B-1, Koyo D4-08B-1, Konnect-It D4-08ND3S, and 6 more models

Page 85

CPU Specifications and Operation In This Chapter. . . ., Overview, CPU General Specifications, CPU Electrical Specifications, CPU Hardware Features, Using Battery Backup, Selecting the Program Storage Media, CPU Setup, CPU Operation, I/O Response Time, CPU Scan Time Considerations, PLC Numbering Systems, Memory Map, DL405 Aliases, X Input/Y Output Bit Map, Control Relay Bit Map, Timer and Counter Status Bit Maps, Remote I/O Bit Map, Staget Control / Status Bit Map

13

Page 86

3--2

CPU Specifications and Operation

Overview

CPU Specifications and Operation

The CPU is the heart of the control system. Almost all system operations are controlled by the CPU, so it is very important to set up and install it correctly. This chapter provides the information needed to understand: S the differences between the various models of CPUs S the steps required to setup and install the CPU General CPU Features

The DL430, DL440, and DL450 are all modular CPUs which are installed in either 4, 6, or 8 slot bases. All I/O modules in the DL405 family will work with either CPU. The DL405 CPUs offer a wide range of processing power and program instructions. All offer RLL and Stage program instructions (See Chapter 5 for instruction definitions). All DL405 CPUs have extensive internal diagnostics that can be monitored from the application program or from an operator interface. The three standard CPU types accept either 110VAC or 220 VAC for power input. The DL440 CPU is available in two additional DC versions: the DL440DC--1 uses 24 VDC, and the DL440DC--2 uses 125 VDC.

DL430 CPU Features

The DL430 has 6.5K of program memory comprised of 3.5K of ladder memory and 3K of V-memory (data registers). It has 113 instructions available for program development, and supports a maximum of 640 points of local and local expansion I/O and 512 points of remote I/O. Program storage is in the EEPROM which is built into the CPU. In addition to the EEPROM there is also RAM on the CPU which will store system parameters, V-memory and other data which is not in the application program. The DL430 provides two built-in communications ports. The first has a RS232C interface and the other has a RS232C/RS422 interface. This allows for a point-to-point connection on the first port and the option of either a multidrop network connection (such as DirectNET) or a point-to-point connection on the other port.

DL440 CPU Features

The DL440 includes all the DL430 features, plus more I/O points, more program instructions, and greater memory space with plug-in memory cartridges. It has a maximum of 22.5K of program memory comprised of 15.5K of ladder memory and 7K of V-memory (data registers). It supports a maximum of 640 points of local and local expansion I/O and 1024 points of remote I/O. Its two communications ports operate identically to the DL430’s ports. The DL440 has 170 instructions. The additional 57 instructions to the DL430 instruction set allow for more sophisticated program development through the use of subroutines, additional instructions that support double word manipulation, enhanced stack operations, diagnostic messaging, and ASCII/Hex data formatting.

DL405 User Manual, 4th Edition

Page 87

CPU Specifications and Operation DL450 CPU Features

3--3

The new DL450 offers all the DL440 features, plus more I/O points, program instructions, and two additional (4 total) communications ports. It has a maximum of 30.8K of program memory comprised of 15.5K of ladder memory and 15.3K of V-memory (data registers). It supports a maximum of 2048 points of local and local expansion I/O, and 1536 points of remote I/O. It includes an additional internal RISC--based microprocessor for greater processing power. The DL450 has 210 instructions. The additional 40 instructions to the DL440 instruction set include drum timers, a print function, floating point math, trigonometric functions, and PID loop control for 16 loops. The DL450 has a total of four communications ports. The first two ports are identical to those on the DL430 and DL440. The third port has a RS-232C interface and can be configured for either N sequence or K sequence protocol. It uses a modular connector for point-to-point communications to devices such as the DV-1000 Data Access Unit. The fourth port has a RS-422 interface using either MODBUS master/slave, N sequence, or K sequence protocol. These four ports utilize three physical connectors (the bottom connector has two ports on the DL450).

CPU Specifications and Operation

DL405 User Manual, 4th Edition

Page 88

3--4

CPU Specifications and Operation

CPU Specifications and Operation

CPU General Specifications Features

DL430

DL440

DL450

Total Program memory (words)

6.5K

14.5K / 22.5K*

22.8K / 30.8K*

Ladder memory (words), built-in

3.5K

7.5K / 15.5K*

7.5K / 15.5K*

V-memory (words)

3.0K

7.0K

15.3K

Scan Time, typical (1 K boolean)

8 -- 10 mS

2 -- 3 mS

4 -- 5 mS

Run time edit

No

Yes

Yes

RLL and RLL PLUS Programming

Yes

Yes

Yes

Handheld programmer with cassette tape interface

Yes

Yes

Yes

DirectSOFT programming for Windows™

Yes

Yes

Yes

Built-in communication ports

2 ports

2 ports

4 ports

CMOS RAM

No w/mem. cartridge w/mem. cartridge

UVPROM

No w/mem. cartridge w/mem. cartridge

EEPROM

Standard on CPU w/mem. cartridge w/mem. cartridge

FLASH RAM

No

No

Standard on CPU

CoProcessor™ modules

Yes

Yes

Yes

Networking modules

Yes

Yes

Yes

RS232C/RS422 Data Comm. Module

Yes

Yes

Yes

1152

1664

3584

Local I/O / Local expansion I/O / Remote I/O

640

640

4096

Remote I/O

512 max.

1024 max.

2048 max.

Remote I/O Channels

2

2

3

Local discrete input points maximum

320

320

1024

Local discrete output points maximum

320

320

1024

Local analog input channels maximum

320**

320**

512**

Local analog output channels maximum

320**

320**

512**

Maximum number of channels / masters (remote or slice) per local CPU base

2

2

2

Remote I/O Distance

3300 ft. (1000m)

3300 ft. (1000m)

3300 ft. (1000m)

Discrete I/O Module Point Density

8/16/32/64

8/16/32/64

8/16/32/64

Slots per Base

4/6/8

4/6/8

4/6/8

Compatible with:

Total I/O Total I/O available as:

* The first values represent CPUs using the 7.5K memory cartridge and the second value is for using 15.5K memory cartridges. ** Additional Discrete and Analog I/O can be supported (within the power budget) through the use of remote I/O.

DL405 User Manual, 4th Edition

Page 89

CPU Specifications and Operation

Feature

DL430

DL450

Number of instructions available (see Chapter 5 for 113 a description of the available instructions)

170

210

Control relays

480

1024

2048

Special relays (system defined)

288

352

512

Stages in RLL PLUS

384

1024

1024

V-memory

3072 words

7168 words

15360 words

Timers

128

256

256

Counters

128

128

256

Immediate I/O

Yes

Yes

Yes

Interrupt input

8 points

16 points

16 points

Subroutines

No

Yes

Yes

For/Next Loops

No

Yes

Yes

Drum Timers

No

No

Yes

Math

Integer

Integer

Integer and Floating Point

PID Loop Control, built-in

No

No

16 loops

Time of Day Clock/Calendar

No

Yes

Yes

Internal diagnostics

Yes

Yes

Yes

Password security

No

Yes

Yes, multi-level

System and user error log

No

Yes

Yes

Battery backup

Yes

Yes

Yes

CPU Electrical Specifications Parameter

DL430/DL440/DL450

DL440/450DC--1

DL440/450DC--2

Input Voltage, Nominal

120 VAC

24 VDC

125 VDC

Input Voltage Range

100--120 VAC and 196--240 VAC +10% --15%

20--29 VDC

100--132 VDC +10% --15%

Input Voltage Ripple

N/A less than 10% less than 10%

Inrush Current, maximum

20 A

10 A

20 A

Power Consumption, maximum

50 VA

38W

30 W

Voltage withstand (dielectric strength)

1 min. at 1500 VAC between primary, secondary, field ground and run relay

Insulation resistance

> 10MΩ at 500 VDC

Output Voltage, auxiliary power supply 20--28 VDC (24 nominal), ripple more than 1V P-P (N/A on DL440--DC--1 and DL440--2) Output Current, auxiliary power supply 24 VDC @ 400 mA maximum

DL405 User Manual, 4th Edition

CPU Specifications and Operation

DL440

3--5

Page 90

3--6

CPU Specifications and Operation

CPU Hardware Features The following diagram shows the main external features of the DL405 CPUs.

DL430/DL440 CPUs Status indicators Keyswitch (mode select)

Port 0 (programming, MMI)

CPU Specifications and Operation

Wiring Terminals

CPU Battery

Slot for DL440 Memory Cartridge (optional on DL450)

DL450 CPU

Status indicators

Wiring Terminals

Port 1 (programming, MMI)

DIP Switch Config. (battery, station address, baud rate)

Keyswitch (mode select) Port 2 (programming, MMI)

Port 0 (programming, MMI)

CPU Battery

Port 1 (programming, MMI) Slot for optional Memory Cartridge Port 3 (remote I/O, network)

DL405 User Manual, 4th Edition

Page 91

CPU Specifications and Operation

Keyswitch Functions

3--7

The keyswitch on the DL405 CPUs provides positions for enabling and disabling program changes in the CPU. Unless the keyswitch is in the TERM position, RUN and STOP mode changes will not be allowed by any interface device, (handheld programmer, DirectSOFT programing package or operator interface). Programs may be viewed or monitored but no changes may be made. If the switch is in the TERM position and no program password is in effect, all operating modes as well as program access will be allowed through the connected programming or monitoring device. Keyswitch Position (Run Program)

RUN

TERM (Terminal) STOP

(Stop Program)

CPU Action CPU is forced into the RUN mode if no errors are encountered. No changes are allowed by the attached programming/monitoring device. RUN, PROGRAM and the TEST modes are available. Mode and program changes are allowed by the programming/monitoring device. CPU is forced into the STOP mode. No changes are allowed by the programming/monitoring device.

There are two ways to change the CPU mode.

Status Indicators

The status indicator LEDs on the CPU front panels have specific functions which can help in programming and troubleshooting. Indicator

Status

Meaning

PWR

ON

Power good

OFF

Power failure

ON

CPU is in Run Mode

OFF

CPU is in Stop Mode

FLASHING

CPU is in firmware upgrade mode

ON

CPU self diagnostics error

OFF

CPU self diagnostics good

BATT Note:.Refer to page 3--12

ON

CPU battery voltage is low

OFF

CPU battery voltage is good or disabled

(DL450)

ON

CPU self diagnostics or local bus error

OFF

CPU self diagnostics and local bus good

ON

I/O self diagnostics error

OFF

I/O self diagnostics good

ON

Communications error has occurred

OFF

Communications OK

ON

Data is being transmitted by the CPU

OFF

No data is being transmitted by the CPU

ON

Data is being received by the CPU

OFF

No data is being received by the CPU

RUN

CPU

DIAG I/O COM TXD RXD

(DL430/DL440) (DL450) (DL450)

DL405 User Manual, 4th Edition

CPU Specifications and Operation

1. Use the CPU key switch to select the operating mode. 2. Place the CPU key switch in the TERM position and use a programming device to change operating modes. In this position, you can change between Run and Program modes.

Page 92

3--8

CPU Specifications and Operation

125VDC Terminal Strip

24VDC Terminal Strip

AC Terminal Strip

24V Auxiliary Power Logic Ground Chassis Ground + DC

Logic Ground Chassis Ground + DC

-- DC

-- DC

Logic Ground Chassis Ground AC Line AC Neutral 110/220 Voltage Select

Setting the CPU DIP Switches

430 440 450

Install shunt for 110 VAC range, leave off for 220 VAC range.

Locate the bank of four configuration switches located on the back of DL430 and DL440 CPUs as shown in the figure below. These switches affect battery low detection, station address override and baud rate of port 1 (25 pin D connector). Use Aux Functions on the DL450 for these selections, via a programming device. Switch 1 S ON = Battery low indicator disabled ON S OFF= Battery low indicator enabled Switch 2 S ON = Station address override is enabled (address 1) S OFF = Station address is set by AUX function with programming device 1 2

CPU Specifications and Operation

Install shunt between LG and G Recommended screw torque: 10.6 lb--in (1.2Nm)

3 4

NOTE: Setting Switch 2 on forces the station address to 1. It does not change the address set by the programming device. When Switch 2 is turned off again the address will revert back to the address stored in memory via the AUX function. Port 1 Baud Rate

Switch 3

Switch 4

300

Off

Off

1200

Off

On

9600

On

Off

19200

On

On

NOTE: Parity, Mode and Station address for port 1 is selected by AUX functions using a programming device.

DL405 User Manual, 4th Edition

Page 93

CPU Specifications and Operation

Communication Ports Port 0 Specifications

430 440 450

DL405 CPUs provides up to four communication ports. The DL430/DL440 CPUs have two ports, while the DL450 CPU has a total of four ports. The first port (all CPUs) is located on the 15 pin D-shell connector. It is for general programming such as DirectSOFT, or operator interface connections. The D4--HPP handheld programmer can only be used on this port on the CPU. The operating parameters for Port 0 are permanently set to the values shown. S 15 Pin female D type connector S Protocol: K sequence S RS232C, non-isolated, distance within 15 m (approx. 50 feet) S 9600 baud, 8 data bits, 1 start, 1 stop bit, odd parity S Asynchronous, Half duplex, DTE Port 0 9

8

15

430 440 450

Port 0 Pin Descriptions (All CPUs) 1 YOP Sense connection between HPP and CPU 2 TXD Transmit Data (RS232C) 3 RXD Receive Data (RS232C) 4 ONLINE Request Communication (TTL) 5 ABNO CPU Error (TTL) 6 PRDY CPU ready to communicate (TTL) 7 CTS Clear to Send (RS232C) 8 YOM Sense connection between HPP and CPU 9 -Not Used 10 LCBL Sense cable connection (TTL) 11 5V2 5 VDC for HPP logic 12 5V2 5 VDC for LCD backlight 13 0V Logic ground 14 0V Logic ground 15 0V Logic ground

Port 1 (all CPUs) is located on the 25-pin connector, and is called the “secondary comm port” for the DL430/DL440 CPUs. The secondary comm port address is stored in the memory cartridge along with the I/O configuration. It is for general programming such as DirectSOFT, operator interfaces, and networking, but it cannot connect to the handheld programmer. Port 1 provides additional features such as programmable baud rate, parity, ASCII/Hex mode and network address. Its RS422 signals support multidrop networking and programming applications. The baud rate and station address override is selected by dip switches on the rear of the DL430/DL440 CPUs. The DL450 uses Aux functions to set the same parameters (it has no DIP switches). RS232C or RS422 is selected by cabling to the proper signal pin sets on the connector. Parity, ASCII/Hex mode and station address are selected by AUX (auxiliary) functions with a programming device. S 25 Pin female D type connector S Protocols: K-sequence, DirectNet. The DL450 additionally supports Non-Sequence and MODBUS protocols. (Note: The DL430 cannot support K--sequence on ports 0 and 1 simultaneously. Use DirectNet on port 1 if port 0 is used for communications). S RS232C / RS422, Selectable address 1--90 (use Aux function) S 300/ 600/ 1200/2400/4800/9600/19200/(38400 DL450 only) baud S Hex / ASCII modes (use Aux function to configure) S 8 data bits, 1 start, 1 stop bit, Odd, Even or No parity S Asynchronous, Half duplex (use Aux function to configure), DTE

DL405 User Manual, 4th Edition

CPU Specifications and Operation

1

15-pin Female D Connector

Port 1 Specifications

3--9

Page 94

3--10

CPU Specifications and Operation

Port 1 Pin Descriptions (All CPUs)

Port 1 1

14

13

25

CPU Specifications and Operation

25-pin Female D Connector

Port 2 Specifications

430 440 450

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25

-TXD RXD RTS CTS -SG -RXD+ RXD-CTS+ --TXD+ -TXD--RTS-RTS+ ---CTS----

Not used Transmit Data (RS232C) Receive Data (RS232C) Request to Send (RS232C) Clear to Send (RS2332C) Not used Signal ground (RS232C/RS422) (port 3 on DL450) Receive Data + (RS422) Receive Data -- (RS422) Clear to Send + (RS422) (port 3 on DL450) (port 3 on DL450) Transmit Data + (RS422) Not used Transmit Data -- (RS422) Not used Request to Send -- (RS422) Request to Send + (RS422) Not used Not used Not used Clear to Send -- (RS422) (port 3 on DL450) (port 3 on DL450)

The operating parameters for Port 2 on the DL450 CPU are configurable using Aux functions on a programming device. S 6 Pin female modular (RJ12 phone jack) type connector S Protocols: DirectNet (slave only), K sequence, Non-procedure S RS232C, 300 / 600 / 1200 / 2400 / 4800 / 9600 / 19200 / 38400 baud S 8 data bits, 1 start, 1 stop bit; odd, even, or no parity S Nodes -- from 1 to 90

Port 2 Port 2 Pin Descriptions (DL450) 1 6

1 2 3 4 5 6

0V 5V RXD TXD 5V 0V

Power (--) connection (GND) Power (+) connection Receive Data (RS232C) Transmit Data (RS232C Power (+) connection Power (--) connection (GND)

6-pin Female Modular Connector

NOTE: The 5V pins are rated at 200mA maximum, primarily for use with some operator interfaces.