DL405 User Manual: Chapter 4: System Design and Configuration, pages 141 to 148

Pages 141 to 148 of 608, from DL405 User Manual

The original document is the PDF (8.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect D4-08B-1, AutomationDirect D4-08ND3S, AutomationDirect D4-16TA, PLC Direct D4-16TD2, AutomationDirect D4-32ND3-1, Konnect-It D4-08B-1, Koyo D4-08B-1, Konnect-It D4-08ND3S, and 6 more models

Page 141

System Design and Configuration

14

In This Chapter. . . ., DL405 System Design Strategies, Module Placement and Configuration, Calculating the Power Budget, Local I/O Expansion, Remote I/O Expansion, Network Connections to MODBUSR and DirectNET, Network Slave Operation, Network Master Operation

Page 142

4--2

System Design and Configuration

DL405 System Design Strategies I/O System Configurations

The DL405 PLCs offer the following ways to add networking to the system: S Local I/O -- consists of I/O modules located in the same base as the CPU. S Expansion I/O -- consists of I/O modules in expansion bases located close to the the local base. Expansion cables connect them to the local CPU base’s serial bus in daisy-chain fashion. S Remote I/O -- consists of I/O modules located in bases which are serially connected to the local CPU base through a Remote Master module, or may connect directly to port 3 on a DL450 CPU. A DL405 system can be developed using many different arrangements of these configurations. All I/O configurations use the standard complement of DL405 I/O modules and bases. Below is a brief description of each of these configurations. Examples of each configuration are discussed in detail later in this chapter.

Local I/O 3280 ft. (1000m) Total distance 7 Bases per channel

R M

CPU (RM)

Remote I/O channel (DL450) RS

1 meter max. length, each cable

System Design and Configuration

EXP

EXP

EXP

DL405 User Manual, 4th Edition

Expansion I/O -- 3 Expansion racks maximum -- DL430/440 up to 320 input and 320 outputs (includes I/O in the local CPU base) -- DL450 up to 1024 input and 1024 outputs (includes I/O in the local CPU base)

Remote I/O DL440/430 supports a maximum of 2 channels. These channels can be any combination of remote I/O. DL450 supports a maximum of 3 channels. One remote channel connects directly to the DL450 CPU. The other channel uses Remote Masters in any combination.

Page 143

System Design and Configuration Networking Configurations

4--3

The DL405 PLCs offer the following four ways to add I/O modules to the system: S Data Communications Module -- connects a DL405 system to devices using the DirectNET protocol, or connects as a slave to a MODBUS network. S DL450 Communications Ports -- the DL450 CPU has two extra (total of four) built-in comm ports. It allow two network connections directly from the CPU. See Chapter 3, CPU Specifications and Operation, for individual port specifications, and the sections at the end of this chapter for network connections. S MODBUS Master Module -- You can use MODBUS master modules in any slot of a DL405 system for connecting it as a master to a MODBUS network, using the RTU protocol. S MODBUS Slave Module -- You can use MODBUS slave modules in any slot of a DL405 system for connecting it as a slave to a MODBUS network, using the RTU protocol. S TIWAYR Network Interface Module -- Interface to Texas Instruments and Siemens TIWAY networks by using this module as a slave. S Shared Data Network Module -- The Shared Data Network Module lets you make peer--to--peer connections between DL405 PLC systems.

PEER-TO-PEER and MASTER/SLAVE COMMUNICATIONS

305

System Migration or Expansion

DirectNET/MODBUSr Communication (max. 3300ft/1000m)

DirectNET/MODBUSr Communication (max. 3300ft/1000m) DirectNET Communication (max. 3300ft/1000m)

405

DCM MB DCM MSTR

DL405 User Manual, 4th Edition

System Design and Configuration

405

Page 144

4--4

System Design and Configuration

Module Placement and Configuration Valid Module/Unit Locations

The most commonly used I/O modules for the DL405 system (AC, DC, AC/DC, Relay and Analog) can be used in any base in your system. The table below lists by category the valid locations for all modules/units in a DL405 system. Remember that the power budget can limit the number of modules in a base (discussed later). Module/Unit CPUs

Local CPU Base

Local Exp. Base

Remote Base

CPU Slot Only

Expansion Units

CPU Slot Only

8/16/32pt DC Input Modules 64pt DC Input Modules n n

Note 1 n n n

Note 1, 2

AC Input Modules n n n

AC/DC Input Modules n n n

8/16/32pt DC Output Modules n n n

64pt DC Output Modules n

Note 1 n

Note 1, 2

AC Output Modules n n n

Relay Output Modules n n n

Analog Modules n n n

Remote I/O Remote Master n

Remote Slave Unit

CPU Slot Only

Communications and Networking Modules n

CoProcessor Modules n n

Note 2

Specialty Modules

System Design and Configuration

Interrupt

DL430 -- Slot 0 Only DL440 -- Slots 0 & 1 DL450 -- Slots 0 & 1

High Speed Counter n

PID Module n

SDS n

4 Loop Temp. Controller n

Input Simulator n n n

Filler n n n n

Note 1: When using 64 pt modules, you cannot use any specialty modules in slots 5, 6, and 7 in the same base. Note 2: Specialty modules are allowed in expansion bases only if you are using the DL450 CPU and all bases in the system are the D4--xxB--1 type bases.

DL405 User Manual, 4th Edition

Page 145

System Design and Configuration I/O Configuration Methods

Automatic Configuration

4--5

There are two methods of I/O configuration for the DL405 CPUs: S Auto configuration -- the CPU automatically configures the I/O. It assigns the lowest I/O numbers to the module in slot 0 (the slot next to the CPU), the next set of I/O numbers to the next module in the base, etc. The numbers are assigned only to modules actually in the base, not to empty slots in the base. This is the default mode of the CPU. S Manual configuration -- (DL440/DL450 only) allows you assign I/O numbers. Numbers can be assigned to empty slots or in any order as long as the numbers are assigned in groups of 16 or 32. The DL405 CPUs automatically detect any installed I/O modules (including specialty modules)at powerup, and establish the correct I/O configuration and addresses. For most applications, you will never have to change the configuration. I/O addresses use octal numbering, starting at X0 and Y0 in the slot next to the CPU. The addresses are assigned in groups of 8, 16, 32, or 64 depending on the number of points for the I/O module. The discrete input and output modules can be mixed in any order, but there may be restrictions placed on some specialty modules. The following diagram shows the I/O numbering convention for an example system.

Slot 0 8pt. Input X0--X7

Slot 1 32pt. Output Y0--Y37

Slot 2 16pt. Input X10--X27

Slot 3 8pt. Input X30--X37

Manual Configuration

430 440 450

It may never become necessary, but DL440 and DL450 CPUs allow manual I/O address assignment for any I/O slot(s) in local or expansion bases. You can manually modify an auto configuration to match arbitrary I/O numbering. For example, two adjacent input modules can have starting addresses at X10 and X200. In automatic configuration, the addresses are assigned on 8-point boundaries. Manual configuration, however, assumes that all modules are at least 16 points, so you can only assign addresses that are a multiple of 20 (octal). For example, X30 and Y50 are not valid addresses. You can still use 8 point modules, but 16 addresses will be assigned and the upper eight addresses will be unused. WARNING: If you manually configure an I/O slot, the I/O addressing for the other modules may change. This is because the DL405 CPUs do not allow you to assign duplicate I/O addresses. You must always correct any I/O configuration errors before you place the CPU in RUN mode. Uncorrected errors can cause unpredictable machine operation that can result in a risk of personal injury or damage to equipment.

DL405 User Manual, 4th Edition

System Design and Configuration

Both the Handheld Programmer and DirectSOFT provide AUX functions that allow you to automatically configure the I/O. For example, with the Handheld Programmer AUX 46 executes an automatic configuration, which allows the CPU to examine the installed modules and determine the I/O configuration and addressing. With DirectSOFT, the PLC Configure I/O menu option would be used.

Page 146

4--6

System Design and Configuration

Removing a Manual Configuration

After a manual configuration, the system will automatically retain the new I/O addresses through a power cycle. You can remove (overwrite) any manual configuration changes by simply performing an automatic configuration. The following diagram shows how I/O addresses change after manually configuring a slot.

Automatic

Manual

System Design and Configuration

Power--On I/O Configuration Check

Slot 0 8pt. Input X0--X7

Slot 1 32pt. Output Y0--Y37

Slot 2 16pt. Input X10--X27

Slot 3 8pt. Input X30--X37

Slot 0 8pt. Input X0--X7

Slot 1 32pt. Output Y0--Y37

Slot 2 16pt. Input X100--X117

Slot 3 8pt. Input X20--X27

The DL405 CPUs can also be set to automatically check the I/O configuration on power-up. By selecting this feature you can detect any changes that may have occurred while the power was disconnected. For example, if someone places an output module in a slot that previously held an input module, the configuration check will detect the change and print a message on the Handheld Programmer or DirectSOFT screen (use AUX 44 on the HPP to enable the configuration check). If the system detects a change in the I/O configuration at power-up, an error code E252 NEW I/O CONFIGURATION will be generated. You can use AUX 42 to determine the exact base and slot location where the change occurred. WARNING: You should always correct any I/O configuration errors before you place the CPU into RUN mode. Uncorrected errors can cause unpredictable machine operation that can result in a risk of personal injury or damage to equipment. When a configuration error is generated, you may actually want to use the new I/O configuration. For example, you may have intentionally changed an I/O module to use with a program change. You can use AUX 45 to select the new configuration, or, keep the existing configuration stored in memory. WARNING: Verify the I/O configuration being selected will work properly with the CPU program. Always correct any I/O configuration errors before placing the CPU in RUN mode. Uncorrected errors can cause unpredictable machine operation that can result in a risk of personal injury or damage to equipment.

DL405 User Manual, 4th Edition

Page 147

System Design and Configuration

4--7

Calculating the Power Budget Managing your Power Resource

As you have seen, the I/O configuration depends on your choice of I/O modules, bases, and I/O location. When determining the types and quantity of I/O modules you will be using in the DL405 system it is important to remember there is a limited amount of power available from the power supply to the system. We have provided a chart to help you easily see the amount of power you will have with your CPU, Expansion Unit or Remote Slave selection. The following chart will help you calculate the amount of power you need with your I/O selections. At the end of this section you will also find an example of power budgeting and a worksheet for your own calculations. If the I/O you chose exceeds the maximum power available from the power supply you can resolve the problem by shifting some of the modules to an expansion base which contains another power supply. WARNING: It is extremely important to calculate the power budget correctly. If you exceed the power budget, the system may operate in an unpredictable manner which may result in a risk of personal injury or equipment damage.

CPU Power Specifications

The following chart shows the amount of current available for the two voltages supplied on the DL405 CPU, Expansion unit or Remote Slave unit. Use these currents when calculating the power budget for you system. The Auxiliary 24V Power Source mentioned in the table is a connection at the base terminal strip allowing you to connect to devices or DL405 modules that require 24VDC. Auxiliary 24V Power Source Current Supplied in mA.

Remote and Expansion Units

5V Current Supplied in mA.

Auxiliary 24V Power Source Current Supplied in mA.

D4--430

3700

400

D4--EX

4000

400

D4--440

3700

400

D4--EXDC

4000

None

D4--440DC--1

3700

None

D4--EXDC--2

3700

None

D4--440DC--2

3700

None

D4--RS

3700

400

D4--450

3100

400

D4--RSDC

3700

None

D4--450DC--1

3100

None

H4--EBC

3470

400

D4--450DC--2

3100

None

H4--EBC--F

3300

400

Module Power Requirements

The chart on the next page shows the amount of maximum current required for each of the DL405 modules. Use these currents when calculating the power budget for your system. If external 24VDC is required, the external 24V from the CPU power supply may be used as long as the power budget is not exceeded.

DL405 User Manual, 4th Edition

System Design and Configuration

CPUs

5V Current Supplied in mA.

Page 148

4--8

System Design and Configuration

Device

5V Current Required (mA)

External 24V Current Req. (mA)

I/O Bases 80

None

D4--06B, D4--06BNX, D4--06B--1

80

None

80

None

DC Input Modules

F4--04AD

85

100

F4--04ADS

270

120

F4--08AD

75

90

F4--04DA

120

180

F4--04DA--1

70

75 + 20 per channel

F4--04DA--2

90

75 + 20 per channel

D4--08ND3S

100

None

F4--04DAS--1

60

50 per channel

D4--16ND2

150

None

F4--04DAS--2

60

60 per channel

D4--16ND2F

150

None

F4--08DA--1

90

100 + 20 per channel

D4--32ND3--1

150

None

F4--16DA--1

90

100 + 20 per channel

D4--32ND3--2

150

None

F4--16DA--2

80

25 max.

D4--64ND2

300 (max)

None

F4--16AD--1

100

100

F4--16AD--2

75

100

D4--08NA

100

None

F4--08THM--n

120

50 + 20 per channel

D4--16NA

150

None

F4--08RTD

80

None

D4--16NA--1

150

None

Remote I/O D4--ERM

320

None

D4--16NE3

150

None

D4--ERM--F

450

None

F4--08NES

90

None

D4--RM

300

None

D4--08TD1

150

35

D4--DCM

500

None

F4--08TD1S

295

None

H4--ECOM

530

None

D4--16TD1

200

125

H4--ECOM--F

670

None

D4--16TD2

400

None

H4--ECOM100

300

None

D4--32TD1

250

140

F4--MAS--MB

235

None

D4--32TD1--1

250

140 (5--15VDC)

CoProcessors™

D4--32TD2

350

120 / (4A max including loads)

F4--CP128

305

None

D4--64TD1

800 (max)

None

F4--CP512

235

None

F4--CP128--T

350

None

D4--16SIM

150

None

D4--HSC

300

None

F4--16PID

160

None

F4--8MPI

225

170

F4--4LTC

280

75

H4--CTRIO

400

None

AC Input Modules

AC/DC Input Modules

DC Output Modules

System Design and Configuration

External 24V Current Req. (mA)

Analog Modules

D4--04B, D4--04BNX, D4--04B--1

D4--08B, D4--08BNX, D4--08B--1

5V Current Required (mA)

Device

Communications and Networking

AC Output Modules D4--08TA

250

None

D4--16TA

450

None

Relay Output Modules D4--08TR

550

None

F4--08TRS--1

575

None

F4--08TRS--2

575

None

D4--16TR

1000

None

D4--HPP

320

None

DV--1000

150

None

Programming

DL405 User Manual, 4th Edition

Specialty Modules