DL405 User Manual: Chapter 4: System Design and Configuration, pages 141 to 148
Pages 141 to 148 of 608, from DL405 User Manual
The original document is the PDF (8.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect D4-08B-1, AutomationDirect D4-08ND3S, AutomationDirect D4-16TA, PLC Direct D4-16TD2, AutomationDirect D4-32ND3-1, Konnect-It D4-08B-1, Koyo D4-08B-1, Konnect-It D4-08ND3S, and 6 more models
Page 141
System Design and Configuration
14
In This Chapter. . . ., DL405 System Design Strategies, Module Placement and Configuration, Calculating the Power Budget, Local I/O Expansion, Remote I/O Expansion, Network Connections to MODBUSR and DirectNET, Network Slave Operation, Network Master Operation
Page 142
4--2
System Design and Configuration
DL405 System Design Strategies I/O System Configurations
The DL405 PLCs offer the following ways to add networking to the system: S Local I/O -- consists of I/O modules located in the same base as the CPU. S Expansion I/O -- consists of I/O modules in expansion bases located close to the the local base. Expansion cables connect them to the local CPU base’s serial bus in daisy-chain fashion. S Remote I/O -- consists of I/O modules located in bases which are serially connected to the local CPU base through a Remote Master module, or may connect directly to port 3 on a DL450 CPU. A DL405 system can be developed using many different arrangements of these configurations. All I/O configurations use the standard complement of DL405 I/O modules and bases. Below is a brief description of each of these configurations. Examples of each configuration are discussed in detail later in this chapter.
Local I/O 3280 ft. (1000m) Total distance 7 Bases per channel
R M
CPU (RM)
Remote I/O channel (DL450) RS
1 meter max. length, each cable
System Design and Configuration
EXP
EXP
EXP
DL405 User Manual, 4th Edition
Expansion I/O -- 3 Expansion racks maximum -- DL430/440 up to 320 input and 320 outputs (includes I/O in the local CPU base) -- DL450 up to 1024 input and 1024 outputs (includes I/O in the local CPU base)
Remote I/O DL440/430 supports a maximum of 2 channels. These channels can be any combination of remote I/O. DL450 supports a maximum of 3 channels. One remote channel connects directly to the DL450 CPU. The other channel uses Remote Masters in any combination.
Page 143
System Design and Configuration Networking Configurations
4--3
The DL405 PLCs offer the following four ways to add I/O modules to the system: S Data Communications Module -- connects a DL405 system to devices using the DirectNET protocol, or connects as a slave to a MODBUS network. S DL450 Communications Ports -- the DL450 CPU has two extra (total of four) built-in comm ports. It allow two network connections directly from the CPU. See Chapter 3, CPU Specifications and Operation, for individual port specifications, and the sections at the end of this chapter for network connections. S MODBUS Master Module -- You can use MODBUS master modules in any slot of a DL405 system for connecting it as a master to a MODBUS network, using the RTU protocol. S MODBUS Slave Module -- You can use MODBUS slave modules in any slot of a DL405 system for connecting it as a slave to a MODBUS network, using the RTU protocol. S TIWAYR Network Interface Module -- Interface to Texas Instruments and Siemens TIWAY networks by using this module as a slave. S Shared Data Network Module -- The Shared Data Network Module lets you make peer--to--peer connections between DL405 PLC systems.
PEER-TO-PEER and MASTER/SLAVE COMMUNICATIONS
305
System Migration or Expansion
DirectNET/MODBUSr Communication (max. 3300ft/1000m)
DirectNET/MODBUSr Communication (max. 3300ft/1000m) DirectNET Communication (max. 3300ft/1000m)
405
DCM MB DCM MSTR
DL405 User Manual, 4th Edition
System Design and Configuration
405
Page 144
4--4
System Design and Configuration
Module Placement and Configuration Valid Module/Unit Locations
The most commonly used I/O modules for the DL405 system (AC, DC, AC/DC, Relay and Analog) can be used in any base in your system. The table below lists by category the valid locations for all modules/units in a DL405 system. Remember that the power budget can limit the number of modules in a base (discussed later). Module/Unit CPUs
Local CPU Base
Local Exp. Base
Remote Base
CPU Slot Only
Expansion Units
CPU Slot Only
8/16/32pt DC Input Modules 64pt DC Input Modules n n
Note 1 n n n
Note 1, 2
AC Input Modules n n n
AC/DC Input Modules n n n
8/16/32pt DC Output Modules n n n
64pt DC Output Modules n
Note 1 n
Note 1, 2
AC Output Modules n n n
Relay Output Modules n n n
Analog Modules n n n
Remote I/O Remote Master n
Remote Slave Unit
CPU Slot Only
Communications and Networking Modules n
CoProcessor Modules n n
Note 2
Specialty Modules
System Design and Configuration
Interrupt
DL430 -- Slot 0 Only DL440 -- Slots 0 & 1 DL450 -- Slots 0 & 1
High Speed Counter n
PID Module n
SDS n
4 Loop Temp. Controller n
Input Simulator n n n
Filler n n n n
Note 1: When using 64 pt modules, you cannot use any specialty modules in slots 5, 6, and 7 in the same base. Note 2: Specialty modules are allowed in expansion bases only if you are using the DL450 CPU and all bases in the system are the D4--xxB--1 type bases.
DL405 User Manual, 4th Edition
Page 145
System Design and Configuration I/O Configuration Methods
Automatic Configuration
4--5
There are two methods of I/O configuration for the DL405 CPUs: S Auto configuration -- the CPU automatically configures the I/O. It assigns the lowest I/O numbers to the module in slot 0 (the slot next to the CPU), the next set of I/O numbers to the next module in the base, etc. The numbers are assigned only to modules actually in the base, not to empty slots in the base. This is the default mode of the CPU. S Manual configuration -- (DL440/DL450 only) allows you assign I/O numbers. Numbers can be assigned to empty slots or in any order as long as the numbers are assigned in groups of 16 or 32. The DL405 CPUs automatically detect any installed I/O modules (including specialty modules)at powerup, and establish the correct I/O configuration and addresses. For most applications, you will never have to change the configuration. I/O addresses use octal numbering, starting at X0 and Y0 in the slot next to the CPU. The addresses are assigned in groups of 8, 16, 32, or 64 depending on the number of points for the I/O module. The discrete input and output modules can be mixed in any order, but there may be restrictions placed on some specialty modules. The following diagram shows the I/O numbering convention for an example system.
Slot 0 8pt. Input X0--X7
Slot 1 32pt. Output Y0--Y37
Slot 2 16pt. Input X10--X27
Slot 3 8pt. Input X30--X37
Manual Configuration
430 440 450
It may never become necessary, but DL440 and DL450 CPUs allow manual I/O address assignment for any I/O slot(s) in local or expansion bases. You can manually modify an auto configuration to match arbitrary I/O numbering. For example, two adjacent input modules can have starting addresses at X10 and X200. In automatic configuration, the addresses are assigned on 8-point boundaries. Manual configuration, however, assumes that all modules are at least 16 points, so you can only assign addresses that are a multiple of 20 (octal). For example, X30 and Y50 are not valid addresses. You can still use 8 point modules, but 16 addresses will be assigned and the upper eight addresses will be unused. WARNING: If you manually configure an I/O slot, the I/O addressing for the other modules may change. This is because the DL405 CPUs do not allow you to assign duplicate I/O addresses. You must always correct any I/O configuration errors before you place the CPU in RUN mode. Uncorrected errors can cause unpredictable machine operation that can result in a risk of personal injury or damage to equipment.
DL405 User Manual, 4th Edition
System Design and Configuration
Both the Handheld Programmer and DirectSOFT provide AUX functions that allow you to automatically configure the I/O. For example, with the Handheld Programmer AUX 46 executes an automatic configuration, which allows the CPU to examine the installed modules and determine the I/O configuration and addressing. With DirectSOFT, the PLC Configure I/O menu option would be used.
Page 146
4--6
System Design and Configuration
Removing a Manual Configuration
After a manual configuration, the system will automatically retain the new I/O addresses through a power cycle. You can remove (overwrite) any manual configuration changes by simply performing an automatic configuration. The following diagram shows how I/O addresses change after manually configuring a slot.
Automatic
Manual
System Design and Configuration
Power--On I/O Configuration Check
Slot 0 8pt. Input X0--X7
Slot 1 32pt. Output Y0--Y37
Slot 2 16pt. Input X10--X27
Slot 3 8pt. Input X30--X37
Slot 0 8pt. Input X0--X7
Slot 1 32pt. Output Y0--Y37
Slot 2 16pt. Input X100--X117
Slot 3 8pt. Input X20--X27
The DL405 CPUs can also be set to automatically check the I/O configuration on power-up. By selecting this feature you can detect any changes that may have occurred while the power was disconnected. For example, if someone places an output module in a slot that previously held an input module, the configuration check will detect the change and print a message on the Handheld Programmer or DirectSOFT screen (use AUX 44 on the HPP to enable the configuration check). If the system detects a change in the I/O configuration at power-up, an error code E252 NEW I/O CONFIGURATION will be generated. You can use AUX 42 to determine the exact base and slot location where the change occurred. WARNING: You should always correct any I/O configuration errors before you place the CPU into RUN mode. Uncorrected errors can cause unpredictable machine operation that can result in a risk of personal injury or damage to equipment. When a configuration error is generated, you may actually want to use the new I/O configuration. For example, you may have intentionally changed an I/O module to use with a program change. You can use AUX 45 to select the new configuration, or, keep the existing configuration stored in memory. WARNING: Verify the I/O configuration being selected will work properly with the CPU program. Always correct any I/O configuration errors before placing the CPU in RUN mode. Uncorrected errors can cause unpredictable machine operation that can result in a risk of personal injury or damage to equipment.
DL405 User Manual, 4th Edition
Page 147
System Design and Configuration
4--7
Calculating the Power Budget Managing your Power Resource
As you have seen, the I/O configuration depends on your choice of I/O modules, bases, and I/O location. When determining the types and quantity of I/O modules you will be using in the DL405 system it is important to remember there is a limited amount of power available from the power supply to the system. We have provided a chart to help you easily see the amount of power you will have with your CPU, Expansion Unit or Remote Slave selection. The following chart will help you calculate the amount of power you need with your I/O selections. At the end of this section you will also find an example of power budgeting and a worksheet for your own calculations. If the I/O you chose exceeds the maximum power available from the power supply you can resolve the problem by shifting some of the modules to an expansion base which contains another power supply. WARNING: It is extremely important to calculate the power budget correctly. If you exceed the power budget, the system may operate in an unpredictable manner which may result in a risk of personal injury or equipment damage.
CPU Power Specifications
The following chart shows the amount of current available for the two voltages supplied on the DL405 CPU, Expansion unit or Remote Slave unit. Use these currents when calculating the power budget for you system. The Auxiliary 24V Power Source mentioned in the table is a connection at the base terminal strip allowing you to connect to devices or DL405 modules that require 24VDC. Auxiliary 24V Power Source Current Supplied in mA.
Remote and Expansion Units
5V Current Supplied in mA.
Auxiliary 24V Power Source Current Supplied in mA.
D4--430
3700
400
D4--EX
4000
400
D4--440
3700
400
D4--EXDC
4000
None
D4--440DC--1
3700
None
D4--EXDC--2
3700
None
D4--440DC--2
3700
None
D4--RS
3700
400
D4--450
3100
400
D4--RSDC
3700
None
D4--450DC--1
3100
None
H4--EBC
3470
400
D4--450DC--2
3100
None
H4--EBC--F
3300
400
Module Power Requirements
The chart on the next page shows the amount of maximum current required for each of the DL405 modules. Use these currents when calculating the power budget for your system. If external 24VDC is required, the external 24V from the CPU power supply may be used as long as the power budget is not exceeded.
DL405 User Manual, 4th Edition
System Design and Configuration
CPUs
5V Current Supplied in mA.
Page 148
4--8
System Design and Configuration
Device
5V Current Required (mA)
External 24V Current Req. (mA)
I/O Bases 80
None
D4--06B, D4--06BNX, D4--06B--1
80
None
80
None
DC Input Modules
F4--04AD
85
100
F4--04ADS
270
120
F4--08AD
75
90
F4--04DA
120
180
F4--04DA--1
70
75 + 20 per channel
F4--04DA--2
90
75 + 20 per channel
D4--08ND3S
100
None
F4--04DAS--1
60
50 per channel
D4--16ND2
150
None
F4--04DAS--2
60
60 per channel
D4--16ND2F
150
None
F4--08DA--1
90
100 + 20 per channel
D4--32ND3--1
150
None
F4--16DA--1
90
100 + 20 per channel
D4--32ND3--2
150
None
F4--16DA--2
80
25 max.
D4--64ND2
300 (max)
None
F4--16AD--1
100
100
F4--16AD--2
75
100
D4--08NA
100
None
F4--08THM--n
120
50 + 20 per channel
D4--16NA
150
None
F4--08RTD
80
None
D4--16NA--1
150
None
Remote I/O D4--ERM
320
None
D4--16NE3
150
None
D4--ERM--F
450
None
F4--08NES
90
None
D4--RM
300
None
D4--08TD1
150
35
D4--DCM
500
None
F4--08TD1S
295
None
H4--ECOM
530
None
D4--16TD1
200
125
H4--ECOM--F
670
None
D4--16TD2
400
None
H4--ECOM100
300
None
D4--32TD1
250
140
F4--MAS--MB
235
None
D4--32TD1--1
250
140 (5--15VDC)
CoProcessors™
D4--32TD2
350
120 / (4A max including loads)
F4--CP128
305
None
D4--64TD1
800 (max)
None
F4--CP512
235
None
F4--CP128--T
350
None
D4--16SIM
150
None
D4--HSC
300
None
F4--16PID
160
None
F4--8MPI
225
170
F4--4LTC
280
75
H4--CTRIO
400
None
AC Input Modules
AC/DC Input Modules
DC Output Modules
System Design and Configuration
External 24V Current Req. (mA)
Analog Modules
D4--04B, D4--04BNX, D4--04B--1
D4--08B, D4--08BNX, D4--08B--1
5V Current Required (mA)
Device
Communications and Networking
AC Output Modules D4--08TA
250
None
D4--16TA
450
None
Relay Output Modules D4--08TR
550
None
F4--08TRS--1
575
None
F4--08TRS--2
575
None
D4--16TR
1000
None
D4--HPP
320
None
DV--1000
150
None
Programming
DL405 User Manual, 4th Edition
Specialty Modules