DL405 User Manual: Chapter 4: System Design and Configuration, pages 157 to 164

Pages 157 to 164 of 608, from DL405 User Manual

The original document is the PDF (8.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect D4-08B-1, AutomationDirect D4-08ND3S, AutomationDirect D4-16TA, PLC Direct D4-16TD2, AutomationDirect D4-32ND3-1, Konnect-It D4-08B-1, Koyo D4-08B-1, Konnect-It D4-08ND3S, and 6 more models

Page 157

System Design and Configuration

When configuring a Remote I/O channel for fewer than 7 slaves, we must fill the remainder of the table with zeros. This is necessary because the CPU will try to interpret any non-zero number as slave information. We continue our setup program from the previous page by adding a segment which fills the remainder of the table with zeros. The easiest way is the use the fill command as shown. The example to the right fills zeros for slave numbers 2--7, which do not exist in our example system (6 bases x 4 = 24 locations, = 18 hex).

4--17

DirectSOFT LD K18 LDA O37710 FILL K0 C740 SET

On the last rung in the example program above, we set a special relay contact C740. This particular contact indicates to the CPU that the ladder program has just finished specifying a remote I/O system. At that moment the CPU begins remote I/O communications. Be sure to include this contact after any Remote I/O setup program. Remote I/O Test Program

Now we can verify the remote I/O link and setup program operation. A simple quick check can be done with just one rung of ladder, shown to the right. It connects the first input of the remote base with the first output. After placing the PLC in RUN mode, we can go to the remote base and activate its first input. Then its first output should turn on.

DirectSOFT X60

Y40 OUT

System Design and Configuration

DL405 User Manual, 4th Edtition

Page 158

4--18

System Design and Configuration

Network Connections to MODBUSR and DirectNET Configuring the CPU’s Comm Ports

430 440 450

This section describes how to configure the CPU’s built-in networking ports. for either MODBUS or DirectNET. This will allow you to connect the DL405 PLC system directly to MODBUS networks using the RTU protocol, or to other devices on a DirectNET network. MODBUS hosts system on the network must be capable of issuing the MODBUS commands to read or write the appropriate data. For details on the MODBUS protocol, please refer to the Gould MODBUS Protocol reference Guide (P1--MBUS--300 Rev. B). In the event a more recent version is available, check with your MODBUS supplier before ordering the documentation. For more details on DirectNET, order our DirectNET manual, part number DA--DNET--M. NOTE: For information about the MODBUS protocol see the Group Schneider website at: www.schneiderautomation.com. At the main menu, select Support/Services, Modbus Technical Manuals, PI--MBUS--300 Modbus Protocol Reference Guide or search for PIMBUS300. For more information about DirectNET protocol, order our DirectNET user manual, part number DA--DNET--M, or download it free from our website: www.automationdirect.com. Select Manuals/Docs > Online User Manuals > Misc. > DA--DNET--M. The DL430 and DL440 can be DirectNET slaves on port 1. Both the DL450’s Port 1 and Port 3 can operate as master or slave for both MODBUS and DirectNET. Port 1 has RS--232 and RS--422 signal levels available on separate pins, and Port 3 (DL450) uses RS--422 signal levels. Ports 1 and Port 3 on the DL450 share the 25-pin D-shell connector, as shown to the right. Connect one or both ports as shown below. Note that you cannot simultaneously use Port 1’s RS--232 signals and its RS--422 signals.

System Design and Configuration

Port 1

Port 3

DL430 DirectNET, N/A and slave only DL440 DirectNET or DirectNET or DL450 MODBUS, MODBUS, master/slave master/slave

Port 3

Port 1

1 TXD RXD RTS CTS 0V RXD+ RXD-CTS+

TXD+

14

TXD-RTS-RTS+

0V

CTS-TXD+ TXD--

13

25

RXD+ RXD--

NOTE: The recommended cable for RS--232 or RS--422 is Belden 8102 or equivalent.

DL405 User Manual, 4th Edition

Page 159

System Design and Configuration

4--19

You will need to determine whether the network connection is a 3-wire RS--232 type, or a 5-wire RS--422 type. Normally, we use RS--232 signals for shorter distances (15 meters max), for communications between just two devices. Use RS--422 signals for longer distances (1000 meters max.), and for multi-drop networks (from 2 to 248 devices). Be sure to use termination resistors at the both ends of RS--422 network wiring, matching the impedance rating of the cable (between 100 and 500 ohms). NOTE: If your DL405 is to be used as a MODBUS Master and the distance will be more than 1000 feet, you can use the MODBUS Network Master module, F4--MAS--MB, and use the RS--485 port. See the module on our website, www.automationdirect.com for more details.

RS--422 Network Master

RXD+ RXD-TXD+ TXD-Signal GND

TXD RXD

RS--232C Point-to-point Signal GND

PORT 1 RS--232C

PORT 1 RS--422

PORT 3 RS--422

2 3 4 5 7

14 TXD+ 16 TXD-9 RXD+ 10 RXD-18 RTS-19 RTS+ 11 CTS+ 23 CTS-7 0V

12 TXD+ 13 TXD-24 RXD+ 25 RXD-7 0V

TXD RXD RTS CTS 0V

RS--422 Network Slaves

System Design and Configuration

DL405 User Manual, 4th Edtition

Page 160

4--20

System Design and Configuration

MODBUS Port Configuration

430 440 450

In DirectSOFT, choose the PLC menu, then Setup > Secondary Comm Port. S Port: From the port number list box at the top, choose Port 1 or 3. S Protocol: Click the box to the left of MODBUS to select it (use AUX 56 on the HPP, and select MBUS). The dialog below will appear.

3

S S

System Design and Configuration

S

S

S S

Timeout: amount of time the port will wait after it sends a message to get a response before logging an error. RTS on delay time: the amount of time the port waits to send a message after it’s ready to send. For port 1, it activates the RTS line before it begins transmitting (assuming CTS is already active). The port will not transmit if the CTS input is false. Station Number: For making the CPU port a MODBUSR master, choose “1”. The possible range for MODBUS slave numbers is from 1 to 247, but the DL450 network instructions will access only slaves 1 to 90. Each slave must have a unique number. At powerup, the port is automatically a slave, unless and until the DL450 executes ladder logic network instructions which use the port as a master. Thereafter, the port reverts back to slave mode until ladder logic uses the port again. Baud Rate: The available baud rates include 300, 600, 900, 2400, 4800, 9600, 19200, and 38400 baud. Choose a higher baud rate initially, reverting to lower baud rates if you experience data errors or noise problems on the network. Important: You must configure the baud rates of all devices on the network to the same value. Refer to the appropriate product manual for details. Stop Bits: Choose 1 or 2 stop bits for use in the protocol. Parity: Choose none, even, or odd parity for error checking. Then click the button indicated to send the Port configuration to the CPU, and click Close.

DL405 User Manual, 4th Edition

Page 161

System Design and Configuration DirectNET Port Configuration

430 440 450

4--21

In DirectSOFT, choose the PLC menu, then Setup > Secondary Comm Port. S Port: From the port number list box, choose Port 1 or 3 (DL450 only). S Protocol: Click the box to the left of DirectNET to select it (use AUX 56 on the HPP, then select DNET). The dialog below will appear.

S S

S

S S S

Then click the button indicated to send the Port configuration to the CPU, and click Close.

DL405 User Manual, 4th Edtition

System Design and Configuration

S

Timeout: amount of time the port will wait after it sends a message to get a response before logging an error. RTS delay time: the amount of time the port waits to send a message after it’s ready to send. For port 1, it activates the RTS line before it begins transmitting (assuming CTS is already active). The port will not transmit if the CTS input is false. Station Number: For making the CPU port a DirectNET master, choose “1”. The allowable range for DIrectNET slaves is from 1 to 90 (each slave must have a unique number). At powerup, the port is automatically a slave, unless and until the DL450 executes ladder logic instructions which attempt to use the port as a master. Thereafter, the port reverts back to slave mode until ladder logic uses the port again. Baud Rate: The available baud rates include 300, 600, 900, 2400, 4800, 9600, 19200, and 38400 baud. Choose a higher baud rate initially, reverting to lower baud rates if you experience data errors or noise problems on the network. Important: You must configure the baud rates of all devices on the network to the same value. Stop Bits: Choose 1 or 2 stop bits for use in the protocol. Parity: Choose none, even, or odd parity for error checking. Format: Choose between hex or ASCII formats.

Page 162

4--22

System Design and Configuration

Network Slave Operation This section describes how other devices on a network can communicate with a CPU port that you have configured as a DirectNETslave or MODBUS slave (DL450). A MODBUS host must use the MODBUS RTU protocol to communicate with the DL450 as a slave. The host software must send a MODBUS function code and MODBUS address to specify a PLC memory location the DL450 comprehends. The DirectNET host just uses normal I/O addresses to access any DL405 CPU and system. No CPU ladder logic is required to support either MODBUS slave or DirectNET slave operation. MODBUS Function The MODBUS function code determines whether the access is a read or a write, and Codes Supported whether to access a single data point or a group of them. The DL450 supports the MODBUS function codes described below.

430 440 450

430 440 450

MODBUS Function Code 01

Read a group of coils

Y, CR, T, CT, GY

02

Read a group of inputs

X, SP, GX

05 (slave only)

Set / Reset a single coil

Y, CR, T, CT

Set / Reset a group of coils

Y, CR, T, CT

15 03, 04

Read a value from one or more registers V

06 (slave only) 16

MODBUS Data Types Supported

Write a value into a single register

V

Write a value into a group of registers

V

The memory types in a DL405 system include X input, Y output, C control relay, V memory data registers, etc. MODBUS uses differently named data types. So, you will need to determine which MODBUS data type corresponds to any desired PLC memory location by using the cross-reference table below.

DL450 Memory Type

System Design and Configuration

DL405 Data Types Available

Function

Quantity (Decimal)

PLC Range (Octal)

Corresponding MODBUS Data Type

Rx Function Code

Inputs (X)

1024

X0 -- X1777

Input

02

Global Inputs (GX)

1536

GX0 -- GX2777

Input

02

Special Relays (SP)

512

SP0 -- SP137 SP320 -- SP717

Input

02

Outputs (Y)

1024

Y0 -- Y1777

Coil

01

Global Outputs (GY)

1536

GY0 -- GY2777

Coil

01

Control Relays (CR)

2048

C0 -- C3777

Coil

01

Timer Contacts (T)

256

T0 -- T377

Coil

01

Counter Contacts (CT)

256

CT0 -- CT377

Coil

01

Stage Status Bits (S)

1024

S0 -- S1777

Coil

01

Timer Current Values (V)

256

V0 -- V377

Input Register

03

Counter Current Value (V)

256

V1000 -- V1377

Input Register

03

V--Memory, user data (V)

3072 12288

V1400 -- V7377 V10000 -- V37777

Holding Register

03

V--Memory, system (V)

320

V700 -- V777 V7400 -- V7777

Holding Register

03

DL405 User Manual, 4th Edition

Page 163

System Design and Configuration Determining the MODBUS Address

4--23

There are typically two ways that most host software conventions allow you to specify a PLC memory location. These are: S By specifying the MODBUS data type and address S By specifying a MODBUS address only.

If Your Host Software Many host software packages allow you to specify the MODBUS data type and the Requires the Data MODBUS address that corresponds to the PLC memory location. This is the easiest Type and Address... method, but not all packages allow you to do it this way. The various MODBUS data types were presented earlier, but they have been included again in the following table.

The actual equation used to calculate the address depends on the type of PLC data you are using. The PLC memory types are split into two categories for this purpose. S Discrete -- X, SP, Y, CR, S, T, C (contacts) S Word -- V, Timer current value, Counter current value In either case, you basically just convert the PLC octal address to decimal and add the appropriate MODBUS address (if required). The table below shows the exact equation used for each group of data.

DL450 Memory Type

QTY (Dec.)

MODBUS Address Range (Decimal)

PLC Range (Octal)

For Discrete Data Types .... Convert PLC Addr. to Dec.

+

Start of Range

MODBUS Data Type + Data Type

1024

X0

--

X1777

2048

--

3071

Input

Special Relays (SP)

512

SP0 SP320

---

SP137 SP717

3072 3280

---

3167 3535

Input

Outputs (Y)

1024

Y0

--

Y1777

2048

--

3071

Coil

Control Relays (CR)

2048

C0

--

C3777

3072

--

5119

Coil

Timer Contacts (T)

256

T0

--

T377

6144

--

6399

Coil

Counter Contacts (CT)

256

CT0

--

CT377

6400

--

6655

Coil

Stage Status Bits (S)

1024

S0

--

S1777

5120

--

6143

Coil

Global Inputs (GX) *

1536

GX0

--

GX2777

0

--

1535

Input

Global Outputs (GY) *

1536

GY0

--

GY2777

0

--

1535

Coil

For Word Data Types .... Timer Current Values (V)

Convert PLC Addr. to Dec.

+

Data Type

256

V0

--

V377

0

--

255

Input Register

Counter Current Values (V) 256

V1000

--

V1377

512

--

767

Input Register

V--Memory, user data (V)

3072 12288

V1400 -V10000 --

V7377 V37777

768 4096

---

3839 16383

Holding Register

V--Memory, system (V)

320

V700 V7400

V777 V7777

448 3480

---

768 3735

Holding Register

---

* Note: The total of GX and GY global I/O points cannot exceed 1536 points.

DL405 User Manual, 4th Edtition

System Design and Configuration

Inputs (X)

Page 164

4--24

System Design and Configuration The following examples show how to generate the MODBUS address and data type for hosts which require this format.

Example 1: V2100

Find the MODBUS address for User V location V2100. 1. Find V--memory in the table. 2. Convert V2100 into decimal (1088). 3. Use the MODBUS data type from the table. V--Memory, user data (V)

Example 2: Y20

System Design and Configuration

V1400 -V7377 V10000--V37777

1024

Y0

--

Y1777

Find the MODBUS address to obtain the current value from Timer T10. 1. Find Timer Current Values in the table. 2. Convert T10 into decimal (8). 3. Use the MODBUS data type from the table. Timer Current Values (V)

Example 4: C54

V2100 = 1088 decimal 1088 + Hold. Reg. = Holding Reg. 1088

768 4096

---

3839 16383

Holding Register

Find the MODBUS address for output Y20. PLC Addr. (Dec) + Start Addr. + Data Type 1. Find Y outputs in the table. Y20 = 16 decimal 2. Convert Y20 into decimal (16). 16 + 2048 + Coil = Coil 2064 3. Add the starting address for the range (2048). 4. Use the MODBUS data type from the table. Outputs (Y)

Example 3: T10 Current Value

3072 12288

PLC Address (Dec.) + Data Type

256

V0

--

2048

--

3071

Coil

PLC Address (Dec.) + Data Type T10 = 8 decimal 8 + Input Reg. = Input Reg. 8

V377

0

--

255

Input Register

Find the MODBUS address for Control Relay PLC Addr. (Dec) + Start Addr. +Data Type C54. C54 = 44 decimal 1. Find Control Relays in the table. 44 + 3072 + Coil = Coil 3116 2. Convert C54 into decimal (44). 3. Add the starting address for the range (3072). 4. Use the MODBUS data type from the table. Control Relays (CR)

DL405 User Manual, 4th Edition

2048

C0

--

C3777

3072

--

5119

Coil