Page 223

Standard RLL Instructions Timer, Counter, and Shift Register Instructions

Up/Down Counter (UDC)

430 440 450

DS

HPP

This Up/Down Counter counts up on each off to on transition of the Up input and counts down on each off to on transition of the Down input. The counter is reset to 0 when the Reset input is on. The count range is 0--99999999. The count input not being used must be off in order for the active count input to function.

Up

Counters

DL430 Range

CT aaa B bbb

Down

Counter #

Reset

Instruction Specification Counter Reference (CTaaa): Specifies the counter number. Preset Value (Bbbb): Constant value (K) or two consecutive V--memory locations. (V locations are 16-bit words.) Current Values: Current count is a double word value accessed by referencing the associated V or CT memory locations*. The V-memory location is the counter location + 1000. For example, the counter current value for CT5 resides in V--memory location V1005 and V1006. (V locations are 16-bit words.) Discrete Status Bit: The discrete status bit is accessed by referencing the associated CT memory location. It will be on if value is equal to or greater than the preset value. For example the discrete status bit for counter 2 would be CT2. Operand Data Type

UDC

5--51

Preset

The counter discrete status bit and the current value is not specified in the counter instruction.

Caution: The UDC uses two consecutive counter locations, since the preset can now be 8 digits, which requires two V--memory locations. For example, if UDC CT0 is used in the program, the next available counter is CT2. Or if CT0 was a normal counter, and CT1 was an up/down counter, then the next available counter would be CT3.

DL440 Range

DL450 Range

B aaa bbb aaa bbb aaa

CT

0--176

----

0--176

----

0--376 bbb ----

----

1400--7377 10000--37777

V--memory

V

----

1400--7377

----

1400--7377 10000--17777

Pointers (preset only)

P

----

----

----

1400--7377 10000--17777

----

1400--7377 10000--37777

Constants

K

----

0--99999999

----

0--99999999

----

0--99999999

Counter discrete status bits

CT

0--177

0--177

0--377

Counter current values

V/ CT*

1000--1177

1000--1177

1000--1377

Standard RLL Instructions

NOTE:* For the Handheld Programmer, both the Stage Counter discrete status bits and current value can be accessed with the same data type (example CT2). The way the data type is used determines if it is a status bit or a current value. Any comparative instruction using CT2 will access the current value, all other instructions using CT2 will access the status bit. Current values may also be accessed by the V-memory location. For DirectSOFT, the use of CT2 will refer to the timer’s discrete status bit. You should use V1002 (or the alias CTA2) to refer to the current value.

DL405 User Manual, 4th Edition

Page 224

5--52

Standard RLL Instructions Timer, Counter, and Shift Register Instructions

Up/Down Counter Example Using Discrete Status Bits

In the following example if X2 and X3 are off when X1 toggles from off to on the counter will increment by one. If X1 and X3 are off the counter will decrement by one when X2 toggles from off to on. When the count value reaches the preset value of 3, the counter status bit will turn on. When the reset X3 turns on, the counter status bit will turn off and the current value will be 0. Counting Diagram

DirectSOFT X1 UDC

CT2 X1

K3 X2

X2 X3 X3 Y10

Y10

CT2

Current Value

OUT

1

Handheld Programmer Keystrokes

2

1

2

0

Handheld Programmer Keystrokes (cont)

STR

X(IN)

1

K(CON)

3

STR

X(IN)

2

STR

CNT

2

STR

X(IN)

3

OUT

Y(OUT)

1

SHFT

U

D

Up/Down Counter Example Using Comparative Contacts

3

C

SHFT

CNT

0

2

In the following example, when X1 makes an off to on transition, counter CT2 will increment by one. Comparative contacts are used to energize Y3 and Y4 at different counts. The comparative contacts will turn off when the counter is reset. When the reset X3 turns on, the counter status bit will turn off and the current value will be 0. Counting Diagram

DirectSOFT (see Note) X1 UDC

CT2 X1

V1400 X2

X2 X3 X3

CTA2

Y3

K1

Y3

OUT Y4 CTA2

Y4

K2

Current Value

OUT

Standard RLL Instructions

Handheld Programmer Keystrokes

1

2

3

4

0

Handheld Programmer Keystrokes (cont)

STR

X(IN)

1

OUT

Y(OUT)

3

STR

X(IN)

2

STR

CNT

2

STR

X(IN)

3

OUT

Y(OUT)

4

SHFT

U

D

C

SHFT

V

1

4

0

0

STR

CNT

2

K(CON)

1

CNT

K(CON)

2

2

NOTE: Since this representation is showing a DirectSOFT example, you would use the alias CTA2 (or V1002) instead of CT2, which would be necessary for the equivalent rung entered with the Handheld.

DL405 User Manual, 4th Edition

Page 225

5--53

Standard RLL Instructions Timer, Counter, and Shift Register Instructions

The Shift Register instruction shifts data through a predefined number of control relays. The control ranges in the shift register block must start at the beginning of an 8 bit boundary and end at the end of an 8 bit boundary. The Shift Register has three contacts. S Data, determines the value (1 or 0) that will enter the register S Clock, shifts the bits one position on each low to high transition S Reset, resets the Shift Register to all zeros.

Shift Register (SR)

430 440 450

DS

HPP

SR

DATA

From C aaa CLOCK To

C bbb

RESET

With each off to on transition of the clock input, the bits which make up the shift register block are shifted by one bit position and the status of the data input is placed into the starting bit position in the shift register. The direction of the shift depends on the entry in the From and To fields. From C0 to C17 would define a block of sixteen bits to be shifted from lower address to higher address. From C17 to C0 would define a block of sixteen bits, to be shifted from higher address to lower address. The maximum size of the shift register block depends on the number of available control relays. The minimum block size is 8 control relays. Operand Data Type

Control Relay

DL430 Range

DL440 Range

DL440 Range

B aaa bbb aaa bbb aaa bbb

C

0--737

0--737

0--1777

0--1777

0--3777

0--3777

Handheld Programmer Keystrokes

DirectSOFT X1

Data Input

From

X2

STR

X(IN)

1

STR

X(IN)

2

C0

STR

X(IN)

3

SR

C(CR)

0

C17

C(CR)

1

7

SR

Clock Input To

X3

Reset Input

Inputs on Successive Scans Data

Clock

Reset

0

0

0

0

0

1

0

0

0

--

--

1

C0

C17

Standard RLL Instructions

1

Shift Register Bits

DL405 User Manual, 4th Edition

Page 226

5--54

Standard RLL Instructions Accumulator/Data Stack, Load, and Output Instructions

Accumulator/Data Stack Load and Output Instructions Using the Accumulator

Copying Data to the Accumulator

The accumulator in the DL405 series CPUs is a 32 bit register which is used as a temporary storage location for data that is being copied or manipulated in some manner. For example, you have to use the accumulator to perform math operations such as add, subtract, multiply, etc. Since there are 32 bits, you can use up to an 8-digit BCD number, or a 32-bit 2’s complement number. The accumulator is reset to 0 at the end of every CPU scan. The Load and Out instructions and their variations are used to copy data from a V--memory location to the accumulator, or, to copy data from the accumulator to V--memory. The following example copies data from V-memory location V1400 to V--memory location V1410. X1

V1400

LD

8

V1400 Copy data from V1400 to the lower 16 bits of the accumulator

9

3

5

8

9

3

5

8

9

3

5

Unused accumulator bits are set to zero Acc. 0

0

0

0

OUT V1410

V1410

Copy data from the lower 16 bits of the accumulator to V1410

Since the accumulator is 32 bits and V--memory locations are 16 bits, the Load Double and Out Double (or variations thereof) use two consecutive V--memory locations or 8 digit BCD constants to copy data either to the accumulator from a V--memory address or from a V--memory address to the accumulator. For example, if you wanted to copy data from V--memory location V1400 and V1401 to V--memory location V1410 and V1411, the most efficient way to perform this function would be as follows: X1

V1400

V1401

LDD V1400

6

7

3

9

5

0

2

6

Acc. 6

7

3

9

5

0

2

6

6

7

3

9

5

0

2

6

Copy data from V1400 and V1401 to the accumulator

OUTD V1410

Standard RLL Instructions

Copy data from the accumulator to V1410 and V1411

DL405 User Manual, 4th Edition

V1411

V1410

Page 227

5--55

Standard RLL Instructions Accumulator/Data Stack Load and Output Instructions Changing the Accumulator Data

X1

Instructions that manipulate data also use the accumulator. The result of the manipulated data resides in the accumulator. The data that was being manipulated is cleared from the accumulator. The following example loads the constant BCD value 4935 into the accumulator, shifts the data right 4 bits, and outputs the result to V1410. 4

9

3

5

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9

8

7

6 5

4 3

2

1

0

0

1

0

0

1

1

0

1

Constant

LD K4935 Load the value 4935 into the accumulator Acc.

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

0

0

1

0

0

1

0

The upper 16 bits of the accumulator will be set to 0 S S

SHFR K4

S S

Shifted out of accumulator

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9

8

7

6 5

4 3

2

1

0

0

0

0

1

0

1

0

1

1

0

4

9

3

Acc.

0

0

0

0

0 1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

0

0

Shift the data in the accumulator 4 bits (K4) to the right

OUT V1410 Output the lower 16 bits of the accumulator to V1410

V1410

Some of the data manipulation instructions use 32 bits. They use two consecutive V--memory locations or 8 digit BCD constants to manipulate data in the accumulator. The following example rotates the value 67053101 two bits to the right and outputs the value to V1410 and V1411. X1

Constant 6

LDD

7

0

5

3

1

0

1

K67053101 Load the value 67053101 into the accumulator

Acc.

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9

8

7

6 5

4 3

2

1

0

0

0

1

0

0

0

0

0

0

1

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9

8

7

6 5

4 3

2

1

0

0

0

0

0

1

0

0

0

0

8

C

4

0

1

1

0

0

1

1

S S

ROTR K2 Rotate the data in the accumulator 2 bits to the right

Acc.

1 0

0

1 0

1 0

0 1

1

0

0

0

0

0

1

0

1

0

0

1

1

0

0

0

S S

1 0

1 0

1 0

5

9

C

1

0

0

0

0

0

1 0

0

1

0

0

1

1

0

0

OUTD V1410 Output the value in the accumulator to V1410 and V1411

V1411

V1410

DL405 User Manual, 4th Edition

Standard RLL Instructions

0

Page 228

5--56

Standard RLL Instructions Accumulator/Data Stack, Load, and Output Instructions

The accumulator stack is used for instructions that require more than one parameter Using the Accumulator Stack to execute a function or for user defined functionality. The accumulator stack is used when more than one Load type instruction is executed without the use of the Out type instruction. The first load instruction in the scan places a value into the accumulator. Every Load instruction thereafter without the use of an Out instruction places a value into the accumulator and the value that was in the accumulator is placed onto the accumulator stack. The Out instruction nullifies the previous load instruction and does not place the value that was in the accumulator onto the accumulator stack when the next load instruction is executed. Every time a value is placed onto the accumulator stack the other values in the stack are pushed down one location. The accumulator is eight levels deep (eight 32 bit registers). If there is a value in the eighth location when a new value is placed onto the stack, the value in the eighth location is pushed off the stack and cannot be recovered. X1

Constant

LD K3245 Load the value 3245 into the accumulator

Acc. 0

0

0

X

X

X

3

2

4

5

X

5

X

1

X

5

X

1

Acc. 0

0

0

0

5

1

5

Accumulator Stack Level 1

X

X

X

X

X

X

X

X

Level 2

X

X

X

X

X

X

X

X

Level 3

X

X

X

X

X

X

X

X

Level 4

X

X

X

X

X

X

X

X

Level 5

X

X

X

X

X

X

X

X

Level 6

X

X

X

X

X

X

X

X

Level 7

X

X

X

X

X

X

X

X

Level 8

X

X

X

X

X

X

X

X

1

0

0

LD

0

3

6

2

3

4

6

5

3

Current Acc. value Acc. 0

0

0

0

6

3

6

Level 1

0

0

0

0

3

2

4

5

Level 2

X

X

X

X

X

X

X

X

Level 3

X

X

X

X

X

X

X

X

Level 4

X

X

X

X

X

X

X

X

Level 5

X

X

X

X

X

X

X

X

Level 6

X

X

X

X

X

X

X

X

Level 7

X

X

X

X

X

X

X

X

Level 8

X

X

X

X

X

X

X

X

3

Bucket Accumulator Stack

Previous Acc. value Acc. 0

0

0

Bucket

Accumulator Stack

Previous Acc. value

Constant

Load the value 6363 into the accumulator, pushing the value 5151 to the 1st stack location and the value 3245 to the 2nd stack location

5

Current Acc. value

Acc. 0

K6363

4

Previous Acc. value

LD

Standard RLL Instructions

0

Constant

Load the value 5151 into the accumulator, pushing the value 1234 onto the stack

2

Current Acc. value

Acc. X

K5151

3

0

5

1

5

1

Level 1

0

0

0

0

5

1

5

Level 2

0

0

0

0

3

2

4

1 5

Level 3

X

X

X

X

X

X

X

X

Level 4

X

X

X

X

X

X

X

X

Level 5

X

X

X

X

X

X

X

X

Level 6

X

X

X

X

X

X

X

X

Level 7

X

X

X

X

X

X

X

X

Level 8

X

X

X

X

X

X

X

X Bucket

The POP instruction rotates values upward through the stack into the accumulator. When a POP is executed the value which was in the accumulator is cleared and the value that was on top of the stack is in the accumulator. The values in the stack are shifted up one position in the stack.

DL405 User Manual, 4th Edition

Page 229

Standard RLL Instructions Accumulator/Data Stack Load and Output Instructions

X1

5--57

Previous Acc. value

POP

Acc. X POP the 1st value on the stack into the accumulator and move stack values up one location

X

X

X

X

X

X

X Accumulator Stack

Current Acc. value Acc. 0

0

OUT

0

0

V1400

V1400

4

4

5

5

4

4

5

5

Copy data from the accumulator to V1400

Level 1

0

0

0

0

3

7

9

Level 2

0

0

0

0

7

9

3

2 0

Level 3

X

X

X

X

X

X

X

X

Level 4

X

X

X

X

X

X

X

X

Level 5

X

X

X

X

X

X

X

X

Level 6

X

X

X

X

X

X

X

X

Level 7

X

X

X

X

X

X

X

X

Level 8

X

X

X

X

X

X

X

X

Level 1

0

0

0

0

7

9

3

0

Level 2

X

X

X

X

X

X

X

X

Level 3

X

X

X

X

X

X

X

X

Level 4

X

X

X

X

X

X

X

X

Level 5

X

X

X

X

X

X

X

X

Level 6

X

X

X

X

X

X

X

X

Level 7

X

X

X

X

X

X

X

X

Level 8

X

X

X

X

X

X

X

X

Level 1

X

X

X

X

X

X

X

X

Level 2

X

X

X

X

X

X

X

X

Level 3

X

X

X

X

X

X

X

X

Level 4

X

X

X

X

X

X

X

X

Level 5

X

X

X

X

X

X

X

X

Level 6

X

X

X

X

X

X

X

X

Level 7

X

X

X

X

X

X

X

X

Level 8

X

X

X

X

X

X

X

X

0

0

9

2

Previous Acc. value

POP

Acc. 0 POP the 1st value on the stack into the accumulator and move stack values up one location

0

0

0

4

5

4

5

0

3

7

9

2

Accumulator Stack

Current Acc. value Acc. 0

0

OUT

0

V1400

V1401

3

7

9

2

Copy data from the accumulator to V1401 Previous Acc. value POP

Acc. 0

0

0

0

3

7

9

2

X

7

9

3

0

Accumulator Stack

Current Acc. value POP the 1st value on the stack into the accumulator and move stack values up one location

OUT V1402

Acc. X

X

X

V1400

7

9

3

0

Copy data from the accumulator to V1402

Accumulator and Accumulator Stack Memory Locations

430 440 450

DS

HPP

Accumulator 0

0

3

V701

7

V700

Accumulator Stack Level 1

0

0

0

0

3

7

9

2

V703 -- V702

Level 2

0

0

0

0

7

9

3

0

V705 -- V704

Level 3

X

X

X

X

X

X

X

X

V707 -- V706

Level 4

X

X

X

X

X

X

X

X

V711 -- V710

Level 5

X

X

X

X

X

X

X

X

V713 -- V712

Level 6

X

X

X

X

X

X

X

X

V715 -- V714

Level 7

X

X

X

X

X

X

X

X

V717 -- V716

Level 8

X

X

X

X

X

X

X

X

V721 -- V720

DL405 User Manual, 4th Edition

Standard RLL Instructions

There may be times when you want to read a value that has been placed onto the accumulator stack without having to pop the stack first. Both the accumulator and the accumulator stack have corresponding V-memory locations that can be accessed by the program. You cannot write to these locations, but you can read them or use them in comparative boolean instructions, etc.

Page 230

5--58

Standard RLL Instructions Accumulator/Data Stack, Load, and Output Instructions

Using Pointers

Many of the DL405 series instructions will allow V--memory pointers as a operand. Pointers can be useful in ladder logic programming, but can be difficult to understand or implement in your application if you do not have prior experience with pointers (commonly known as indirect addressing). Pointers allow instructions to obtain data from V--memory locations referenced by the pointer value. NOTE: In the DL405 V-memory addressing is in octal. However the value in the pointer location which will reference a V-memory location is viewed as HEX. Use the Load Address instruction to move a address into the pointer location. This instruction performs the Octal to Hexadecimal conversion for you. The following example uses a pointer operand in a Load instruction. V-memory location 1400 is the pointer location. V1400 contains the value 340 which is the HEX equivalent of the Octal address V-memory location V1500. The CPU copies the data from V1500 (contains 2635) into the lower word of the accumulator.

X1

LD P1400 V1400 (P1400) contains the value 340 Hex. 340 Hex. = 1500 Octal which contains the value 2635. V1400 0

3

4

0

V1476

X

X

X

X

V1477

X

X

X

X

V1500

2

6

3

5

V1501

X

X

X

X

V1502

X

X

X

X

V1503

X

X

X

X

V1504

X

X

X

X

V1505

X

X

X

X

OUT

Accumulator 2

6

3

5

S S

V1600 Copy the data from the lower 16 bits of the accumulator to V1600.

V1600

2

6

3

5

V1601

X

X

X

X

The following example is similar to the one above, except for the LDA (load address) instruction which automatically converts the Octal address to the Hex equivalent. X1

LDA O 1500

OUT V 1400

LD P 1400

Load the lower 16 bits of the accumulator with Hexadecimal equivalent to Octal 1500 (340)

1

5

0

0 1500 Octal is converted to Hexadecimal 340 and loaded into the accumulator

Unused accumulator bits are set to zero

Copy the data from the lower 16 bits of the accumulator to V1400

Acc. 0

0

0

0

V1400 (P1400) contains the value 340 HEX 340 HEX. = 1500 Octal which contains the value 2635

0

3

4

0

0

3

4

0

V1400 OUT

Standard RLL Instructions

V 1600

Copy the data from the lower 16 bits of the accumulator to V1600

S S

V1400 0

3

4

0

V1476

X

X

X

X

V1477

X

X

X

X

V1500

2

6

3

5

V1501

X

X

X

X

V1502

X

X

X

X

V1503

X

X

X

X

V1504

X

X

X

X

V1505

X

X

X

X

S S

DL405 User Manual, 4th Edition

V1600

2

6

3

5

V1601

X

X

X

X

Accumulator 0

0

0

0

2

6

3

5

Page 231

5--59

Standard RLL Instructions Accumulator/Data Stack Load and Output Instructions

The Load instruction is a 16 bit instruction that loads the value (Aaaa) (either a V-memory location or a 4 digit constant) into the lower 16 accumulator bits. The upper 16 accumulator bits are set to 0.

Load (LD)

430 440 450

DS

HPP

430 440 450

DS

HPP

A aaa

The Load Double instruction is a 32 bit instruction that loads the value (Aaaa), which is either two consecutive V--memory locations or an 8 digit constant value, into the accumulator.

Load Double (LDD)

LD

Operand Data Type

LDD A aaa

DL430 Range

DL440 Range

DL440 Range aaa aaa aaa

A V--memory

V

All (See p. 3--40)

All (See p. 3--41)

All (See p. 3--42)

Pointer

P

All V mem (See p. 3--40)

All V mem (See p. 3--41)

All V mem (See p. 3--42)

Constant

K

0--FFFF

0--FFFF

0--FFFF

Discrete Bit Flags

Description

SP76 on when the value loaded into the accumulator by any instruction is zero.

NOTE: Two consecutive Load or Load Double instructions will place the value of the first load instruction onto the accumulator stack. In the following Load example, when X1 is on, the value in V1400 will be loaded into the accumulator and output to V1500. Handheld Programmer Keystrokes

DirectSOFT X1

LD V1400 Load the value in V1400 into the lower 16 bits of the accumulator

V1400

STR

X(IN)

1

LD

V

1

4

0

0

OUT

V

1

5

0

0

8

9

3

5

8

9

3

5

8

9

3

5

The unused accumulator bits are set to zero Acc. 0

0

0

0

OUT V1500 Copy the value in the lower 16 bits of the accumulator to V1500

V1500

In the following example, when X1 is on, the 32 bit value in V1400 and V1401 will be loaded into the accumulator and output to V1500 and V1501. DirectSOFT X1

V1500

Copy the value in the 32 bit accumulator to V1500 and V1501

OUTD

V1401

V1400

6

7

3

9

5

0

2

6

Acc. 6

7

3

9

5

0

2

6

6

7

3

9

5

0

2

6

Handheld Programmer Keystrokes STR

X(IN)

1

LD

SHFT

D

SHFT

V

1

4

0

0

OUT

SHFT

D

SHFT

V

1

5

0

0

V1501

V1500

DL405 User Manual, 4th Edition

Standard RLL Instructions

V1400

Load the value in V1400 and V1401 into the 32 bit accumulator

LDD

Page 232

5--60

Standard RLL Instructions Accumulator/Data Stack, Load, and Output Instructions

The Load Formatted instruction loads 1--32 consecutive bits from discrete memory locations into the accumulator. The instruction requires a starting location (Aaaa) and the number of bits (Kbbb) to be loaded. Unused accumulator bit locations are set to zero.

Load Formatted (LDF)

430 440 450

DS

HPP

Operand Data Type

LDF

A aaa K bbb

DL440 Range

DL450 Range

A aaa bbb aaa bbb

Inputs

X

0--477

----

0--1777

----

Outputs

Y

0--477

----

0--1777

----

Control Relays

C

0--1777

----

0--3777

----

Stage Bits

S

0--1777

----

0--1777

----

Timer Bits

T

0--377

----

0--377

----

Counter Bits

CT

0--177

----

0--377

----

Special Relays

SP

0--137 320--717

----

0--137 320--717

----

Global I/O

GX

0--1777

----

0--2777

----

Constant

K

----

1--32

----

1--32

Discrete Bit Flags

Description

SP76 on when the value loaded into the accumulator by any instruction is zero.

NOTE: Two consecutive Load instructions will place the value of the first load instruction onto the accumulator stack. In the following example, when C0 is on, the binary pattern of C10--C16 (7 bits) will be loaded into the accumulator using the Load Formatted instruction. The lower 6 bits of the accumulator are output to Y20--Y26 using the Out Formatted instruction. DirectSOFT C0

LDF

C10 K7

Load the status of 7 consecutive bits (C10--C16) into the accumulator

Constant K7

C16 C15 C14 C13 C12 C11 C10 OFF OFF OFF ON ON ON OFF

The unused accumulator bits are set to zero

Acc.

OUTF

Location C10

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9

8

7

6 5

4 3

2

1

0

0

0

0

0

0

1

1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

Y20 K7

Standard RLL Instructions

Copy the value from the specified number of bits in the accumulator to Y20--Y26

Handheld Programmer Keystrokes STR

C(CR)

0

LD

SHFT

F

SHFT

C(CR)

1

0

K(CON)

7

OUT

SHFT

F

SHFT

Y(OUT)

2

0

K(CON)

7

DL405 User Manual, 4th Edition

Location

Constant

Y26 Y25 Y24 Y23 Y22 Y21 Y20

Y20

K7

OFF OFF OFF ON ON ON OFF