Standard RLL Instructions Program Control Instructions
Goto Subroutine (GTS)
430 440 450
DS
HPP
The Goto Subroutine instruction allows a section of ladder logic to be placed outside the main body of the program execute only when needed. There can be a maximum of 192 (DL440) and an unlimited amount for DL450 GTS instructions.
5--181
K aaa GTS
Upon completion of executing the subroutine, program execution returns to the main program immediately after the GTS instruction. GTS instructions can be nested up to 8 levels. An error E412 will occur if the maximum limits are exceeded. Typically this will be used in an application where a block of program logic may be slow to execute and is not required to execute every scan. Operand Data Type
Constant
Subroutine (SBR)
430 440 450
DS
HPP
DL440 Range
K
DL450 Range aaa aaa
1--FFFF
1--FFFF
The subroutine label and all associated logic is placed after the End statement in the program. There can be a maximum of 64 (DL440) and 256 (DL450) SBR instructions used in a program. When the subroutine is called from the main program, the CPU will execute the subroutine (SBR) with the same constant number (K) as the GTS instruction which called the subroutine.
K aaa
SBR
By placing code in a subroutine it is only scanned and executed when needed since it resides after the End instruction. Code which is not scanned does not impact the overall scan time of the program. Operand Data Type
Constant
Subroutine Return (RT)
430 440 450
DS
HPP
430 440 450
DS
HPP
K
DL450 Range aaa aaa
1--FFFF
1--FFFF
When a Subroutine Return is executed in the subroutine the CPU will return to the point in the main body of the program from which it was called. The Subroutine Return is used as termination of the subroutine which must be the last instruction in the subroutine and is a stand alone instruction (no input contact on the rung). The Subroutine Return Conditional instruction is a optional instruction used with a input contact to implement a conditional return from the subroutine. The Subroutine Return (RT) is still required for termination of the Subroutine.
RT
RTC
DL405 User Manual, 4th Edition
Standard RLL Instructions
Subroutine Return Conditional (RTC)
DL440 Range
Page 354
5--182
Standard RLL Instructions Program Control Instructions In the following example, when X1 is on, Subroutine K3 will be called. The CPU will jump to the Subroutine Label K3 and the ladder logic in the subroutine will be executed. If X35 is on the CPU will return to the main program at the RTC instruction. If X35 is not on Y0--Y17 will be reset to off and then the CPU will return to the main body of the program. DirectSOFT
X1
K3 GTS
C0 LD K10
S S S END
SBR
K3
X20
Y5 OUTI
X21
Y10 OUTI
X35 RTC
X35
Y0
Y17 RSTI
RT
Handheld Programmer Keystrokes STR
X(IN)
1
SHFT
G
T
SHFT
S
STR
SHFT
OUT
S
SHFT
K(CON)
3
B
R
SHFT
K(CON) 1
3
I
SHFT
X(IN)
2
0
SHFT
I
SHFT
Y(OUT)
5
S S
Standard RLL Instructions
END
DL405 User Manual, 4th Edition
STR
SHFT
I
SHFT
X(IN)
2
1
OUT
SHFT
I
SHFT
Y(OUT)
1
0
X(IN)
3
5
STR
SHFT
I
SHFT
SHFT
R
T
C
STR
NOT
SHFT
I
SHFT
X(IN)
3
5
RST
SHFT
I
SHFT
Y(OUT)
0
Y(OUT)
1
SHFT
R
T
7
Page 355
Standard RLL Instructions Program Control Instructions
Master Line Set (MLS)
430 440 450
DS
HPP
The Master Line Set instruction allows the program to control sections of ladder logic by forming a new power rail controlled by the main left power rail. The main left rail is always master line 0. When a MLS K1 instruction is used, a new power rail is created at level 1. Master Line Sets and Master Line Resets can be used to nest power rails up to seven levels deep. Operand Data Type
Constant
Master Line Reset (MLR)
430 440 450
DS
HPP
K aaa MLS
DL430 Range
DL440 Range
DL450 Range aaa aaa aaa
1--7
1--7
1--7
The Master Line Reset instruction marks the end of control for the corresponding MLS instruction. The MLR reference is one less than the corresponding MLS. Operand Data Type
Constant
Understanding Master Control Relays
K
K
5--183
K aaa MLR
DL430 Range
DL440 Range
DL450 Range aaa aaa aaa
0--6
0--6
1--6
The Master Line Set (MLS) and Master Line Reset (MLR) instructions allow you to quickly control the power flow for sections of the RLL program. This provides program control flexibility. The following example shows how the MLS and MLR instructions operate by creating a sub power rail for control logic.
430 440 450
DS
HPP
In the following MLS/MLR example, logic between the first MLS K1 (A) and MLR K0 (B) will only have power flow present at the power rail if input X0 is on. (Note, if X0 is MLS/MLR Example off the logic will still be scanned, but there is no power flow.) The logic between the MLS K2 (C) and MLR K1 (D) will only have power flow present at the power rail if input X10 and X0 are on. The last rung is not controlled by either of the MLS coils and always has power flow present at the beginning of the rung. Remember, the MLS / MLR instructions control the power flow between the power rails. It does not control the execution of the instructions. The instructions are still executed, but since there is no power flow, the logic cannot turn on the output coils. Consider the following case for our example.
DL405 User Manual, 4th Edition
Standard RLL Instructions
1. X0 is off, which means that there is no power flow at the second rung. 2. You use a programming device to turn on C0. Since there is no power flow at the second rung (STR X1, OUT C0), then you would expect that C0 would remain on, since you turned it on with the programming device. However, the MLS instruction does not mean that the instructions within the zone of control are not executed. They are in fact executed, but with no power flow. So in our case, C0 would be turned off when the rung was executed. This is because the CPU sees that there is no power flow present at the rung. When it executes this rung, it will turn off C0.
Page 356
5--184
Standard RLL Instructions Program Control Instructions
DirectSOFT X0
K1 MLS
X1
When contact X0 is on, logic under the first MLS will be executed.
Y7 OUT K2
X2
MLS X3
When contact X0 and X2 are ON, logic under the second MLS will be executed.
Y10 OUT K1 MLR The MLR instructions note the end of the Master Control area.
K0 MLR Y11
X10
OUT
DirectSOFT X0
Handheld Programmer Keystrokes K1 MLS
X1
A
C0 OUT
X2
C1
X5
X4
X(IN)
1
C(CR)
0
STR
X(IN)
3
OUT
Y(OUT)
0
STR
X(IN)
1
MLS
MSL
K(CON)
2
Y1
STR
X(IN)
5
OUT
OUT
Y(OUT)
1
Y0
K2
C
Y2
D
C2
Y3 OUT
Standard RLL Instructions
STR OUT
1
OUT
K0 MLR Y22 OUT
DL405 User Manual, 4th Edition
1
2
MLR
X7
K(CON)
X(IN)
K1
X6
MLS
C(CR)
OUT
X5
0
STR
OUT X10
X(IN)
OUT
OUT X3
STR
B
STR
X(IN)
4
OUT
Y(OUT)
2
MLR
K(CON)
1
STR
X(IN)
5
OUT
C(CR)
2
STR
X(IN)
6
OUT
Y(OUT)
3
MLR
K(CON)
0
STR
X(IN)
7
OUT
Y(OUT)
2
0
2
Page 357
5--185
Standard RLL Instructions Interrupt Instructions
Interrupt Instructions The Interrupt instruction allows a section of ladder logic to be placed outside the main body of the program and executed when O aaa INT needed. Interrupts can be called from the program or an interrupt module can be installed in slot 0 to provide 8 interrupt inputs. One interrupt module can be installed in a DL430 system (X0--X7) and two interrupt modules can be installed in a DL440 or DL450 System (X0--X7, and X20--X27). Remember, the interrupt modules consume 16 points. The two software interrupts use interrupt #16 and #17 which means the hardware interrupts #16 and #17 and the software interrupt cannot be used together. Typically, interrupts will be used in an application where a fast response to an input is needed or a program section needs to execute faster than the normal CPU scan. The interrupt label and all associated logic must be placed after the End statement in the program. When the interrupt routine is called from the interrupt module or software interrupt, the CPU will complete execution of the instruction it is currently processing in ladder logic, then execute the designated interrupt routine. There are two software interrupts and INT 16 and INT 17. Once the interrupt is serviced, the program execution will continue from where it was before the interrupt occurred. The software interrupts are setup by programming the interrupt times in V736 and V737. The valid range is 3--999ms. The value must be a BCD value. The interrupt will not execute if the value is out of range. See the example program of a software interrupt.
Interrupt (INT)
430 440 450
DS
HPP
Operand Data Type
Constant
DL430 Range
DL440 Range aaa aaa aaa
0--7
0--17
0--17
O Software
DL430
DL440/450
Interrupt Input
Interrupt Routine
Interrupt Input
Interrupt Routine
Interrupt Input
Interrupt Routine
----
----
X0
INT 0
X0
INT 0
----
----
X1
INT 1
X1
INT 1
----
----
X2
INT 2
X2
INT 2
----
----
X3
INT 3
X3
INT 3
----
----
X4
INT 4
X4
INT 4
----
----
X5
INT 5
X5
INT 5
----
----
X6
INT 6
X6
INT 6
----
----
X7
INT 7
X7
INT 7
----
----
----
----
X20
INT 10
----
----
----
----
X21
INT 11
----
----
----
----
X22
INT 12
----
----
----
----
X23
INT 13
----
----
----
----
X24
INT 14
----
----
----
----
X25
INT 15
V736 sets interrupt time
INT 16
----
----
X26(cannot be used along with s/w interrupt)
INT 16
V737 sets interrupt time
INT 17
----
----
X27 (cannot be used along with s/w interrupt)
INT 17
DL405 User Manual, 4th Edition
Standard RLL Instructions
2nd Module
DL450 Range
Page 358
5--186
Standard RLL Instructions Interrupt Instructions
Interrupt Return (IRT)
430 440 450
DS
HPP
Interrupt Return Conditional (IRTC)
430 440 450
DS
HPP
Enable Interrupts (ENI)
430 440 450
DS
HPP
Disable Interrupts (DISI)
430 440 450
DS
HPP
The Interrupt Return Conditional instruction is a optional instruction used with an input contact to implement a conditional return from the interrupt routine. The Interrupt Return is still required to terminate the interrupt routine
IRT
IRTC
The Enable Interrupt instruction is programmed in the main body of the application program (before the End instruction) to enable hardware or software interrupts. Once the coil has been energized interrupts will be enabled until the interrupt is disabled by the Disable Interrupt instruction.
ENI
The Disable Interrupt instruction is programmed in the main body of the application program (before the End instruction) to disable both hardware or software interrupts. Once the coil has been energized interrupts will be disabled until the interrupt is enabled by the Enable Interrupt instruction.
DISI
Standard RLL Instructions
When an Interrupt Return is executed in the interrupt routine the CPU will return to the point in the main body of the program from which it was called. The Interrupt Return is programmed as the last instruction in an interrupt routine and is a stand alone instruction (no input contact on the rung).
DL405 User Manual, 4th Edition
Page 359
Standard RLL Instructions Interrupt Instructions Interrupt Example for Interrupt Module
5--187
In the following example, when X40 is on, the interrupts will be enabled. When X40 is off the interrupts will be disabled. When a interrupt signal X1 is received the CPU will jump to the interrupt label INT O 1. The application ladder logic in the interrupt routine will be performed. If X35 is on the CPU will return to the main program with the IRTC instruction. If X35 is not on Y0--Y17 will be reset to off and then the CPU will return to the main body of the program.
DirectSOFT
Handheld Programmer Keystrokes STR
X40 ENI
X40
X(IN)
4
0
SHFT
E
N
I
STR
NOT
X(IN)
1
7
SHFT
D
I
S
I
SHFT
I
N
T
OCT
1
STR
SHFT
I
SHFT
X(IN)
2
OUT
SHFT
I
SHFT
Y(OUT)
5
STR
SHFT
I
SHFT
X(IN)
2
1
OUT
SHFT
I
SHFT
Y(OUT)
1
0
STR
SHFT
I
SHFT
X(IN)
3
5
S DISI
S END
S S S END S S S INT
O1
X20
Y5 OUTI
X21
0
SHFT
I
R
T
C
STR
NOT
SHFT
I
SHFT
X(IN)
3
5
RST
SHFT
I
SHFT
Y(OUT)
0
Y(OUT)
1
SHFT
I
R
T
7
Y10 OUTI
X35 IRTC
X35
Y0
Y17 RSTI
IRT
Standard RLL Instructions
DL405 User Manual, 4th Edition
Page 360
5--188
Standard RLL Instructions Interrupt Instructions In the following example, when X1 is on, the value 10 is copied to V737. This value sets the software interrupt to 10 ms. When X20 turns on, the interrupt will be enabled. When X20 turns off, the interrupts will be disabled. Every 10 ms the CPU will jump to the interrupt label INT O 17. The application ladder logic in the interrupt routine will be performed. If X35 is on the CPU will return to the main program with the IRTC instruction. If X35 is not on Y0--Y17 will be reset to off and then the CPU will return to the main body of the program when the IRT instruction is executed. The software interrupt is limited to the range 3 -- 999 milliseconds. Entering a 0, 1, or 2 will yield an interrupt time of 3 milliseconds.
Interrupt Example for Software Interrupt
DirectSOFT
Handheld Programmer Keystrokes X1
LD K10 Load the constant value (K10) into the lower 16 bits of the accumulator
STR
X(IN)
1
LD
K(CON)
1
0
OUT
V
7
3
7
STR
X(IN)
2
0
V737
SHFT
E
N
I
Copy the value in the lower 16 bits of the accumulator to V737
STR
NOT
X(IN)
2
0
SHFT
D
I
S
I
SHFT
I
N
T
OCT
1
7
STR
SHFT
I
SHFT
X(IN)
2
0
OUT
S X20
S END
ENI
X20 DISI
S S
OUT
SHFT
I
SHFT
Y(OUT)
5
STR
SHFT
I
SHFT
X(IN)
2
1
OUT
SHFT
I
SHFT
Y(OUT)
1
0
STR
SHFT
I
SHFT
X(IN)
3
5
SHFT
I
R
T
C
STR
NOT
SHFT
I
SHFT
X(IN)
3
5
RST
SHFT
I
SHFT
Y(OUT)
0
Y(OUT)
1
SHFT
I
R
T
S END
INT
O 17
X20
Y5 OUTI
X21
Y10 OUTI
X35
Standard RLL Instructions
IRTC
X35
Y0
Y17 RSTI
IRT
DL405 User Manual, 4th Edition
7
Page 361
Standard RLL Instructions Intelligent I/O Instructions
5--189
Intelligent I/O Instructions Read from Intelligent Module (RD)
430 440 450
DS
HPP
The Read from Intelligent Module instruction reads a block of data (1--128 RD bytes maximum) from an intelligent I/O V aaa module into the CPU’s V--memory. It loads the function parameters into the first and second level of the accumulator stack, and the accumulator by three additional instructions. Listed below are the steps to program the Read from Intelligent module function. Step 1:, Load the base number (0--3) into the first byte and the slot number (0--7) into the second byte of the second level of the accumulator stack. Step 2:, Load the number of bytes to be transferred into the first level of the accumulator stack. (maximum of 128 bytes) Step 3:, Load the address from which the data will be read into the accumulator. This parameter must be a HEX value. Step 4:, Insert the RD instruction which specifies the starting V memory location (Vaaa) where the data will be read into. Helpful Hint:, Use the LDA instruction to convert an octal address to its HEX equivalent and load it into the accumulator when the hex format is required. Operand Data Type
V--memory
V
DL430 Range
DL440 Range
DL450 Range aaa aaa aaa
All (See p. 3--40)
All (See p. 3--41)
All (See p. 3--42)
Discrete Bit Flags
Description
SP54 on when RX, WX, RD, WT instructions are executed with the wrong parameters.
NOTE: Status flags are valid only until another instruction uses the same flag. In the following example when X1 is on, the RD instruction will read six bytes of data from a intelligent module in base 1, slot 2 starting at address 0 in the intelligent module and copy the information into V-memory locations V1400--V1402. CPU
DirectSOFT X1
LD K0102
LD K6
The constant value K0 specifies the starting address in the intelligent module
V1400
V1400 is the starting location in the CPU where the specified data will be stored
RD
V1400
3
4
1
2
V1401
7
8
5
6
V1402
0
1
9
0
V1403
X
X
X
X
V1404
X
X
X
X
12
Address 0
34
Address 1
56
Address 2
78
Address 3
90
Address 4
01
Address 5
Standard RLL Instructions
The constant value K6 specifies the number of bytes to be read
K0
LD
Intelligent Module Data
The constant value K0102 specifies the base number (01) and the base slot number (02)
Handheld Programmer Keystrokes STR
X(IN)
1
LD
K(CON)
0
LD
K(CON)
6
LD
K(CON)
0
V
1
4
1
0
0
2
SHFT
R
D
SHFT
0
DL405 User Manual, 4th Edition
Page 362
5--190
Standard RLL Instructions Intelligent I/O Instructions
Write to Intelligent Module (WT)
430 440 450
DS
HPP
The Write to Intelligent Module instruction writes a block of data (1--128 bytes maximum) to an intelligent I/O module from WT a block of V--memory in the CPU. The V aaa function parameters are loaded into the first and second level of the accumulator stack, and the accumulator by three additional instructions. Listed below are the steps necessary to program the Read from Intelligent module function. Step 1:, Load the base number (0--3) into the first byte and the slot number (0--7) into the second byte of the second level of the accumulator stack. Step 2:, Load the number of bytes to be transferred into the first level of the accumulator stack. (maximum of 128 bytes) Step 3:, Load the intelligent module address which will receive the data into the accumulator. This parameter must be a HEX value. Step 4:, Insert the WT instruction which specifies the starting V memory location (Vaaa) where the data will be written from in the CPU. Helpful Hint:, Use the LDA instruction to convert an octal address to its HEX equivalent and load it into the accumulator when the hex format is required. Operand Data Type
V--memory
V
DL430 Range
DL440 Range aaa aaa
DL450 Range aaa
All (See p. 3--40)
All (See p. 3--41)
All (See p. 3--42)
Discrete Bit Flags
Description
SP54 on when RX, WX, RD, WT instructions are executed with the wrong parameters.
NOTE: Status flags are valid only until another instruction uses the same flag. In the following example, when X1 is on, the WT instruction will write six bytes of data to an intelligent module in base 1, slot 2 starting at address 0 in the intelligent module and copy the information from Vmemory locations V1400--V1402. DirectSOFT X1
CPU LD K0102
LD
Standard RLL Instructions
K6
LD K0
WT V1400
The constant value K0102 specifies the base number (01) and the base slot number (02)
Data
The constant value K6 specifies the number of bytes to be written
The constant value K0 specifies the starting address in the intelligent module
V1400 is the starting location in the CPU where the specified data will be written from
DL405 User Manual, 4th Edition
Intelligent Module
V1377
X
X
X
X
V1400
3
4
1
2
V1401
7
8
5
6
V1402
0
1
9
0
V1403
X
X
X
X
V1404
X
X
X
X
12
Address 0
34
Address 1
56
Address 2
78
Address 3
90
Address 4
01
Address 5
Handheld Programmer Keystrokes STR
X(IN)
1
LD
K(CON)
0
LD
K(CON)
6
LD
K(CON)
0
V
1
4
1
0
0
2
SHFT
W
0
T
SHFT