The text of a manual · part 57 of 68
DL405 User Manual: Chapter 9: Maintenance and Troubleshooting, pages 505 to 513
Pages 505 to 513 of 608, from DL405 User Manual
The original document is the PDF (8.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect D4-08B-1, AutomationDirect D4-08ND3S, AutomationDirect D4-16TA, PLC Direct D4-16TD2, AutomationDirect D4-32ND3-1, Konnect-It D4-08B-1, Koyo D4-08B-1, Konnect-It D4-08ND3S, and 6 more models
Page 505
Maintenance and Troubleshooting
19
In This Chapter. . . ., Hardware Maintenance, Diagnostics, CPU Indicators, I/O Module Troubleshooting, Noise Troubleshooting, Machine Startup and Program Troubleshooting
Page 506
9--2
Maintenance and Troubleshooting
Hardware Maintenance Standard Maintenance
A routine maintenance check (about every one or two months) or your PLC and control system is good practice, an should include the following items: S Air Temperature -- Check the ambient air temperature in the control cabinet, so the operating temperature range of any component is not exceeded. S Air Filter -- If the control cabinet has an air filter, clean or replace it periodically as required. S Memory Backup Battery -- Make sure the CPU memory backup battery does not become completely discharged. The CPU uses the same battery indicator to signal a low CPU battery and if applicable a low memory cartridge battery. Make sure you have correctly diagnosed which battery is requiring replacement. S Fuses or breakers -- verify that all fuses and breakers are intact. S DL405 Module Air Vents -- verify that all air vents of the CPU and all I/O modules are clear, allowing air to circulate for cooling.
CPU Battery Replacement
The CPU battery is used to retain program V-memory and the system parameters. The life expectancy of this battery is five years.
Maintenance and Troubleshooting
NOTE: Before replacing your CPU battery you should back-up your V-memory and system parameters. This can be done by saving the V-memory and system parameters to either a Memory Cartridge or to cassette tape or by using DirectSOFT to save the program to hard/floppy disk on a personal computer. To prevent memory loss the CPU battery can be changed while the system is powered up. If the CPU has been powered off you should power-up the CPU for at least 5 seconds prior to changing the battery. This is done to ensure the capacitor used to maintain the proper voltage levels necessary to retain memory is fully charged.
Replace battery with part #D3--D4--BAT
DL405 User Manual, 4th Edition
To replace the CPU battery: S Pull the battery out from the battery retaining clip. S Lift the clip on the two wire battery connector. S Slide the battery connector apart. To install the CPU battery: S Join the (keyed) battery connector so the red wires match. S Push gently till the connector snaps closed S Slide the battery into the battery retaining clip till the battery lies flush in the opening. S Note the date the battery was changed. WARNING: Do not attempt to recharge the battery or dispose of it by fire. The battery may explode or release hazardous materials.
Page 507
Maintenance and Troubleshooting CMOS RAM Memory Cartridge Battery Replacement
9--3
The CMOS RAM Memory Cartridge battery is used to maintain the contents of the Memory Cartridge RAM when the power is turned off. The life expectancy of this battery is three years. NOTE: For added security you will want to save the contents of the memory cartridge to either another memory cartridge, cassette tape, or computer disk,to avoid losing the contents of the memory cartridge when the battery is removed. The memory cartridge does however have a built in capacitor to retain the memory for several minutes while the battery is being replaced. If the system has been powered off, you should power-up the CPU with the memory cartridge installed for at least 5 seconds prior to changing the battery. This is done to ensure the capacitor used to maintain the proper voltage levels necessary to retain memory is fully charged. WARNING: Never remove the Memory Cartridge from the CPU when the CPU is powered-up. If the memory cartridge is removed while under power the memory cartridge may become unreliable. Do not attempt to recharge the battery or dispose of it by fire. The battery may explode or release hazardous materials.
Replace battery with part # D4--MC--BAT
DL405 User Manual, 4th Edition
Maintenance and Troubleshooting
To remove the CMOS RAM Memory Cartridge battery: 1. Power down the CPU. 2. Remove the memory cartridge from the CPU by gently pulling the lever down till the cartridge is loosened, then pull the lever straight out . 3. Remove the cover retaining screw. 4. Lift top cover off ( lifting at a slight tilt to avoid breaking the guides beside the connector). 5. Grasp battery and lift straight up. To install the CMOS RAM Memory Cartridge battery: 1. Align the battery leads to the (keyed) holes in the circuit board. 2. Press the battery flush with the circuit board. 3. Place cover back on module (using a slight tilt to catch the guides beside the connector). 4. Install the cover retaining screw. 5. Note the date the battery was changed.
Page 508
9--4
Maintenance and Troubleshooting
Maintenance and Troubleshooting
Diagnostics Diagnostics
DL405 performs over 90 pre-defined diagnostic routines with every CPU scan. The diagnostics have been designed to detect failures for the CPU local base and local expansion bases. These detected errors cover the following: CPUs, expansion units, I/O, bases, communication modules, memory cartridges and batteries. There are two primary error classes: fatal and non-fatal.
Fatal Errors
Fatal errors are errors the CPU has detected that offer a risk of the system not functioning safely or properly. They will either cause the CPU to change from RUN mode to PROGRAM or will disallow changing from PROGRAM mode to RUN mode. If the fatal error is detected while in PROGRAM mode the CPU will not enter the RUN mode until the error has been corrected. Examples of fatal errors: S Power supply failure on the CPU base S Parity error or CPU malfunction S Certain programming errors
Non-fatal Errors
Non-fatal errors are errors that are flagged by the CPU as requiring attention. They can neither cause the CPU to change from RUN mode to PROGRAM nor do they prevent entering RUN mode. There are special relays the application program can use to detect if a non-fatal error has occurred. The application program can then be used to take the system to an orderly shutdown or switch the PLC out of RUN mode if needed. Example of non-fatal errors are: S Battery backup battery voltage low S All I/O module errors S Certain programming errors
Finding Diagnostic Diagnostic information can be found in several places with varying levels of message detail. Information S The CPU automatically logs error codes and any FAULT messages into two separate tables which can be viewed with the Handheld or DirectSOFT. S The handheld programmer displays error numbers and short descriptions of the error. S DirectSOFT provides the error number and an error message. S Appendix B in this manual has a complete list of error messages sorted by error number. Many of these messages point to supplemental memory locations which can be referenced for additional related information. These memory references are in the form of V-memory and SPs (special relays). The following two tables name the specific memory locations that correspond to certain types of error messages. The special relay table also includes status indicators which can be used in programming. For a more detailed description of each of these special relays refer to Appendix D.
DL405 User Manual, 4th Edition
Page 509
Maintenance and Troubleshooting V-memory Error Code Locations
9--5
The following table names the specific memory locations that correspond to certain types of error messages. Error Class
Error Category
Diagnostic V-memory
Minor
Battery Voltage (DL450)
V7746
System
10ms calender timer (DL440/450)
V7747
User-defined
Fault message error code
V7751
I/O configuration
Current module ID code
V7752
I/O configuration
Correct module ID code
V7753
I/O configuration
Base number/Slot number
V7754
Fatal
Error code
V7755
Major
Error code
V7756
Minor
Communications Error code
V7757
Module
Base number/Slot number
V7760
Module
Error code
V7762
Grammatical
Address
V7763
Grammatical
Error Code
V7764
Special Relays (SP) The special relay table also includes status indicators which can indicate errors. For Corresponding to a more detailed description of each of these special relays refer to Appendix D. Error Codes Startup and Real-time Relays
CPU Status Relays
System Monitoring Relays
Accumulator Status Relays
Communication Monitoring Relays
First scan relay
SP11
Forced run mode relay
SP40
Critical error relay
SP60
Value less than relay
SP120
Module busy relay Slot 0
SP1
Always ON relay
SP12
Terminal run mode relay
SP41
Warning relay
SP61
Value equal to relay
SP121
Communication error relay Slot 0
SP3
1 minute relay
SP13
Test run mode relay
SP43
Battery low relay
SP62
Value greater than relay
SP122
Module busy relay Slot 1
SP4
1 second relay
SP14
Break relay 1
SP44
Program memory error relay
SP63
Zero relay
SP123
Communication error relay Slot 1
SP5
100 millisecond relay
SP15
Test program mode relay
SP45
I/O error relay
SP64
Half borrow relay
SP124
Module busy relay Slot 2
SP6
50 millisecond relay
SP16
Terminal program mode relay
SP46
Communications error relay
SP65
Borrow relay
SP125
Communication error relay Slot 2
SP7
Alternate scan relay
SP17
Forced stop mode relay
SP47
I/O configuration error relay
SP66
Half carry relay
SP126
Module busy relay Slot 3
SP21
Break relay 2
SP50
FAULT instruction relay
SP67
Carry relay
SP127
Communication error relay Slot 3
SP22
Interrupt enabled relay
SP51
Math timeout relay
SP70
Sign relay
SP130
Module busy relay Slot 4
SP25
CPU battery disabled relay
SP52
Grammatical error relay
SP71
Pointer reference error
SP131
Communication error relay Slot 4
SP26
I/O update disable relay (DL440)
SP53
Math/Table pointer error
SP73
Overflow relay
SP132
Module busy relay Slot 5
SP27
Selective I/O update disable relay (DL440)
SP54
Communication error
SP75
Data error relay
SP133
Communication error relay Slot 5
SP30
Dipswitch 1 status relay
SP56
Table instruction overrun relay
SP76
Load zero relay
SP134
Module busy relay Slot 6
SP31
Dipswitch 2 status relay
SP135
Communication error relay Slot 6
SP32
Dipswitch 3 status relay
SP136
Module busy relay Slot 7
SP33
Dipswitch 4 status relay
SP137
Communication error relay Slot 7
DL405 User Manual, 4th Edition
Maintenance and Troubleshooting
SP0
Page 510
9--6
Maintenance and Troubleshooting
I/O Module Codes
Each system component has a code identifier. This code identifier is used in some of the error messages related to the I/O modules. The following table list these codes. Code (Hex)
Component Type
Code (Hex)
Component Type
01
CPU
21
8 pt. Input
02
Expansion Unit
28
16 pt. Output, FL series Analog Output
03
I/O Base
2B
16 pt. Input, FL series Analog Input, Interrupt
11
DCM, All CoProcessor Modules
30
32 pt. Output, DL series Analog Output
12
Remote Master, Slice Master
3F
32 pt. Input, DL series Analog Input
18
High Speed Counter, Magnetic Pulse Input
7F
Abnormal
20
8 pt. Output
FF
No module detected
Maintenance and Troubleshooting
The following diagram shows an example of how the I/O module codes are used:
Incorrect module
Program Control Information V7752 0028 Current module ID code V7753 0026 Current module ID code V7754 0002 Location of conflict V7756 0252 Module Error Code SP45
DL405 User Manual, 4th Edition
I/O abnormality
Page 511
Maintenance and Troubleshooting Error Message Tables X 430 440 450
9--7
The DL440 and DL450 CPUs will automatically log any system error codes and any custom messages you have created in your application program with the Fault instructions. (See Chapter 11 for details on the Fault instruction.) The CPU logs the error code, the date, and the time the error occurred. There are two separate tables that store this information. S System Error Table -- stores up to 32 errors in the table. S Fault Message Table -- stores up to 16 messages in the table. When an error or message is triggered, it is put into the first available table location. Therefore, the most recent error message may not appear in the first row of the table. If the table is full when an error occurs, the oldest error is pushed (erased) from the table and the new error is inserted in the row. The following diagram shows an example of a the Fault Message table as shown in DirectSOFT. You can access the error code table and the message table through DirectSOFT’s PLC Diagnostic sub-menus. Details on how to access these logs are provided in the DirectSOFT manual. Error Msg. Example Most recent message appears here, not at the top of the table.
Next message will show up in this row, which is now the oldest message.
Use AUX 5C to view the tables CLR
AUX
5
SHFT
C
ENT
AUX 5C SHOW ERR/MSG ERR OR MSG
Arrow key selects Errors or Messages SHFT
ENT
Example of a message display
AUX 5C SHOW ERR/MSG ERR OR MSG
PUMP 3 FAILED 04/22/93 17:30:00
DL405 User Manual, 4th Edition
Maintenance and Troubleshooting
You cannot view the entire table at one time with the handheld programmer. Instead, the messages automatically appear on the handheld programmer display as they occur. The message will remain on the display as long as the Fault instruction is being executed. The following examples show you how to use the Handheld and AUX Function 5C to show the error codes. The most recent error or message is always displayed. You can use the PREV and NXT keys to scroll through the messages.
Page 512
9--8
Maintenance and Troubleshooting
System Error Codes X 430 440 450
The System error log contains 32 of the most recent errors that have been detected. The errors that are trapped in the error log are a subset of all the error messages which the DL405 systems generate. The following errors are captured in the System error log upon first detection or reoccurrence. Error Code
Description
Error Code
Description
E003
Software time-out
E155
RAM failure
E004
Invalid instruction (RAM parity error in the CPU)
E201
Terminal block missing
E041
CPU battery low
E202
Missing I/O module
E043
Memory cartridge battery low
E203
Blown fuse
E099
Program memory exceeded
E206
User 24V power supply failure
E101
CPU memory cartridge missing
E250
Communication failure in the I/O chain
E104
Write fail
E251
I/O parity error
E151
Invalid Command
E252
New I/O configuration
Maintenance and Troubleshooting
These errors are captured in the System error log if they exist when the CPU attempts to transition to RUN mode. Error Code
Description
Error Code
Description
E401
Missing END statement
E431
Invalid ISG/SG address
E402
Missing LBL
E432
Invalid jump (GOTO) address
E403
Missing RET
E433
Invalid SBR address
E404
Missing FOR
E434
Invalid RTC address
E405
Missing NEXT
E435
Invalid RT address
E406
Missing IRT
E436
Invalid INT address
E412
SBR/LBL > 64
E437
Invalid IRTC address
E413
FOR/NEXT > 64
E438
Invalid IRT address
E421
Duplicate stage reference
E440
Invalid Data Address
E422
Duplicate SBR/LBL reference
E441
ACON/NCON
E423
Nested loops
DL405 User Manual, 4th Edition
Page 513
Maintenance and Troubleshooting
9--9
CPU Status Indicators The DL405 CPUs have indicators on the front to help you diagnose problems with the system. The table below gives a quick reference of potential problems associated with each status indicator. Following the table is a detailed description of each indicator.
Status
Potential Causes
PWR
OFF
1. Power input voltage is incorrect for selected operating mode, 110/220 VAC select jumper incorrect on CPU terminal strip 2. External power is off or disconnected (check fuses, breakers) 3. Power supply/CPU is faulty 4. Other component such an I/O module has power supply shorted 5. Power budget exceeded for the CPU being used
RUN
OFF
1. CPU programming error 2. Key switch in STOP position
Flashing
CPU is in firmware upgrade mode
CPU
ON
1. Electrical noise interference 2. CPU defective
BATT
ON, or flashing
1. Flashing at 2 Hz: CPU battery low 2. Flashing at 0.5 Hz: Memory cartridge battery low (DL440/DL450 only) 3. On constantly: Both the CPU and MC batteries are low 4. CPU or Memory cartridge battery missing, or disconnected
DIAG (DL450)
ON
1. The CPU internal diagnostics has failed 2. The local bus on the backplane has had a communications error
I/O
ON
1. I/O module failure 2. External power supply failure 3. Configuration error 4. Base expansion unit failure
COM (DL430/ DL440)
ON
1. Device port setup incorrect 2. Cabling error 3. Grounding problem 4. Electrical noise 5. Device port faulty
TXD (DL450)
OFF
1. The CPU is not transmitting data on the secondary ports (ports 1, 2, and 3), due to programming error 2. The CPU is not in Run mode
RXD (DL450)
OFF
1. External device is not transmitting to CPU secondary ports (ports 1, 2, and 3) 2. Communications cable is defective, or not connected
DL405 User Manual, 4th Edition
Maintenance and Troubleshooting
Indicator