Page 531
Auxiliary Functions
1A
In This Appendix. . . ., Introduction, AUX 1*, Operating Modes, AUX 2*, RLL Operations, AUX 3*, V-memory Operations, AUX 4*, I/O Configuration, AUX 5*, CPU Configuration, AUX 6*, Handheld Programmer Configuration, AUX 7*, Memory Cartridge Operations, AUX 8*, Password Operations
Page 532
Appendix A Auxiliary Functions
A--2
Auxiliary Functions
Introduction What are Auxiliary Functions?
Many CPU setup tasks involve the use of Auxiliary (AUX) Functions. The AUX Functions perform various operations, ranging from simple operating mode changes to copying programs to memory cartridges. They are divided into categories that affect different system resources. You can access AUX Functions from DirectSOFT or from the Handheld Programmer. Some AUX Functions are designed specifically for the Handheld Programmer setup, so they will not be available with the DirectSOFT package. You may need to supplement this Appendix with information from the documentation for your choice of programming device.
AUX Function and Description
430
440
450
HPP
AUX 1*, Operating Mode
AUX Function and Description
430
440
450
HPP
AUX 5*, CPU Configuration
11
Go to Run Mode
51
Modify Program Name
12
Go to Test Mode
52
Display / Change Calendar
13
Go to Program Mode
53
Display Scan Time
14
Run Time Edit
54
Initialize Scratchpad
55
Set Watchdog Timer
AUX 2*, RLL Operations 21
Check Program
56
Configure Comm. Ports
22
Change Reference
57
Set Retentive Ranges
23
Clear Ladder Range
58
Test Operations
24
Clear Ladders
5C
Display Error History
25
Select MC or Flash Memory
5D
Select PLC Scan Mode
26
Copy MC Contents to Flash
AUX 6*, Handheld Programmer Configuration
27
Copy Flash contents to MC
61
Show Revision Numbers
28
Verify Flash contents = MC
62
Beeper On / Off
63
Backlight On / Off
AUX 3*, V-Memory Operations
31
Clear V Memory
64
Select Online / Offline
32
Clear V Range
65
Run Self Diagnostics
33
Find V-memory Value
AUX 7*, Memory Cartridge Operations
AUX 4*, I/O Configuration
71
CPU to Memory Cartridge
41
Show I/O Configuration
72
Memory Cartridge to CPU
42
I/O Diagnostics
73
Compare MC with CPU
44
Power up I/O Configuration Check
74
Memory Cart. Blank Check
45
Select Configuration
75
Clear Memory Cartridge
46
Configure I/O
76
Display Memory Cart. Type
47
Intelligent I/O
77
Tape to Memory Cartridge
78
Memory Cartridge to Tape
79
Compare MC with Tape, supported, not supported or not applicable
DL405 User Manual, 4th Edition
AUX 8*, Password Operations 81
Modify Password
82
Unlock CPU
83
Lock CPU
Page 533
Auxilliary Functions
DirectSOFT provides various menu options during both online and offline programming. Some of the AUX functions are only available during online programming, some only during offline programming, and some during both online and offline programming. The following diagram shows an example of the PLC operations menu available within DirectSOFT.
Menu Options
Accessing AUX Functions via the Handheld Programmer
You can also access the AUX functions by using a Handheld Programmer. Plus, remember some of the AUX functions are only available from the Handheld. The following diagram shows how you could quickly access the AUX function from the Handheld. CLR
AUX
AUX FUNCTION SELECTION AUX 1* OPERATING MODE
Use NXT or PREV to cycle through the menus NXT
AUX FUNCTION SELECTION AUX 2* RLL OPERATIONS
Press ENT to select sub-menus ENT
AUX 2* RLL OPERATIONS AUX 21 CHECK PROGRAM
You can also enter the exact AUX number to go straight to the sub-menu. Enter the AUX number directly AUX
2
1
ENT
AUX 2* RLL OPERATIONS AUX 21 CHECK PROGRAM
DL405 User Manual, 4th Edition
Appendix A Auxiliary Functions
Accessing AUX Functions via DirectSOFT
A--3
Page 534
Appendix A Auxiliary Functions
A--4
Auxiliary Functions
AUX 1*, Operating Modes AUX 11 Go to Run Mode
You can use AUX 11 to place the CPU in Run Mode. In Run Mode the CPU executes the program and updates the I/O modules. You can also change the PLC mode from within DirectSOFT by using the PLC/PLC Modes sub-menu.
AUX 12 Go to Test Mode
Test Mode allows the CPU to start in TEST-PGM mode, enter TEST-RUN mode, run a fixed number of scans (from 1 to 65,535), and then return to TEST-PGM mode. You can also change enter TEST Mode from within DirectSOFT by using the PLC > PLC Modes sub-menu. You gain some advantages by using Test Mode. S The status displays are more detailed with the Handheld Programmer. S You can enable the CPU to hold output states. For some instructions, the Handheld Programmer TEST-RUN mode display is more detailed than the status displays shown in RUN mode. The following diagram shows an example of a Timer instruction display during TEST-RUN mode. RUN Mode
$ TMR
TEST-RUN Mode
3 T 000
K0500
$ TMR
3
T=510 T 000 K0500 Current Value
AUX 13 Go to Program Mode AUX 14 Run Time Edit
Use AUX 13 to place the CPU in Program Mode. In PGM mode, you can enter or change the program. The CPU does not execute the program or update the output modules. All output points are turned off. You can also change enter Program Mode from within DirectSOFT by using the PLC > PLC Modes sub-menu. With the DL440 or DL450 CPU you can edit programs during Run Mode and Test-Run Mode with AUX14, or from within DirectSOFT by using the PLC > PLC Modes sub-menu. Most of the things you can do in Program Mode also apply. For example, you can use the same techniques to search for a specific instruction or a specific address. However, you cannot use Search and Replace functions during Run Mode. The Run Mode Edits are not “bumpless.” Instead, the CPU maintains the outputs in their last state while it accepts the new program information. If an error is found in the new program, then the CPU will turn all the outputs off and enter the Program Mode. WARNING: Only authorized personnel fully familiar with all aspects of the application should make changes to the program. Changes during Run Mode become effective immediately. Make sure you thoroughly consider the impact of any changes to minimize the risk of personal injury or damage to equipment. Edits during Run Mode are ideally suited to small changes. For major program changes, we strongly recommended switching the system to program mode, taking the same precautions as if it were the initial machine startup.
DL405 User Manual, 4th Edition
Page 535
Auxilliary Functions
A--5
AUX 21 Check Program
Both the Handheld and DirectSOFT automatically check for errors during program entry. However, there may be occasions when you want to check a program that has already been in the CPU. There are two types of checks available. S Syntax S Duplicate References The Syntax check will find a wide variety of programming errors, such as missing END statements, incomplete FOR/NEXT loops, etc. If you perform this check and get an error, see Appendix B for a complete listing of programming error codes. Correct the problem and then continue running the Syntax check until the message “NO SYNTAX ERROR appears. Use the Duplicate Reference check to verify you have not used the same output coil reference more than once. Note, this AUX function will also find the same outputs even if they have been used with the OROUT instruction, which is perfectly acceptable. This AUX function is available on the PLC > Diagnostics sub-menu from within DirectSOFT.
AUX 22 Change Reference
There will probably be times when you need to change an I/O address reference or control relay reference. AUX 22 allows you to quickly and easily change all occurrences of a specific instruction. For example, you can replace every instance of X5 with X10.
AUX 23 Clear Ladder Range
There have been many times when we’ve taken existing programs and added or removed certain portions to solve new application problems. By using AUX 23 you can select and delete a portion of the program. DirectSOFT does not have a menu option for this AUX function, but you can just select the appropriate portion of the program and cut it with the editing tools.
AUX 24 Clear Ladders
AUX 24 clears the entire program from CPU memory. Before you enter a new program, you should always clear ladder memory. This AUX function is available on the PLC > Clear PLC Memory sub-menu within DirectSOFT.
AUX 25 Select MC or Flash Memory
AUX 25 lets you select either the (optional) Memory Cartridge or the CPU’s built-in flash memory as the current working memory. NOTE: operations such as Clear Ladder Range and Clear Ladders operate on the current selected memory device.
AUX 26 Copy MC Contents to Flash
AUX 26 copies the entire Memory Cartridge contents to the CPU’s built-in flash memory. Any data in the flash memory will be over-written.
AUX 27 Copy Flash Contents to MC
AUX 27 copies the entire CPU’s built-in flash memory contents to the Memory Cartridge memory. Any data in the Memory Cartridge will be over-written.
AUX 28 Verify Flash Contents = MC
AUX 28 verifies that the data in the CPU’s internal flash memory is the same as the Memory Cartridge contents. This is useful when verifying ladder program updates, and generally managing the ladder program during program development.
DL405 User Manual, 4th Edition
Appendix A Auxiliary Functions
AUX 2*, RLL Operations
Page 536
Appendix A Auxiliary Functions
A--6
Auxiliary Functions
AUX 3*, V-memory Operations AUX 31 Clear V--Memory
AUX 31 clears all the information from the V-memory locations available for general use. This AUX function is available on the PLC > Clear PLC Memory sub-menu within DirectSOFT.
AUX 32 Clear V-memory Range
Just as you can use AUX 23 to delete a portion of the control program, you can also use AUX 32 to clear a portion of V--memory. DirectSOFT provides access to this AUX function on the Tools > Memory Editor sub-menu.
AUX 33 Find V-memory Value
AUX 33 allows you to search through a range of V-memory locations to find a specific value. For example, you may want to search a value of 1234 through the range of V1400 -- V2000. This feature is also available within DirectSOFT via the Tools > Memory Editor sub-menu.
AUX 4*, I/O Configuration AUX 41 Show I/O Configuration
This AUX function allows you to display the current I/O configuration. With the Handheld Programmer, you can scroll through each base and I/O slot to view the complete configuration. The configuration shows the type of module installed in each slot. DirectSOFT provides the same information, but it is much easier to view because you can view a complete base on one screen.
AUX 42 I/O Diagnostics
This is probably one of the most useful AUX function available in the DL405 system. This AUX function will show you the exact base and slot location of any I/O module error that has occurred. This feature is also available within DirectSOFT under the PLC > Diagnostics sub-menu.
AUX 44 Power-up Configuration Check
By selecting this feature you can quickly detect any changes that may have occurred while the power was disconnected. For example, if someone placed an output module in a slot that previously held an input module, the configuration check would detect the change. If the system detects a change in the I/O configuration at power-up, an error code E252 NEW I/O CONFIGURATION will be generated. You can use AUX 42 to determine the exact base and slot location where the change occurred. WARNING: You should always correct any I/O configuration errors before you place the CPU into RUN mode. Uncorrected errors can cause unpredictable machine operation that can result in a risk of personal injury or damage to equipment. This feature is also available within DirectSOFT under the PLC > Setup sub-menu.
DL405 User Manual, 4th Edition
Page 537
Auxilliary Functions
Even though the CPU can automatically detect configuration changes, you may actually want the new I/O configuration to be used. For example, you may have intentionally changed a module to use with a new program. You can use AUX 45 to select the new configuration, or, keep the existing configuration that is stored in memory. This feature is also available within DirectSOFT from the PLC > Setup sub-menu. WARNING: Make sure the I/O configuration being selected will work properly with the CPU program. You should always correct any I/O configuration errors before you place the CPU into RUN mode. Uncorrected errors can cause unpredictable machine operation that can result in a risk of personal injury or damage to equipment.
AUX 46 I/O Configuration
You will probably never need to use this feature, but the DL440 CPU allows you to use AUX 46 to manually assign I/O addresses for any or all I/O slots on the local or expansion bases. It is generally much easier to do the I/O configuration operations from within DirectSOFT. The software package provides a really nice screen that is available from the PLC > Configure I/O sub-menu. This feature is useful if you have a standard configuration you must sometimes change slightly to accommodate special requests. For example, you may require two adjacent input modules to have addresses starting at X10 and X200 respectively. In automatic configuration, the addresses were assigned on 8-point boundaries. Manual configuration assumes that all modules are at least 16 points, so you can only assign addresses that are a multiple of 20 (octal). For example, X30 and Y50 would not be valid starting addresses for a module. X20 and Y40 are valid examples of starting addresses in a manual configuration. This does not mean you can only use 16 or 32 point modules with manual configuration. You can use 8 point modules, but 16 addresses will be assigned and 8 of them are unused. WARNING: If you manually configure an I/O slot, the I/O addressing for the other modules will change. This is because the DL405 products do not allow you to assign duplicate I/O addresses. You should always correct any I/O configuration errors before you place the CPU into RUN mode. Uncorrected errors can cause unpredictable machine operation that can result in a risk of personal injury or damage to equipment. Once you have manually configured the addresses for an I/O slot, the system will automatically retain these values even after a power cycle. You can remove any manual configuration changes by simply performing an automatic configuration.
AUX 47 Intelligent I/O Monitor
This AUX function allows you to monitor the shared RAM data that is associated with many specialty I/O modules. For example, you could use this AUX function to monitor the data accessed by shared RAM in the High Speed Counter. DirectSOFT provides this capability through the PLC > Setup Global I/O sub-menu.
DL405 User Manual, 4th Edition
Appendix A Auxiliary Functions
AUX 45 Select Configuration
A--7
Page 538
Appendix A Auxiliary Functions
A--8
Auxiliary Functions
AUX 5*, CPU Configuration AUX 51 Modify Program Name
The DL405 products can use program names for memory cartridges or cassette tapes. Program names are especially useful with cassette tapes since they can store multiple programs. The program name can be up to eight characters in length and can use any of the available characters (A--Z, 0--9). AUX 51 allows you to enter a program name. You can also perform this operation from within DirectSOFT by using the PLC > Setup sub-menu.
AUX 52 Display /Change Calendar
The DL440 CPU has a clock and calendar feature. If you are using this, you can use the Handheld and AUX 52 to set the time and date. The following format is used. S Date, Year, Month, Date, Day of week (0 -- 6, Sunday thru Saturday) S Time, 24 hour format, Hours, Minutes, Seconds You can use the AUX function to change any component of the date or time. However, the CPU will not automatically correct any discrepancy between the date and the day of the week. For example, if you change the date to the 15th of the month and the 15th is on a Thursday, you will also have to change the day of the week (unless the CPU already shows the date as Thursday). You can also perform this operation from within DirectSOFT by using the PLC > Setup sub-menu.
AUX 53 Display Scan Time AUX 54 Initialize Scratchpad
AUX 53 displays the current, minimum, and maximum scan times. The minimum and maximum times are the ones that have occurred since the last Program Mode to Run Mode transition. You can also perform this operation from within DirectSOFT by using the PLC > Diagnostics sub-menu. The DL405 CPUs maintain system parameters in a memory area often referred to as the “scratchpad”. In some cases, you may make changes to the system setup that will be stored in system memory. For example, if you specify a range of Control Relays (CRs) as retentive, these changes are stored. NOTE: You may never have to use this feature unless you have made changes that affect system memory. Usually, you’ll only need to initialize the system memory if you are changing programs and the old program required a special system setup. You can usually change from program to program without ever initializing system memory. AUX 54 resets the system memory to the default values. You can also perform this operation from within DirectSOFT by using the PLC > Setup sub-menu.
AUX 55 Set Watchdog Timer
The DL405 CPUs have a “watchdog” timer that is used to monitor the scan time. The default value set from the factory is 200 ms. If the scan time exceeds the watchdog time limit, the CPU automatically leaves RUN mode and enters PGM mode. The Handheld displays the following message E003 S/W TIMEOUT when the scan overrun occurs. Use AUX 55 to increase or decrease the watchdog timer value. You can also perform this operation from within DirectSOFT by using the PLC > Setup sub-menu.
DL405 User Manual, 4th Edition
Page 539
Auxilliary Functions
Since the DL405 CPUs have built-in DirectNET ports, you can use the Handheld to set the network address for the port and the port communication parameters. The default settings are: S Station address 1 S Hex mode S Odd parity The DirectNET Manual provides additional information about communication settings required for network operation. NOTE: You will only need to use this procedure if you have the bottom port connected to a network. Otherwise, the default settings will work just fine. Use AUX 56 to set the network address and communication parameters. You can also perform this operation with DirectSOFT by using the PLC > Setup sub-menu.
AUX 57 Set Retentive Ranges
Memory Area
The DL405 CPUs provide certain ranges of retentive memory by default. The default ranges are suitable for many applications, but you can change them if your application requires additional retentive ranges or no retentive ranges at all. The default settings are: DL430
DL440
DL450
Default Range
Avail. Range
Default Range
Control Relays
C600 -- C737
C0 -- C737
C600 -- C737
V--Memory
V2000 -- V7377
V0 -- V7377
V2000 -- V7777
Timers
None by default T0 -- T177
None by default T0 -- T377
None by default
T0 -- T377
Counters
CT0 -- CT177
CT0 -- CT177
CT0 -- CT377
CT0 -- CT377
Stages
None by default S0 -- S577
None by default
S0 -- S1777
CT0 -- CT177
Avail. Range
Default Range
Avail. Range
C0 -- C1777
C1000 -- C3777
C0 -- C3777
V0 -- V17777
V1400 -- V37777 V0 -- V37777
CT0 -- CT177
None by default S0 -- S1777
Use AUX 57 to change the retentive ranges. You can also perform this operation from within DirectSOFT by using the PLC > Setup sub-menu. AUX 58 Test Operations
In normal RUN mode, the outputs are turned off when you return to PGM mode. In TEST-RUN mode you can set each individual output to either turn off or hold its last output state on the transition to TEST-PGM mode. The ability to hold the output states is especially useful, since It allows you to maintain key system I/O points for examination. The following diagram shows the differences between RUN and TEST-RUN modes. You can use AUX 58 to configure each individual output. You can also perform this operation from within DirectSOFT by using the PLC > Setup sub-menu.
AUX 5C Display Error History
The DL440 and DL450 CPUs will automatically log any system error codes and custom messages created with the FAULT instructions. The CPU logs the error code, date, and time the error occurred in two separate tables: S Error Code Table -- the system logs up to 32 errors in the table. When an error occurs, the errors already on the table are pushed down and the most recent error is loaded into the top slot. If the table is full when an error occurs, the oldest error is pushed out (erased) of the table.
DL405 User Manual, 4th Edition
Appendix A Auxiliary Functions
AUX 56 CPU Network Address
A--9
Page 540
A--10
Auxiliary Functions
Appendix A Auxiliary Functions
S
Message Table -- the system logs up to 16 messages in this table. When a message is triggered, the messages already stored in the table are pushed down and the most recent message is loaded into the top slot. If the table is full when an error occurs, the oldest message is pushed out (erased) of the table. Example messages below. Date
Time
Message
1993--05--26
08:41:51:11
* Conveyor--2 stopped
1993--04--30
17:01:11:56
* Conveyor--1 stopped
1993--04--30
17:01:11:12
* Limit SW1 failed
1993--04--28
03:25:14:31
* Saw Jam Detect
You can use AUX Function 5C to show the error codes or messages You can also view the errors and messages from within DirectSOFT by using the PLC > Diagnostics sub-menu. AUX 5D Select PLC Scan Mode
The DL450 CPU has two program scan modes: fixed and variable. In fixed mode, the scan time is lengthened to the time you specify (in milliseconds). In variable scan mode, the CPU begins each scan as soon as the previous scan’s activities complete.
AUX 6*, Handheld Programmer Configuration AUX 61 Show Revision Numbers
Over the years there have been several additions and enhancements made to the products that are compatible with the DL405 family. Sometimes these new features only work with certain releases of firmware. By using AUX 61 you can quickly view the CPU, Gate Array, and Handheld Programmer firmware revision numbers. This information is also available from within DirectSOFT from the PLC > Diagnostics sub-menu.
AUX 62 Beeper On / Off
The Handheld has a beeper that provides confirmation of keystrokes. This can be quite annoying in an office environment. You can use Auxiliary (AUX) Function 62 to turn off the beeper.
AUX 63 Turning Off the Backlight
If necessary, you can use AUX 63 to turn off the display backlight. However, in most cases it seems to be easier to read if you just leave the display backlight enabled.
AUX 64 Select Online / Offline
You can use AUX 64 to take the Handheld Programmer offline. That is, the Handheld will not communicate with the CPU until it is returned to online operation. For example, if you have selected offline you cannot access the CPU.
AUX 65 Run Self Diagnostics
If you think the Handheld Programmer is not operating correctly, you can use AUX 65 to run a self diagnostics program. You can check the following items. S Keypad S Display S LEDs and Backlight S Tape Port (requires adapter) S Memory Cartridge
DL405 User Manual, 4th Edition
Page 541
Auxilliary Functions
A--11
Transferrable Memory Areas
Many of these AUX functions allow you to copy different areas of memory to and from the CPU, memory cartridge, and cassette tapes. The following table shows the areas that may be mentioned. Option and Memory Type
DL440 Range
DL430 Range
1:PGM, Program
$00000 -- $07679 (7.5K program memory) $00000 -- $015871 (15.5K program memory)
$00000 -- $03583
2:V, V--memory
$00000 -- $37777
$00000 -- $07777
3:SYS, System memory
Non-selectable copies all system parameters
AUX 71 CPU to Memory Cartridge
AUX 71 copies information from a CPU to a memory cartridge that is installed in the Handheld Programmer. If a memory cartridge is not present in the Handheld, you can just remove the memory cartridge from the CPU and place it in the Handheld, but if you want to keep the CPU that is already installed up and running you should use this AUX function to copy the CPU memory. You can copy different portions of CPU memory to the memory cartridge as shown in the previous table.A single memory cartridge cannot hold an entire system. You may have to use more than one cartridge. If so, put V memory on a cartridge by itself.
AUX 72 Memory Cartridge to CPU
AUX 72 copies information from a memory cartridge installed in the Handheld Programmer to the CPU. If a memory cartridge is not present in the CPU, you can just remove the memory cartridge from the Handheld and place it in the CPU.You can copy different information types from the memory cartridge as shown in the previous table.
AUX 73 Compare Memory Cartridge to CPU
AUX 73 compares the Handheld memory cartridge program with the CPU program.You can compare different types of information as shown previously.
AUX 74 Memory Cartridge Blank Check AUX 75 Clear Memory Cartridge
AUX 74 allows you to check the memory cartridge to make sure it is blank. It’s a good idea to use this function anytime you start to copy information to a memory cartridge.
AUX 76 Display Memory Cartridge Type
You can use AUX 76 to quickly display the type of memory cartridge that is installed in both the CPU and the Handheld Programmer. Remember, there are three types of memory cartridges, CMOS RAM, EEPROM, and UVPROM.
AUX 77 Tape to Memory Cartridge
Use AUX 77 to read a program from a cassette tape. Before you begin the procedure make sure you review the procedures identified in the DL405 Handheld Programmer manual. These procedures are important to help ensure a successful transfer of information.
AUX 75 allows you to clear all data from a memory cartridge. This is true for the RAM and EEPROM memory cartridges. The UVPROM cartridges must be erased with a UV light source.
DL405 User Manual, 4th Edition
Appendix A Auxiliary Functions
AUX 7*, Memory Cartridge Operations
Page 542
Appendix A Auxiliary Functions
A--12
Auxiliary Functions
AUX 78 Memory Cartridge to Tape
Since it is very easy to store multiple programs on a single cassette it is very important idea to name each program. You already know you can enter a name for the CPU program. The cassette program name does not have to be the same. For example, the CPU name may be PRESS1 and the tape name may be STATION1. Since there are three areas of CPU memory that can be transferred, it is a good idea to give each of these a separate program name. For example, you could use three programs, STAT1PGM, STAT1V, and STAT1SYS, for Station 1. NOTE: Remember tape programs are stored sequentially. It is very easy to overwrite existing programs if you do not position the tape correctly. Make sure you review the procedures identified in the DL405 Handheld Programmer manual before beginning this procedure.
AUX 79 Compare Memory Cartridge to Tape
Use AUX 79 to compare a cassette program to a program stored in the CPU. Make sure you review the procedures identified in the DL405 Handheld Programmer manual before beginning this procedure.
AUX 8*, Password Operations AUX 81 Modify Password
You can use AUX 81 with the DL440 or DL450 CPU to provide an extra measure of protection by entering a password that prevents unauthorized machine operations. The password must be an eight-character numeric (0--9) code. Once you’ve entered a password, you can remove it by entering all zeros (00000000). (This is the default from the factory.) NOTE: The 440 and 450 CPUs support multi-level passwords. This allows password protection of the ladder program while not locking the communication port to operator interfaces. The multi-level password can be invoked by making a password with an upper case “A” followed by 7 numeric characters (e.g. A12345678). The password is stored in the memory cartridge. If you install the memory cartridge in another CPU or Handheld, the password protection remains in effect. Once you’ve entered a password, you can lock the CPU against access. There are two ways to lock the CPU with the Handheld Programmer. S The CPU is always locked after a power cycle (if a password is present). S You can use AUX 83 and AUX 84 to lock and unlock the CPU. You can also enter or modify a password from within DirectSOFT by using the PLC > Password sub-menu. This feature works slightly differently in DirectSOFT. Once you’ve entered a password, the CPU is automatically locked when you exit the software package. It will also be locked if the CPU is power cycled. WARNING: Make sure you remember the password before you lock the CPU. Once the CPU is locked you cannot view, change, or erase the password. You also cannot erase the memory cartridge and start over. You can have the password removed by returning the CPU or memory cartridge to the factory for password removal. It is the policy of AutomationDirect to clear the PLC memory along with the password, so be sure to have a copy of the program to reload into the CPU memory once the CPU or memory cartridge has been returned.
DL405 User Manual, 4th Edition
Page 543
Auxilliary Functions AUX 82 Unlock CPU AUX 83 Lock CPU
A--13
AUX 82 can be used to unlock a CPU that has been password protected. DirectSOFT will automatically ask you to enter the password if you attempt to communicate with a CPU that contains a password. AUX 83 can be used to lock a CPU that contains a password. Once the CPU is locked, you will have to enter a password to gain access. Remember, this is not necessary with DirectSOFT since the CPU is automatically locked whenever you exit the software package.
DL405 User Manual, 4th Edition