DL405 User Manual: Appendix D: Special Relays

Pages 575 to 578 of 608, from DL405 User Manual

The original document is the PDF (8.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect D4-08B-1, AutomationDirect D4-08ND3S, AutomationDirect D4-16TA, PLC Direct D4-16TD2, AutomationDirect D4-32ND3-1, Konnect-It D4-08B-1, Koyo D4-08B-1, Konnect-It D4-08ND3S, and 6 more models

Page 575

Special Relays

In This Appendix. . . ., Startup and Real-time Special Relays, CPU Status Relays, System Monitoring Relays, Accumulator Status Relays, Communication Monitoring Relays

1D

Page 576

AppendixDD Appendix DL405 Special Relays Special Relays

Appendix C Special Relays

Appendix B DL405 Error Codes

Appendix A DL405 Error Codes

D--2

Special Relays

Startup and Real-time Special Relays First scan on for the first scan after a power cycle or program to run transition, and is reset to off on the second scan. It is useful when a function needs to be performed only at startup.

SP1

Always ON provides a contact to insure a instruction is executed every scan.

SP2

Always OFF provides a contact that is always off.

SP3

1 minute on for 30 seconds and off for 30 seconds.

SP4

1 second on for 0.5 second and off for 0.5 second.

SP5

100 millisecond on for 50 ms. and off for 50 ms.

SP6

50 millisecond on for 25 ms. and off for 25 ms.

SP7

Alternate scan on every other scan.

SP0

CPU Status Relays SP11

Forced run mode on anytime the CPU keyswitch is in the RUN position.

SP12

Terminal run mode on when the CPU keyswitch is in the TERM position and the CPU is in the run mode.

SP13

Test run mode on when the CPU is in the test run mode.

SP14

Break relay 1 on when the BREAK instruction is executed. It is off when the CPU is in any other mode.

SP15

Test program mode on when the CPU is in the test program mode.

SP16

Terminal PGM mode on when the CPU keyswitch is in the TERM position and the CPU is in program mode.

SP17

Forced stop mode on anytime the CPU keyswitch is in the STOP position.

Break relay 2 on when the BREAK instruction is executed. It is off only when the CPU mode is changed to RUN.

SP22

Interrupt enabled on when hardware interrupts are enabled using the ENI instruction.

SP25

CPU battery disabled on when the CPU battery is disabled by dipswitch 1 on the rear of the CPU.

SP26

I/O update disable

(DL440/DL450) turned on by the application program, thus freezing the state of the I/O.

SP27

Selective I/O update disable

(DL440/DL450) relay can be turned on by the application program. If turned on the I/O update is frozen at last state, for I/O modules sensing a missing terminal block .

SP30

Dipswitch 1 status

(DL430/DL440) follows the On/Off status of dipswitch 1 on the rear of the CPU.

SP31

Dipswitch 2 status

(DL430/DL440) follows the On/Off status of dipswitch 2 on the rear of the CPU.

SP32

Dipswitch 3 status

(DL430/DL440) follows the On/Off status of dipswitch 3 on the rear of the CPU.

SP33

Dipswitch 4 status

(DL430/DL440) follows the On/Off status of dipswitch 4 on the rear of the CPU.

Scan control error

(DL450) this relay will be on if the actual scan time is in excess of the scan time set in fixed or limit scan modes. The relay contact may be useful in program error recovery.

SP21

SP37

DL405 User Manual, 4th Edition

Page 577

Special Relays

D--3 on when a critical error such as I/O communication loss has occurred.

SP41

Warning on when a non critical error such as a low battery has occurred.

SP43

Battery low (440/450)

on when either the memory cartridge battery or the CPU battery is low. Once detected, check V7757 for the exact error code.

SP44

Program memory error on when a memory error such as a memory parity error or a failed memory cartridge has occurred.

SP45

I/O error on when a I/O error such as blown fuse or 24V bad has occurred.

SP46

Communications error on when a communications error has occurred on any of the CPU ports.

I/O configuration error on if a I/O configuration error has occurred. The I/O configuration check must be set on in the CPU before this relay will be functional.

SP50

FAULT instruction on when a FAULT Instruction is executed.

SP51

Math timeout relay on if the CPU time out on a math function.

Grammatical error on if a grammatical error has occurred either while the CPU is running or if the syntax check is run. Once detected check V7755 for a exact error code.

SP53

Math/Table pointer on if there is math execution error or a table pointer error.

SP54

Communication error on when RX, WX, RD, WT instructions are executed with the wrong parameters.

SP56

Table instruction overrun on if a table instruction with a pointer is executed and the pointer value is outside the table boundary.

SP47

SP52

Accumulator Status Relays Math/Table pointer error on if there is math execution error or a table pointer error.

SP60

Value less than on when the value in the accumulator is less than the instruction value.

SP61

Value equal to on when the value in the accumulator is equal to the instruction value.

SP62

Value greater than on when the value in the accumulator is greater than the instruction value.

SP63

Zero on when the result of the instruction causes the value in the accumulator to be zero.

SP64

Half borrow on when the 16 bit subtraction instruction results in a borrow.

SP65

Borrow on when the 32 bit subtraction instruction results in a borrow.

SP66

Half carry on when the 16 bit addition instruction results in a carry.

SP67

Carry when the 32 bit addition instruction results in a carry.

SP70

Sign (negative)

on anytime the value in the accumulator is negative.

SP71

Pointer reference error on when the V-memory specified by a pointer (P) is not valid.

SP72

Floating point

(DL450) on when the numerical value in the accumulator is a floating point number.

SP73

Overflow on when a signed addition or subtraction results in an incorrect sign bit.

SP74

Under flow

(DL450) on when a floating point math operation results in an underflow error.

SP75

Data error on when a BCD instruction is executed and a NON--BCD number was encountered.

SP76

Load zero on when the value loaded into the accumulator by any instruction is zero.

DL405 User Manual, 4th Edition

Appendix AppendixDD DL405 Special Relays Special Relays

SP53

Appendix C Special Relays

Critical error

Appendix B DL405 Error Codes

SP40

Appendix A DL405 Error Codes

System Monitoring Relays

Page 578

AppendixDD Appendix DL405 Special Relays Special Relays

Appendix C Special Relays

Appendix B DL405 Error Codes

Appendix A DL405 Error Codes

D--4

Special Relays

Communication Monitoring Relays The Communications Monitoring Relays are numbered in pairs corresponding to CPU port numbers or slot positions in a base. The two relay types are: S Module/port busy -- on when the port or the communication module in the referenced slot and base is busy transmitting or receiving. You must use this relay with RX and WX instructions to prevent attempting to execute a RX or WX while the module is busy. S Communication error -- on when a communications error occurs. This error automatically clears when another RX or WX instruction executes. DL450 CPU only All DL405 CPUs

Local Base

SP112

CPU port busy Port 1

SP114

CPU port busy Port 2

SP116

CPU port busy Port 3

SP113

Comm error Port 1

SP115

Comm error Port 2

SP117

Comm error Port 3

Expansion Base #1

Expansion Base #2

Expansion Base #3

SP120

Module busy Slot 0

SP140

Module busy Slot 0

SP160

Module busy Slot 0

SP200

Module busy Slot 0

SP121

Comm error Slot 0

SP141

Comm error Slot 0

SP161

Comm error Slot 0

SP201

Comm error Slot 0

SP122

Module busy Slot 1

SP142

Module busy Slot 1

SP162

Module busy Slot 1

SP202

Module busy Slot 1

SP123

Comm error Slot 1

SP143

Comm error Slot 1

SP163

Comm error Slot 1

SP203

Comm error Slot 1

SP124

Module busy Slot 2

SP144

Module busy Slot 2

SP164

Module busy Slot 2

SP204

Module busy Slot 2

SP125

Comm error Slot 2

SP145

Comm error Slot 2

SP165

Comm error Slot 2

SP205

Comm error Slot 2

SP126

Module busy Slot 3

SP146

Module busy Slot 3

SP166

Module busy Slot 3

SP206

Module busy Slot 3

SP127

Comm error Slot 3

SP147

Comm error Slot 3

SP167

Comm error Slot 3

SP207

Comm error Slot 3

SP130

Module busy Slot 4

SP150

Module busy Slot 4

SP170

Module busy Slot 4

SP210

Module busy Slot 4

SP131

Comm error Slot 4

SP151

Comm error Slot 4

SP171

Comm error Slot 4

SP211

Comm error Slot 4

SP132

Module busy Slot 5

SP152

Module busy Slot 5

SP172

Module busy Slot 5

SP212

Module busy Slot 5

SP133

Comm error Slot 5

SP153

Comm error Slot 5

SP173

Comm error Slot 5

SP213

Comm error Slot 5

SP134

Module busy Slot 6

SP154

Module busy Slot 6

SP174

Module busy Slot 6

SP214

Module busy Slot 6

SP135

Comm error Slot 6

SP155

Comm error Slot 6

SP175

Comm error Slot 6

SP215

Comm error Slot 6

SP136 SP137

Module busy Slot 7 Comm error Slot 7

DL405 User Manual, 4th Edition

SP156 SP157

Module busy Slot 7 Comm error Slot 7

SP176 SP177

Module busy Slot 7 Comm error Slot 7

SP216 SP217

Module busy Slot 7 Comm error Slot 7