Page 110
Chapter 3: CPU Specifications and Operation
Input Points (X Data Type)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 3–26
The discrete input points are noted by an X data type. There are 20 discrete input points and 256 discrete input addresses available with DL06 CPUs. In this example, the output point Y0 will be turned on when input X0 energizes.
X0
Y0 OUT
X1
Y1 OUT
X6
C5 OUT
C5
Y10 OUT
Output Points (Y Data Type) The discrete output points are noted by a Y data type. There are 16 discrete outputs and 256 discrete output addresses available with DL06 CPUs. In this example, output point Y1 will be turned on when input X1 energizes.
Control Relays (C Data Type) Control relays are discrete bits normally used to control the user program. The control relays do not represent a real world device, that is, they cannot be physically tied to switches, output coils, etc. There are 1024 control relays internal to the CPU. Because of this, control relays can be programmed as discrete inputs or discrete outputs. These locations are used in programming the discrete memory locations (C) or the corresponding word location which contains 16 consecutive discrete locations. In this example, memory location C5 will energize when input X6 turns on. The second rung shows a simple example of how to use a control relay as an input.
Y20 OUT
Timers and Timer Status Bits (T Data Type) There are 256 timers available in the CPU. Timer status bits reflect the relationship between the current value and the preset value of a specified timer. The timer status bit will be on when the current value is equal or greater than the preset value of a corresponding timer. When input X0 turns on, timer T1 will start. When the timer reaches the preset of 3 seconds (K of 30) timer status contact T1 turns on. When T1 turns on, output Y12 turns on. Turning off X0 resets the timer.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
X0
TMR
T1 K30
T1
Y12 OUT
Page 111
Chapter 3: CPU Specifications and Operation
Timer Current Values (V Data Type) As mentioned earlier, some information is automatically stored in V-memory. This is true for the current values associated with timers. For example, V0 holds the current value for Timer 0, V1 holds the current value for Timer 1, etc. These can also be designated as TA0 (Timer Accumulated) for Timer 0, and TA1 for Timer 1. The primary reason for this is programming flexibility. The example shows how you can use relational contacts to monitor several time intervals from a single timer.
Counters and Counter Status Bits (CT Data type) There are 128 counters available in the CPU. Counter status bits that reflect the relationship between the current value and the preset value of a specified counter. The counter status bit will be on when the current value is equal to or greater than the preset value of a corresponding counter. Each time contact X0 transitions from off to on, the counter increments by one. (If X1 comes on, the counter is reset to zero.) When the counter reaches the preset of 10 counts (K of 10) counter status contact CT3 turns on. When CT3 turns on, output Y2 turns on.
X0
TMR T1 K1000
V1
K30
Y2 OUT
V1
K50
Y3 OUT
V1
K75
V1
X0
Y4 OUT
CNT
CT3 K10
X1
Y2 OUT
CT3
X0
CNT
Counter Current Values (V Data Type) Just like the timers, the counter current values are also automatically stored in V-memory. For example, V1000 holds the current value for Counter CT0, V1001 holds the current value for Counter CT1, etc. These can also be designated as CTA0 (Counter Accumulated) for Counter 0 and CTA01 for Counter 1. The primary reason for this is programming flexibility. The example shows how you can use relational contacts to monitor the counter values.
K100
CT3 K10
X1
V1003
K1
Y2 OUT
V1003
K3
Y3 OUT
V1003
K5
V1003
K8
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Y4 OUT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
3–27
Page 112
Chapter 3: CPU Specifications and Operation
Word Memory (V Data Type)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 3–28
Word memory is referred to as V-memory (variable) and is a 16-bit location normally used to manipulate data/numbers, store data/numbers, etc. Some information is automatically stored in V-memory. For example, the timer current values are stored in V-memory. The example shows how a four-digit BCD constant is loaded into the accumulator and then stored in a V-memory location.
X0
LD K1345
OUT
V2000
Stages (S Data type) Stages are used in RLLPLUS programs to create a structured program, similar to a flowchart. Each program Stage denotes a program segment. When the program segment, or Stage, is active, the logic within that segment is executed. If the Stage is off, or inactive, the logic is not executed and the CPU skips to the next active Stage. (See Chapter 7 for a more detailed description of RLLPLUS programming.) Each Stage also has a discrete status bit that can be used as an input to indicate whether the Stage is active or inactive. If the Stage is active, then the status bit is on. If the Stage is inactive, then the status bit is off. This status bit can also be turned on or off by other instructions, such as the SET or RESET instructions. This allows you to easily control stages throughout the program.
Word Locations – 16 bits 0 0 0 1 00 1 1 0 1 0 0 0 1 0 1 1
3
4
5
Ladder Representation ISG
Wait for Start
S0000 Start
S1 JMP
X0 S500 JMP SG
Check for a Part
S0001
Part Present
S2 JMP
X1 Part Present
S6 JMP
X1
Special Relays (SP Data Type) Special relays are discrete memory locations with predefined functionality. There are many different types of special relays. For example, some aid in program development, others provide system operating status information, etc. Appendix D provides a complete listing of the special relays. In this example, control relay C10 will energize for 50 ms and de-energize for 50 ms because SP5 is a pre–defined relay that will be on for 50 ms and off for 50 ms.
SG
Clamp the part
S0002
Clamp SET S400 S3 JMP
Part Locked X2
SP5
C10 OUT
SP4: 1 second clock SP5: 100 ms clock SP6: 50 ms clock
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 113
Chapter 3: CPU Specifications and Operation
DL06 System V-memory System Parameters and Default Data Locations (V Data Type) The DL06 PLCs reserve several V-memory locations for storing system parameters or certain types of system data. These memory locations store things like the error codes, High-Speed I/O data, and other types of system setup information. System V-memory V700-V707 V710-V717 V720-V727 V730-V737 V3630–V3707 V3710-V3767 V7620–V7627 V7620 V7621 V7622 V7623 V7624 V7625 V7626 V7627 V7630
V7631 V7632
Description of Contents Sets the V-memory location for option card in slot 1 Sets the V-memory location for option card in slot 2 Sets the V-memory location for option card in slot 3 Sets the V-memory location for option card in slot 4 The default location for multiple preset values for UP/DWN and UP Counter 1 or pulse catch function The default location for multiple preset values for UP/DWN and UP Counter 2 Locations for DV–1000 operator interface parameters Sets the V-memory location that contains the value Sets the V-memory location that contains the message Sets the total number (1 – 32) of V-memory locations to be displayed Sets the V-memory location containing the numbers to be displayed Sets the V-memory location that contains the character code to be displayed Contains the function number that can be assigned to each key Powerup operational mode Change preset value Starting location for the multi–step presets for channel 1. The default value is 3630, which indicates the first value should be obtained from V3630. Since there are 24 presets available, the default range is V3630 – V3707. You can change the starting point if necessary. Starting location for the multi–step presets for channel 2. The default value is 3710, which indicates the first value should be obtained from V3710. Since there are 24 presets available, the default range is V3710 – V3767. You can change the starting point if necessary. Setup Register for Pulse Output
V7633
Sets the desired function code for the high speed counter, interrupt, pulse catch, pulse train, and input filter. This location can also be used to set the power-up in Run Mode option.
V7634 V7635 V7636 V7637
X0 Setup Register for High-Speed I/O functions for input X0 X1 Setup Register for High-Speed I/O functions for input X1 X2 Setup Register for High-Speed I/O functions for input X2 X3 Setup Register for High-Speed I/O functions for input X3
Default Values / Ranges N/A N/A N/A N/A N/A N/A V0 – V3760 V0 – V3760 1 - 32 V0 – V3760 V0 – V3760 V-memory for X, Y, or C 0,1, 2, 3, 12 0000 to 9999 Default: V3630 Range: V0- V3710 Default: V3710 Range: V0- V3710 N/A Default: 0060 Lower Byte Range:Range: 10 – Counter 20 – Quadrature 30 – Pulse Out 40 – Interrupt 50 – Pulse Catch 60 – Filtered discrete In. Upper Byte Range:Bits 8–11, 14, 15: Unused, Bit 13: Power–up in RUN,only if Mode Switch is inTERM position. Bit 12 is used to enable the low battery indications. Default: 1006 Default: 1006 Default: 1006 Default: 1006
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
3–29
Page 114
Chapter 3: CPU Specifications and Operation
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
System V-memory
Description of Contents
Default Values / Ranges V1200 - V7377 V10000 - v17777 1-8
V7640
PID Loop table beginning address
V7641 V7642 V7643-V7647
Number of PID loops Error Code - V-memory Error location for Loop Table Reserved
V7650
Port 2: Setup for V-memory address for Non-Sequence protocol
V7653 V7655 V7656 V7657 V7660
Port 2: Setup for terminate code for Non-Sequence protocol Port 2: Setup for the protocol, time-out, and the response delay time Port 2: Setup for the station number, baud rate, STOP bit, and parity Port 2: Setup completion code used to notify the completion of the parameter setup 0400h reset port 2 Scan control setup: Keeps the scan control mode Setup timer over counter: Counts the times the actual scan time exceeds the user setup time Reserved Locations for DV–1000 operator interface parameters Titled Timer preset value pointer Titled Counter preset value pointer HiByte-Titled Timer preset block size, LoByte-Titled Counter preset block size Reserved Port 1 and Port 2: Communication Auto Reset Timer Setup Default: 3030 Reserved Location contains a 10 ms counter (0-99). This location increments once every 10 ms Reserved Fault Message Error Code, stores the 4-digit code used with the FAULT instruction when the instruction is executed I/O Configuration Error: Current ID code of error slot I/O Configuration Error: Old ID code of error slot I/O Configuration Error: error slot number Error code, stores the fatal error code Error code, stores the major error code Error code, stores the minor error code Reserved Program address where syntax error exists Syntax error code Scan counter, stores the total number of scan cycles that have occurred since the last Program Mode to Run Mode transition (in decimal) Contains the number of seconds on the clock (00-59) Contains the number of minutes on the clock (00-59) Contains the number of hours on the clock (00-23) Contains the day of the week (Mon., Tues., Wed., etc.) Contains the day of the month (01, 02, etc.) Contains the month (01 to 12) Contains the year (00 to 99) Scan, stores the current scan time (milliseconds) Scan, stores the minimum scan time that has occurred since the last Program Mode to Run Mode transition (milliseconds) Scan, stores the maximum scan rate since the last power cycle (milliseconds)
V7661 V7662–V7717 V7720–V7722 V7720 V7721 V7722 V7723–V7737 V7740 V7741–V7746 V7747 V7750 V7751 V7752 V7753 V7754 V7755 V7756 V7757 V7760–V7762 V7763 V7764 V7765 V7766 V7767 V7770 V7771 V7772 V7773 V7774 V7775 V7776 V7777
3–30
DL06 Micro PLC User Manual, 3rd Edition Rev. A
V1200 – V7377 V10000 - V17777
Page 115
Chapter 3: CPU Specifications and Operation
DL06 Aliases An alias is an alternate way of referring to certain memory types, such as timer/counter current values, V-memory locations for I/O points, etc., which simplifies understanding the memory address. The use of the alias is optional, but some users may find the alias to be helpful when developing a program. The table below shows how the aliases can be used.
DL06 Aliases Address Start
Alias Start
Example
V0
TA0
V1000
CTA0
V40000
VGX
V40200
VGY
V40400
VX0
V40500
VY0
V40600
VC0
V41000
VS0
V41100
VT0
V41140
VCT0
V41200
VSP0
V0 is the timer accumulator value for timer 0, therefore, it’s alias is TA0. TA1 is the alias for V1, etc.. V1000 is the counter accumulator value for counter 0, therefore, it’s alias is CTA0. CTA1 is the alias for V1001, etc. V40000 is the word memory reference for discrete bits GX0 through GX17, therefore, it’s alias is VGX0. V40001 is the word memory reference for discrete bits GX20 through GX 37, therefore, it’s alias is VGX20. V40200 is the word memory reference for discrete bits GY0 through GY17, therefore, it’s alias is VGY0. V40201 is the word memory reference for discrete bits GY20 through GY 37, therefore, it’s alias is VGY20. V40400 is the word memory reference for discrete bits X0 through X17, therefore, it’s alias is VX0. V40401 is the word memory reference for discrete bits X20 through X37, therefore, it’s alias is VX20. V40500 is the word memory reference for discrete bits Y0 through Y17, therefore, it’s alias is VY0. V40501 is the word memory reference for discrete bits Y20 through Y37, therefore, it’s alias is VY20. V40600 is the word memory reference for discrete bits C0 through C17, therefore, it’s alias is VC0. V40601 is the word memory reference for discrete bits C20 through C37, therefore, it’s alias is VC20. V41000 is the word memory reference for discrete bits S0 through S17, therefore, it’s alias is VS0. V41001 is the word memory reference for discrete bits S20 through S37, therefore, it’s alias is VS20. V41100 is the word memory reference for discrete bits T0 through T17, therefore, it’s alias is VT0. V41101 is the word memory reference for discrete bits T20 through T37, therefore, it’s alias is VT20. V41140 is the word memory reference for discrete bits CT0 through CT17, therefore, it’s alias is VCT0. V41141 is the word memory reference for discrete bits CT20 through CT37, therefore, it’s alias is VCT20. V41200 is the word memory reference for discrete bits SP0 through SP17, therefore, it’s alias is VSP0. V41201 is the word memory reference for discrete bits SP20 through SP37, therefore, it’s alias is VSP20.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
3–31
Page 116
Chapter 3: CPU Specifications and Operation
DL06 Memory Map
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Memory Type
Discrete Memory Reference (octal)
Word Memory Reference (octal)
Decimal
Symbol X0
Input Points
X0 – X777
V40400 - V40437
512
Output Points
Y0 – Y777
V40500 – V40537
512
Control Relays
C0 – C1777
V40600 - V40677
1024
Special Relays
SP0 – SP777
V41200 – V41237
512
Timers
T0 – T377
V41100 – V41117
256
Timer Current Values
None
V0 – V377
256
Timer Status Bits
T0 – T377
V41100 – V41117
256
Counters
CT0 – CT177
V41140 – V41147
128
Counter Current Values
None
V1000 – V1177
128
Counter Status Bits
CT0 – CT177
V41140 – V41147
128
Data Words (See Appendix F)
None
V400-V677 V1200 – V7377 V10000 - V17777
192 3200 4096
None specific, used with many instructions. None specific, used with many instructions. May be non-volatile if MOV inst. is used. Data can be rewritten to EEPROM at least 100,000 times before it fails.
Data Words EEPROM (See Appendix F)
None
V7400 – V7577
128
Stages
S0 – S1777
V41000 – V41017
1024
Remote I/O (future use) GX0-GX3777 (See Note 1) GY0-GY3777
V40000-V40177 V40200-V40377
2048 2048
System parameters
V700-V777 V7600 – V7777 V36000-V37777
64 128 1024
3–32
None
Y0 C0
C0 SP0
TMR
K100
T0
V0 K100 T0 CNT CT0 K10 V1000 K100 CT0
SG
SP0
S001 GX0
GY0
None specific, used for various purposes
NOTE 1: This area can be used for additional Data Words. NOTE 2: The DL06 systems have 20 fixed discrete inputs and 16 fixed discrete outputs, but the total can be increased by up to 64 inputs or 64 outputs or a combination of both.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 117
Chapter 3: CPU Specifications and Operation
X Input/Y Output Bit Map This table provides a listing of individual input and output points associated with each Vmemory address bit for the DL06’s twenty integrated physical inputs and 16 integrated physical outputs in addition to up to 64 inputs and 64 outputs for option cards. Actual available references are X0 to X777 (V40400 – V40437) and Y0 to Y777 (V40500 V40537). MSB
DL06 Input (X) and Output (Y) Points
LSB
15 017 037 057 077 117 137 157 177
14 016 036 056 076 116 136 156 176
13 015 035 055 075 115 135 155 175
12 014 034 054 074 114 134 154 174
11 013 033 053 073 113 133 153 173
10 012 032 052 072 112 132 152 172
9 011 031 051 071 111 131 151 171
8 010 030 050 070 110 130 150 170
7 007 027 047 067 107 127 147 167
6 006 026 046 066 106 126 146 166
5 005 025 045 065 105 125 145 165
4 004 024 044 064 104 124 144 164
3 003 023 043 063 103 123 143 163
2 002 022 042 062 102 122 142 162
1 001 021 041 061 101 121 141 161
0 000 020 040 060 100 120 140 160
217 237 257 277 317 337 357 377
216 236 256 276 316 336 356 376
215 235 255 275 315 335 355 375
214 234 254 274 314 334 354 374
213 233 253 273 313 333 353 373
212 232 252 272 312 332 352 372
211 231 251 271 311 331 351 371
210 230 250 270 310 330 350 370
207 227 247 267 307 327 347 367
206 226 246 266 306 326 346 366
205 225 245 265 305 325 345 365
204 224 244 264 304 324 344 364
203 223 243 263 303 323 343 363
202 222 242 262 302 322 342 362
201 221 241 261 301 321 341 361
417 437 457 477 517 537 557 577
416 436 456 476 516 536 556 576
415 435 455 475 515 535 555 575
414 434 454 474 514 534 554 574
413 433 453 473 513 533 553 573
412 432 452 472 512 532 552 572
411 431 451 471 511 531 551 571
410 430 450 470 510 530 550 570
407 427 447 467 507 527 547 567
406 426 446 466 506 526 546 566
405 425 445 465 505 525 545 565
404 424 444 464 504 524 544 564
403 423 443 463 503 523 543 563
402 422 442 462 502 522 542 562
617 637 657 677 717 737 757 777
616 636 656 676 716 736 756 776
615 635 655 675 715 735 755 775
614 634 654 674 714 734 754 774
613 633 653 673 713 733 753 773
612 632 652 672 712 732 752 772
611 631 651 671 711 731 751 771
610 630 650 670 710 730 750 770
607 627 647 667 707 727 747 767
606 626 646 666 706 726 746 766
605 625 645 665 705 725 745 765
604 624 644 664 704 724 744 764
603 623 643 663 703 723 743 763
602 622 642 662 702 722 742 762
X Input Y Output Address Address V40400 V40401 V40402 V40403 V40404 V40405 V40406 V40407
V40500 V40501 V40502 V40503 V40504 V40505 V40506 V40507
200 220 240 260 300 320 340 360
V40410 V40411 V40412 V40413 V40414 V40415 V40416 V40417
V40510 V40511 V40512 V40513 V40514 V40515 V40516 V40517
401 421 441 461 501 521 541 561
400 420 440 460 500 520 540 560
V40420 V40421 V40422 V40423 V40424 V40425 V40426 V40427
V40520 V40521 V40522 V40523 V40524 V40525 V40526 V40527
601 621 641 661 701 721 741 761
600 620 640 660 700 720 740 760
V40430 V40431 V40432 V40433 V40434 V40435 V40436 V40437
V40530 V40531 V40532 V40533 V40534 V40535 V40536 V40537
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
3–33
Page 118
Chapter 3: CPU Specifications and Operation
Stage Control/Status Bit Map
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
MSB
This table provides a listing of individual Stage control bits associated with each V-memory address bit. DL06 Stage (S) Control Bits LSB Address
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
017 037 057 077 117 137 157 177
016 036 056 076 116 136 156 176
015 035 055 075 115 135 155 175
014 034 054 074 114 134 154 174
013 033 053 073 113 133 153 173
012 032 052 072 112 132 152 172
011 031 051 071 111 131 151 171
010 030 050 070 110 130 150 170
007 027 047 067 107 127 147 167
006 026 046 066 106 126 146 166
005 025 045 065 105 125 145 165
004 024 044 064 104 124 144 164
003 023 043 063 103 123 143 163
002 022 042 062 102 122 142 162
001 021 041 061 101 121 141 161
000 020 040 060 100 120 140 160
V41000 V41001 V41002 V41003 V41004 V41005 V41006 V41007
217 237 257 277 317 337 357 377
216 236 256 276 316 336 356 376
215 235 255 275 315 335 355 375
214 234 254 274 314 334 354 374
213 233 253 273 313 333 353 373
212 232 252 272 312 332 352 372
211 231 251 271 311 331 351 371
210 230 250 270 310 330 350 370
207 227 247 267 307 327 347 367
206 226 246 266 306 326 346 366
205 225 245 265 305 325 345 365
204 224 244 264 304 324 344 364
203 223 243 263 303 323 343 363
202 222 242 262 302 322 342 362
201 221 241 261 301 321 341 361
200 220 240 260 300 320 340 360
V41010 V41011 V41012 V41013 V41014 V41015 V41016 V41017
417 437 457 477 517 537 557 577
416 436 456 476 516 536 556 576
415 435 455 475 515 535 555 575
414 434 454 474 514 534 554 574
413 433 453 473 513 533 553 573
412 432 452 472 512 532 552 572
411 431 451 471 511 531 551 571
410 430 450 470 510 530 550 570
407 427 447 467 507 527 547 567
406 426 446 466 506 526 546 566
405 425 445 465 505 525 545 565
404 424 444 464 504 524 544 564
403 423 443 463 503 523 543 563
402 422 442 462 502 522 542 562
401 421 441 461 501 521 541 561
400 420 440 460 500 520 540 560
V41020 V41021 V41022 V41023 V41024 V41025 V41026 V41027
617 637 657 677 717 737 757 777
616 636 656 676 716 736 756 776
615 635 655 675 715 735 755 775
614 634 654 674 714 734 754 774
613 633 653 673 713 733 753 773
612 632 652 672 712 732 752 772
611 631 651 671 711 731 751 771
610 630 650 670 710 730 750 770
607 627 647 667 707 727 747 767
606 626 646 666 706 726 746 766
605 625 645 665 705 725 745 765
604 624 644 664 704 724 744 764
603 623 643 663 703 723 743 763
602 622 642 662 702 722 742 762
601 621 641 661 701 721 741 761
600 620 640 660 700 720 740 760
V41030 V41031 V41032 V41033 V41034 V41035 V41036 V41037
3–34
This table is continued on the next page.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 119
Chapter 3: CPU Specifications and Operation
MSB
DL06 Stage (S) Control Bits (cont’d)
LSB
Address
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1017 1037 1057 1077 1117 1137 1157 1177
1016 1036 1056 1076 1116 1136 1156 1176
1015 1035 1055 1075 1115 1135 1155 1175
1014 1034 1054 1074 1114 1134 1154 1174
1013 1033 1053 1073 1113 1133 1153 1173
1012 1032 1052 1072 1112 1132 1152 1172
1011 1031 1051 1071 1111 1131 1151 1171
1010 1030 1050 1070 1110 1130 1150 1170
1007 1027 1047 1067 1107 1127 1147 1167
1006 1026 1046 1066 1106 1126 1146 1166
1005 1025 1045 1065 1105 1125 1145 1165
1004 1024 1044 1064 1104 1124 1144 1164
1003 1023 1043 1063 1103 1123 1143 1163
1002 1022 1042 1062 1102 1122 1142 1162
1001 1021 1041 1061 1101 1121 1141 1161
1000 1020 1040 1060 1100 1120 1140 1160
V41040 V41041 V41042 V41043 V41044 V41045 V41046 V41047
1217 1237 1257 1277 1317 1337 1357 1377
1216 1236 1256 1276 1316 1336 1356 1376
1215 1235 1255 1275 1315 1335 1355 1375
1214 1234 1254 1274 1314 1334 1354 1374
1213 1233 1253 1273 1313 1333 1353 1373
1212 1232 1252 1272 1312 1332 1352 1372
1211 1231 1251 1271 1311 1331 1351 1371
1210 1230 1250 1270 1310 1330 1350 1370
1207 1227 1247 1267 1307 1327 1347 1367
1206 1226 1246 1266 1306 1326 1346 1366
1205 1225 1245 1265 1305 1325 1345 1365
1204 1224 1244 1264 1304 1324 1344 1364
1203 1223 1243 1263 1303 1323 1343 1363
1202 1222 1242 1262 1302 1322 1342 1362
1201 1221 1241 1261 1301 1321 1341 1361
1200 1220 1240 1260 1300 1320 1340 1360
V41050 V41051 V41052 V41053 V41054 V41055 V41056 V41057
1417 1437 1457 1477 1517 1537 1557 1577
1416 1436 1456 1476 1516 1536 1556 1576
1415 1435 1455 1475 1515 1535 1555 1575
1414 1434 1454 1474 1514 1534 1554 1574
1413 1433 1453 1473 1513 1533 1553 1573
1412 1432 1452 1472 1512 1532 1552 1572
1411 1431 1451 1471 1511 1531 1551 1571
1410 1430 1450 1470 1510 1530 1550 1570
1407 1427 1447 1467 1507 1527 1547 1567
1406 1426 1446 1466 1506 1526 1546 1566
1405 1425 1445 1465 1505 1525 1545 1565
1404 1424 1444 1464 1504 1524 1544 1564
1403 1423 1443 1463 1503 1523 1543 1563
1402 1422 1442 1462 1502 1522 1542 1562
1401 1421 1441 1461 1501 1521 1541 1561
1400 1420 1440 1460 1500 1520 1540 1560
V41060 V41061 V41062 V41063 V41064 V41065 V41066 V41067
1617 1637 1657 1677 1717 1737 1757 1777
1616 1636 1656 1676 1716 1736 1756 1776
1615 1635 1655 1675 1715 1735 1755 1775
1614 1634 1654 1674 1714 1734 1754 1774
1613 1633 1653 1673 1713 1733 1753 1773
1612 1632 1652 1672 1712 1732 1752 1772
1611 1631 1651 1671 1711 1731 1751 1771
1610 1630 1650 1670 1710 1730 1750 1770
1607 1627 1647 1667 1707 1727 1747 1767
1606 1626 1646 1666 1706 1726 1746 1766
1605 1604 1625 1624 1645 1644 1665 1664 1705 1704 1725 1724 1745 1744 1765 1764
1603 1623 1643 1663 1703 1723 1743 1763
1602 1622 1642 1662 1702 1722 1742 1762
1601 1621 1641 1661 1701 1721 1741 1761
1600 1620 1640 1660 1700 1720 1740 1760
V41070 V41071 V41072 V41073 V41074 V41075 V41076 V41077
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
3–35