Page 140
Chapter 4: System Design and Configuration
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
The following examples show how to generate the MODBUS address and data type for hosts which require this format.
Example 1: V2100 Find the MODBUS address for User V location V2100.
Holding Reg 1088
1. Find V-memory in the table. 2. Convert V2100 into decimal (1088). 3. Use the MODBUS data type from the table. V-memory, user data (V)
3200
V1200 – V7377
640 – 3839
Holding Register
Example 2: Y20 Find the MODBUS address for output Y20. 1. Find Y outputs in the table.
Coil 2064
2. Convert Y20 into decimal (16). 3. Add the starting address for the range (2048). 4. Use the MODBUS data type from the table. Outputs (V)
256
Y0 – Y377
2048 - 2303
Coil
Example 3: T10 Current Value Find the MODBUS address to obtain the current value from Timer T10. 1. Find Timer Current Values in the table.
Input Reg. 8
2. Convert T10 into decimal (8). 3. Use the MODBUS data type from the table. Timer Current Values (V)
128
V0 – V177
0 - 127
Input Register
Example 4: C54
4–14
Find the MODBUS address for Control Relay C54. 1. Find Control Relays in the table.
Coil 3116
2. Convert C54 into decimal (44). 3. Add the starting address for the range (3072). 4. Use the MODBUS data type from the table. Control Relays (CR)
512
C0 – C77
3072 – 3583
DL06 Micro PLC User Manual; 3rd Edition Rev. A
Coil
Page 141
Chapter 4: System Design and Configuration
If Your MODBUS Host Software Requires an Address ONLY Some host software does not allow you to specify the MODBUS data type and address. Instead, you specify an address only. This method requires another step to determine the address, but it’s still fairly simple. Basically, MODBUS also separates the data types by address ranges as well. So this means an address alone can actually describe the type of data and location. This is often referred to as “adding the offset”. One important thing to remember here is that two different addressing modes may be available in your host software package. These are: • 484 Mode • 584/984 Mode
We recommend that you use the 584/984 addressing mode if your host software allows you to choose. This is because the 584/984 mode allows access to a higher number of memory locations within each data type. If your software only supports 484 mode, then there may be some PLC memory locations that will be unavailable. The actual equation used to calculate the address depends on the type of PLC data you are using. The PLC memory types are split into two categories for this purpose. • Discrete – X, SP, Y, CR, S, T (contacts), C (contacts) • Word – V, Timer current value, Counter current value
In either case, you basically convert the PLC octal address to decimal and add the appropriate MODBUS addresses (as required). The table below shows the exact equation used for each group of data. Discrete Data Types DL06 Memory Type Global Inputs (GX) Inputs (X) Special Relays (SP) Global Outputs (GY) Outputs (Y) Control Relays (CR) Timer Contacts (T) Counter Contacts (CT) Stage Status Bits (S)
PLC Range (Octal) GX0-GX1746 GX1747-GX3777 X0 – X1777 SP0 – SP777 GY0 - GY3777 Y0 – Y1777 C0 – C3777 T0 – T377 CT0 – CT377 S0 – S1777
Address (484 Address (584/984 MODBUS Data Mode) Mode) Type 1001 - 1999 ------1 - 2048 2049 - 3072 3073 - 5120 6145 - 6400 6401 - 6656 5121 - 6144
10001 - 10999 11000 - 12048 12049 - 13072 13073 - 13584 1 - 2048 2049 - 3072 3073 - 5120 6145 - 6400 6401 - 6656 5121 - 6144
Input Input Input Input Output Output Output Output Output Output
DL06 Micro PLC User Manual; 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
4–15
Page 142
Chapter 4: System Design and Configuration
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 4–16
Registers V-memory (Timers) V-memory (Counters)
V-memory (Data Words)
Word Data Types PLC Range Input/Holding Input/Holding (Octal) (484 Mode)* (584/984 Mode)* V0 - V377 V1000 - V1177 V1200 - V1377 V1400 - V1746 V1747 - V1777 V2000 - V7377 V10000 - V17777
3001/4001 3513/4513 3641/4641 3769/4769 -------
30001/40001 30513/40513 30641/40641 30769/40769 31000/41000 41025 44097
* MODBUS: Function 04 The DL05/06, DL250-1/260, DL350 and DL450 will support function 04, read input register (Address 30001). To use function 04, put the number ‘4’ into the most significant position (4xxx). Four digits must be entered for the intruction to work properly with this mode. LD
K101
LD K4128 LDA O4000
The Maximum constant possible is 4128. This is due to the 128 maximum number of Bytes that the RX/WX instruction can allow. The value of 4 in the most significant position of the word will cause the RX to use function 04 (30001 range).
RX
Y0
1. Refer to your PLC user manual for the correct memory mapping size of your PLC. Some of the addresses shown above might not pertain to your particular CPU. 2. For an automated MODBUS/Koyo address conversion utility, go to our website, www.automationdirect.com, and down load download the EXCEL file modbus_conversion.xls located at: Tech Support > Technical Support Home page.
DL06 Micro PLC User Manual; 3rd Edition Rev. A
Page 143
Chapter 4: System Design and Configuration
Example 1: V2100 584/984 Mode Find the MODBUS address for User V location V2100.
PLC Address (Dec.) + Mode Address
1. Find V-memory in the table.
V2100 = 1088 decimal
2. Convert V2100 into decimal (1088).
1088 + 40001 =
41089
3. Add the MODBUS starting address for the mode (40001). For Word Data Types.... Timer Current Values (V) Counter Current Values (V) V-memory, user data (V)
PLC Address (Dec.) 128 128 1024
V0 – V177 V1200 – V7377 V2000 – V3777
+
Appropriate Mode Address
0 – 127 512 – 639 1024 – 2047
3001 3001 4001
30001 30001 40001
Input Register Input Register Holding Register
Example 2: Y20 584/984 Mode Find the MODBUS address for output Y20.
PLC Addr. (Dec.) + Start Address + Mode
1. Find Y outputs in the table.
Y20 = 16 decimal
2. Convert Y20 into decimal (16).
16 + 2048 + 1 =
2065
3. Add the starting address for the range (2048). 4. Add the MODBUS address for the mode (1). Outputs (Y) Control Relays (CR) Timer Contacts (T)
320 256 128
Y0 - Y477 C0 - C377 T0 - T177
2048 - 2367 3072 - 3551 6144 - 6271
1 1 1
1 1 1
Coil Coil Coil
Example 3: T10 Current Value 484 Mode Find the MODBUS address to obtain the current value from Timer T10.
PLC Address (Dec.) + Mode Address TA10 = 8 decimal
1. Find Timer Current Values in the table.
8 + 3001 =
3009
2. Convert T10 into decimal (8). 3. Add the MODBUS starting address for the mode (3001). For Word Data Types.... Timer Current Values (V) Counter Current Values (V) V-memory, user data (V)
PLC Address (Dec.) 128 128 1024
V0 – V177 V1200 – V7377 V2000 – V3777
+ 0 – 127 512 – 639 1024 – 2047
Appropriate Mode Address 3001 3001 4001
30001 30001 40001
Input Register Input Register Holding Register
Example 4: C54 584/984 Mode Find the MODBUS address for Control Relay C54. PLC Addr. (Dec.) + Start Address + Mode 1. Find Control Relays in the table.
C54 = 44 decimal
2. Convert C54 into decimal (44).
44 + 3072 + 1 =
3117
3. Add the starting address for the range (3072). 4. Add the MODBUS address for the mode (1). Outputs (Y) Control Relays (CR) Timer Contacts (T)
320 256 128
Y0 - Y477 C0 - C377 T0 - T177
2048 - 2367 3072 - 3551 6144 - 6271
1 1 1
1 1 1
Coil Coil Coil
DL06 Micro PLC User Manual; 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
4–17
Page 144
Chapter 4: System Design and Configuration
Network Master Operation
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 4–18
This section describes how the DL06 can communicate on a MODBUS or DirectNET network as a master. For MODBUS networks, it uses the MODBUS RTU protocol, which must be interpreted by all the slaves on the network. Both MODBUS and DirectNet are single master/multiple slave networks. The master is the only member of the network that can initiate requests on the network. This section teaches you how to design the required ladder logic for network master operation. 0V G LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C. OUTPUT: 6-240V
Y
0
X
1
2
50 - 60Hz 3
INPUT: 12 - 24V
4
2.0A, 6 - 27V
5
6
7
10
2.0A 11
12
PWR: 100-240V 13
14
15
16
PWR RUN CPU TX1 RX1 TX2 RX2
50-60Hz 40VA 17
20
D0-06DR
21 22
23
3 - 15mA
LOGIC C0
06
K oyo
X1 X0
X3 X2
X4 C1
X6 X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3
TERM PORT1
PORT2
RUN STOP
Master
MODBUS RTU Protocol, or DirectNET
Slave #1
Slave #2
Slave #3
When using the DL06 PLC as the master station, simple RLL instructions are used to initiate the requests. The WX instruction initiates network write operations, and the RX instruction initiates network read operations. Before executing either the WX or RX commands, we will need to load data related to the read or write operation onto the CPU’s accumulator stack. When the WX or RX instruction executes, it uses the information on the stack combined with data in the instruction box to completely define the task, which goes to the port. LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 G 0V AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C. OUTPUT: 6-240V
Y
X
0
1
2
50 - 60Hz 3
INPUT: 12 - 24V
4
5
2.0A, 6 - 27V 6
7
10
2.0A 11
12
PWR: 100-240V 13
14
15
16
PWR RUN CPU TX1 RX1 TX2 RX2
50-60Hz 40VA 17
20
D0-06DR
21 22
23
3 - 15mA
LOGIC C0
06
K oyo
X1 X0
X3 X2
X4 C1
X6 X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X10 X12 C3 X15 X17 X20 X22 N.C.
TERM PORT1
PORT2
RUN STOP
Master
Network
WX (write) RX (read) Slave
The following step-by-step procedure will provide you the information necessary to set up your ladder program to receive data from a network slave.
DL06 Micro PLC User Manual; 3rd Edition Rev. A
Page 145
Chapter 4: System Design and Configuration
Step 1: Identify Master Port # and Slave # The first Load (LD) instruction identifies the communications port number on the network master (DL06) and the address of the slave station. This instruction can address up to 99 MODBUS slaves, or 90 DirectNET slaves. The format of the word is shown to the right. The “F2” in the upper byte indicates the use of the right port of the DL06 PLC, port number 2. The lower byte contains the slave address number in BCD (01 to 99).
Step 2: Load Number of Bytes to Transfer
F
2
0
1
Slave address (BCD) Port number (BCD) Internal port (hex) LD KF201
6
4
(BCD)
The second Load (LD) instruction determines the number of bytes which will be transferred # of bytes to transfer between the master and slave in the subsequent WX or RX instruction. The value to be loaded LD is in BCD format (decimal), from 1 to 128 K64 bytes. The number of bytes specified also depends on the type of data you want to obtain. For example, the DL06 Input points can be accessed by V-memory locations or as X input locations. However, if you only want X0 – X27, you’ll have to use the X input data type because the V-memory locations can only be accessed in 2-byte increments. The following table shows the byte ranges for the various types of DirectLOGIC products. DL05 / 06 / 205 / 350 / 405 Memory
Bits per unit
Bytes
V-memory T / C current value Inputs (X, SP) Outputs (Y, C, Stage, T/C bits) Scratch Pad Memory Diagnostic Status
16 16 8
2 2 1
8
1
8 8
1 1
DL330 / 340 Memory
Bits per unit
Bytes
Data registers T / C accumulator I/O, internal relays, shift register bits, T/C bits, stage bits Scratch Pad Memory Diagnostic Status(5 word R/W)
8 16
1 2
1
1
8 16
1 10
DL06 Micro PLC User Manual; 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
4–19
Page 146
Chapter 4: System Design and Configuration
Step 3: Specify Master Memory Area
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
4
The third instruction in the RX or WX sequence is a Load Address (LDA) instruction. Its purpose is to load the starting address of the memory area to be transferred. Entered as an octal number, the LDA instruction converts it to hex and places the result in the accumulator. For a WX instruction, the DL06 CPU sends the number of bytes previously specified from its memory area beginning at the LDA address specified. For an RX instruction, the DL06 CPU reads the number of bytes previously specified from the slave, placing the received data into its memory area beginning at the LDA address specified.
0
6
0
0
(octal)
Starting address of master transfer area LDA O40600
MSB
V40600
LSB
15 MSB
0 V40601
LSB
15
0
NOTE: Since V-memory words are always 16 bits, you may not always use the whole word. For example, if you only specify 3 bytes and you are reading Y outputs from the slave, you will only get 24 bits of data. In this case, only the 8 least significant bits of the last word location will be modified. The remaining 8 bits are not affected.
Step 4: Specify Slave Memory Area The last instruction in our sequence is the WX or RX instruction itself. Use WX to write to the slave, and RX to read from the slave. All four of our instructions are shown to the right. In the last instruction, you must specify the starting address and a valid data type for the slave.
SP116
LD KF201 LD K64
• DirectNET slaves – specify the same address in the WX and RX instruction as the slave’s native I/O address
LDA O40600
• MODBUS DL405, DL205, or DL06 slaves – specify the same address in the WX and RX instruction as the slave’s native I/O address
Y0
RX
• MODBUS 305 slaves – use the following table to convert DL305 addresses to MODBUS addresses
DL305 Series CPU Memory Type–to–MODBUS Cross Reference (excluding 350 CPU) PLC Memory Type
PLC Base Address
TMR/CNT Current Values
R600
V0
I/O Points Data Registers Stage Status Bits (D3-330P only)
IO 000 R401,R400 S0
GY0 V100 GY200
4–20
MODBUS PLC Memory Base Address Type TMR/CNT Status Bits Control Relays Shift Registers
DL06 Micro PLC User Manual; 3rd Edition Rev. A
PLC Base Address
MODBUS Base Address
CT600
GY600
CR160 SR400
GY160 GY400
Page 147
Chapter 4: System Design and Configuration
Communications from a Ladder Program Typically network communications SP117 Y1 will last longer than 1 scan. The SET program must wait for the SP116 communications to finish before LD KF201 starting the next transaction. Port Communication Error Port 2, which can be a master, has two LD Port Busy K0003 Special Relay contacts associated with it (see Appendix D for comm port LDA O40600 special relays).One indicates “Port busy”(SP116), and the other indicates RX Y0 ”Port Communication Error”(SP117). The example above shows the use of these contacts for a network master that only reads a device (RX). The “Port Busy” bit is on while the PLC communicates with the slave. When the bit is off the program can initiate the next network request. The “Port Communication Error” bit turns on when the Interlocking Relay PLC has detected an error. Use of this bit is optional. SP116 C100 LD When used, it should be ahead of any network instruction KF201 boxes since the error bit is reset when an RX or WX instruction is executed. LD
Multiple Read and Write Interlocks If you are using multiple reads and writes in the RLL program, you have to interlock the routines to make sure all the routines are executed. If you don’t use the Interlocking interlocks, then the CPU will only execute the first Relay routine. This is because each port can only handle one transaction at a time. SP116 C100 In the example to the right, after the RX instruction is executed, C100 is set. When the port has finished the communication task, the second routine is executed and C100 is reset. If you’re using RLLPLUS Stage Programming, you can put each routine in a separate program stage to ensure proper execution and switch from stage to stage allowing only one of them to be active at a time.
K0003
LDA O40600 RX VY0 C100 SET LD KF201 LD K0003 LDA O40400 WX VY0 C100 RST
DL06 Micro PLC User Manual; 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
4–21
Page 148
Chapter 4: System Design and Configuration
Network Master Operation (using MRX and MWX 1 Instructions)
2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
This section describes how the DL06 can communicate on a MODBUS RTU network as a master using the MRX and MWX read/write instructions. These instructions allow you to enter native MODBUS addressing in your ladder logic program with no need to perform octal to decimal conversions. MODBUS is a single master/multiple slave network. The master is the only member of the network that can initiate requests on the network. This section teaches you how to design the required ladder logic for network master operation.
G LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 0V Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C. AC(L) AC(N) 24V C0 OUTPUT: 6-240V
Y
X
0
1
2
50 - 60Hz 3
INPUT: 12 - 24V
4
5
2.0A, 6 - 27V 6
7
10
2.0A 11
12
PWR: 100-240V 13
14
15
16
PWR RUN CPU TX1 RX1 TX2 RX2
50-60Hz 40VA 17
20
D0-06DR
21 22
23
3 - 15mA
LOGIC C0
06
K oyo
X1 X0
X3 X2
X4 C1
X6 X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3
TERM PORT1
PORT2
RUN STOP
Master
MODBUS RTU Protocol, or DirectNET
Slave #1
Slave #2
Slave #3
MODBUS Function Codes Supported The MODBUS function code determines whether the access is a read or a write, and whether to access a single data point or a group of them. The DL06 supports the MODBUS function codes described below. MODBUS Function Code
4–22
01 02 05 15 03, 04 06 07 08 16
Function Read a group of coils Read a group of inputs Set / Reset a single coil (slave only) Set / Reset a group of coils Read a value from one or more registers Write a value into a single register (slave only) Read Exception Status Diagnostics Write a value into a group of registers
DL06 Micro PLC User Manual; 3rd Edition Rev. A
DL06 Data Types Available Y, CR, T, CT X, SP Y, CR, T, CT Y, CR, T, CT V V V V V
Page 149
Chapter 4: System Design and Configuration
MODBUS Read from Network(MRX) The MODBUS Read from Network (MRX) instruction is used by the DL06 network master to read a block of data from a connected slave device and to write the data into V–memory addresses within the master. The instruction allows the user the to specify the MODBUS Function Code, slave station address, starting master and slave memory addresses, number of elements to transfer, MODBUS data format and the Exception Response Buffer.
• Port Number: must be DL06 Port 2 (K2) • Slave Address: specify a slave station address (0–247) • Function Code: The following MODBUS function codes are supported by the MRX instruction: 01 – Read a group of coils 02 – Read a group of inputs 03 – Read holding registers 04 – Read input registers 07 – Read Exception status 08 – Diagnostics • Start Slave Memory Address: specifies the starting slave memory address of the data to be read. See the table on the following page. • Start Master Memory Address: specifies the starting memory address in the master where the data will be placed. See the table on the following page. • Number of Elements: specifies how many coils, input, holding registers or input register will be read. See the table on the following page. • MODBUS Data Format: specifies MODBUS 584/984 or 484 data format to be used • Exception Response Buffer: specifies the master memory address where the Exception Response will be placed. See the table on the following page.
DL06 Micro PLC User Manual; 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
4–23