Page 450

Chapter 5: Intelligent Box (IBox) Instructions

ECOM100 Read IP Address (ECRDIP) (IB-722)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

DS5

Used

HPP

N/A

5–296

ECOM100 Read IP Address will read the 4 parts of the IP address and store them in 4 consecutive V Memory locations in decimal format, on a leading edge transition to the IBox. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Either the Success or Error bit parameter will turn on once the command is complete. In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the ECOM100 circuit board. ECRDIP Parameters • ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed • IP Address: specifies the starting address where the ECOM100’s IP Address will be placed in 4 consecutive V-memory locations

Parameter ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B IP Address (4 Words) . . . . . . . . . . . . . . . . . . . . V

DL06 Range K0-255 See DL06 V-memory map - Data Words See DL06 V-memory map See DL06 V-memory map See DL06 V-memory map - Data Words

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 451

Chapter 5: Intelligent Box (IBox) Instructions

ECRDIP Example Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module.V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module.

1 2 3 4 5 6 7 8 9 Rung 2: On the 2nd scan, read the IP Address of the ECOM100 and store it in V3000 thru 10 V3003 (4 decimal numbers). The ECOM100's IP Address could be displayed by an HMI. The ECRDIP is leading edge triggered, not power-flow driven (similar to a counter input leg). The command to read the IP Address will be sent to the ECOM100 whenever the power 11 flow into the IBox goes from OFF to ON. 12 If successful, turn on C100. If there is a failure, turn on C101. 13 14 A B C D DL06 Micro PLC User Manual, 3rd Edition Rev. A

5–297

Page 452

Chapter 5: Intelligent Box (IBox) Instructions

ECOM100 Read Module ID (ECRDMID) (IB-720)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

DS5

Used

HPP

N/A

5–298

ECOM100 Read Module ID will read the binary (decimal) WORD sized Module ID on a leading edge transition to the IBox. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Either the Success or Error bit parameter will turn on once the command is complete. In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the ECOM100 circuit board. ECRDMID Parameters • ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed • Module ID: specifies the location where the ECOM100’s Module ID (decimal) will be placed

Parameter ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Module ID. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V

DL06 Range K0-255 See DL06 V-memory map - Data Words See DL06 V-memory map See DL06 V-memory map See DL06 V-memory map - Data Words

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 453

Chapter 5: Intelligent Box (IBox) Instructions

ECRDMID Example Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module.V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module.

Rung 2: On the 2nd scan, read the Module ID of the ECOM100 and store it in V2000. The ECRDMID is leading edge triggered, not power-flow driven (similar to a counter input leg). The command to read the module ID will be sent to the ECOM100 whenever the power flow into the IBox goes from OFF to ON. If successful, turn on C100. If there is a failure, turn on C101.

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–299

Page 454

Chapter 5: Intelligent Box (IBox) Instructions

ECOM100 Read Module Name (ECRDNAM) (IB-724)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

DS5

Used

HPP

N/A

5–300

ECOM100 Read Name will read the Module Name up to the number of specified characters on a leading edge transition to the IBox. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Either the Success or Error bit parameter will turn on once the command is complete. In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the ECOM100 circuit board. ECRDNAM Parameters • ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed • Module Name: specifies the starting buffer location where the ECOM100’s Module Name will be placed • Num Chars: specifies the number of characters (bytes) to read from the ECOM100’s Name field

Parameter ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Module Name . . . . . . . . . . . . . . . . . . . . . . . . . . V Num Chars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K

DL06 Range K0-255 See DL06 V-memory map - Data Words See DL06 V-memory map See DL06 V-memory map See DL06 V-memory map - Data Words K1-128

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 455

Chapter 5: Intelligent Box (IBox) Instructions

ECRDNAM Example Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module.V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module.

Rung 2: On the 2nd scan, read the Module Name of the ECOM100 and store it in V3000 thru V3003 (8 characters). This text can be displayed by an HMI. The ECRDNAM is leading edge triggered, not power-flow driven (similar to a counter input leg). The command to read the module name will be sent to the ECOM100 whenever the power flow into the IBox goes from OFF to ON. If successful, turn on C100. If there is a failure, turn on C101.

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–301

Page 456

Chapter 5: Intelligent Box (IBox) Instructions

ECOM100 Read Subnet Mask (ECRDSNM) (IB-732)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

DS5

Used

HPP

N/A

5–302

ECOM100 Read Subnet Mask will read the 4 parts of the Subnet Mask and store them in 4 consecutive V Memory locations in decimal format, on a leading edge transition to the IBox. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Either the Success or Error bit parameter will turn on once the command is complete. In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the ECOM100 circuit board. ECRDSNM Parameters • ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed • Subnet Mask: specifies the starting address where the ECOM100’s Subnet Mask will be placed in 4 consecutive V-memory locations

Parameter ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Subnet Mask (4 Words) . . . . . . . . . . . . . . . . . . V

DL06 Range K0-255 See DL06 V-memory map - Data Words See DL06 V-memory map See DL06 V-memory map See DL06 V-memory map - Data Words

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 457

Chapter 5: Intelligent Box (IBox) Instructions

ECRDSNM Example Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module.V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module.

Rung 2: On the 2nd scan, read the Subnet Mask of the ECOM100 and store it in V3000 thru V3003 (4 decimal numbers). The ECOM100's Subnet Mask could be displayed by an HMI. The ECRDSNM is leading edge triggered, not power-flow driven (similar to a counter input leg). The command to read the Subnet Mask will be sent to the ECOM100 whenever the power flow into the IBox goes from OFF to ON. If successful, turn on C100. If there is a failure, turn on C101.

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–303

Page 458

Chapter 5: Intelligent Box (IBox) Instructions

ECOM100 Write Description (ECWRDES) (IB-727)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

DS5

Used

HPP

N/A

5–304

ECOM100 Write Description will write the given Description to the ECOM100 module on a leading edge transition to the IBox. If you use a dollar sign ($) or double quote ("), use the PRINT/VPRINT escape sequence of TWO dollar signs ($$) for a single dollar sign or dollar sign-double quote ($") for a double quote character. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Either the Success or Error bit parameter will turn on once the command is complete. If there is an error, the Error Code parameter will report an ECOM100 error code (less than 100), or a PLC logic error (greater than 1000). The Description is stored in Flash-ROM in the ECOM100 and the execution of this IBox will disable the ECOM100 module for at least a half second until it writes the Flash-ROM. Therefore, it is HIGHLY RECOMMENDED that you only execute this IBox ONCE on first scan. Since it requires a LEADING edge to execute, use a NORMALLY CLOSED SP0 (STR NOT First Scan) to drive the power flow to the IBox. In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the ECOM100 circuit board. ECWRDES Parameters • ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed • Error Code: specifies the location where the Error Code will be written • Description: specifies the Description that will be written to the module

Parameter ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

DL06 Range K0-255 See DL06 V-memory map - Data Words See DL06 V-memory map See DL06 V-memory map See DL06 V-memory map - Data Words Text

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 459

Chapter 5: Intelligent Box (IBox) Instructions

ECWRDES Example Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module.V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module.

Rung 2: On the 2nd scan, set the Module Description of the ECOM100. Typically this is done using NetEdit, but this IBox allows you to configure the module description in the ECOM100 using your ladder program. The EWRDES is leading edge triggered, not power-flow driven (similar to a counter input leg). The command to write the module description will be sent to the ECOM100 whenever the power flow into the IBox goes from OFF to ON. If successful, turn on C100. If there is a failure, turn on C101. If it fails, you can look at V2000 for the specific error code.

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–305