Page 160
Chapter 9: Maintenance and Troubleshooting
Program Error Codes The following table lists program syntax and runtime error codes. Error detection occurs during a Program-to-Run mode transition, or when you use AUX 21 – Check Program. The CPU will also turn on SP52 and store the error code in V7755. Appendix B provides a more complete description of the error codes. Error Code E4** E401 E402 E403 E404 E405 E406 E412 E421 E422 E423 E431 E433 E434 E435 E436 E437
Description No Program in CPU Missing END statement Missing LBL Missing RET Missing FOR Missing NEXT Missing IRT SBR / LBL >64 Duplicate stage reference Duplicate SBR/LBL reference Nested loop Invalid ISG/SG address Invalid ISG / SG address Invalid RTC Invalid RT Invalid INT address Invalid IRTC
Error Code E438 E440 E441 E451 E453 E454 E455 E456 E461 E462 E463 E464 E471 E472 E473 E499
Description Invalid IRT address Invalid Data Address ACON/NCON Bad MLS/MLR Missing T/C Bad TMRA Bad CNT Bad SR Stack Overflow Stack Underflow Logic Error Missing Circuit Duplicate coil reference Duplicate TMR reference Duplicate CNT reference Print instruction
DL06 Micro PLC User Manual, 3rd Edition Rev. A
9–5
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Page 161
Chapter 9: Maintenance and Troubleshooting
CPU Indicators
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
The DL06 Micro PLCs have indicators on the front to help you determine potential problems with the system. In normal runtime operation only, the RUN and PWR indicators are on. The table below is a quick reference to potential problems. Indicator Status PWR (Green LED off) RUN (Green LED off) CPU (Red LED on) CPU (Blinking Red LED)
Potential Problems System voltage incorrect PLC power supply faulty CPU programming error (CPU in program mode) Electrical noise interference Internal CPU defective Low backup battery (refer to page 4-8)
PWR Indicator In general there are three reasons for the CPU power status LED (PWR) to be OFF: 1. Power to the unit is incorrect or is not applied. 2. PLC power supply is faulty. 3. Other component(s) have the power supply shut down.
If the voltage to the power supply is not correct, the PLC may not operate properly or may not operate at all. Use the following guidelines to correct the problem. WARNING: To minimize the risk of electrical shock, always disconnect the system power before inspecting the physical wiring. 1. First, disconnect the external power. 2. Verify that all external circuit breakers or fuses are still intact. 3. Check all incoming wiring for loose connections. If you’re using a separate termination block, check those connections for accuracy and integrity. 4. If the connections are acceptable, reconnect the system power and verify the voltage at the DL06 power input is within specification. If the voltage is not correct, shut down the system and correct the problem. 5. If all wiring is connected correctly and the incoming power is within the specifications, the PLC internal supply may be faulty.
The best way to check for a faulty PLC is to substitute a known good one to see if this corrects the problem. The removable connectors on the DL06 make this relatively easy. If there has been a major power surge, it is possible the PLC internal power supply has been damaged. If you suspect this is the cause of the power supply damage, consider installing an AC line conditioner to attenuate damaging voltage spikes in the future.
9–6
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 162
Chapter 9: Maintenance and Troubleshooting
RUN Indicator If the CPU will not enter the Run mode (the RUN indicator is off ), the problem is usually in the application program, unless the CPU has a fatal error. If a fatal error has occurred, the CPU LED should be on. (You can use a programming device to determine the cause of the error.) Both of the programming devices, Handheld Programmer and DirectSOFT 5, will return an error message describing the problem. Depending on the error, there may also be an AUX function you can use to help diagnose the problem. The most common programming error is “Missing END Statement”. All application programs require an END statement for proper termination. A complete list of error codes can be found in Appendix B.
1 2 3 4 CPU Indicator 5 If the CPU indicator is on, a fatal error has occurred in the CPU. Generally, this is not a programming problem but an actual hardware failure. You can power cycle the system to clear 6 the error. If the error clears, you should monitor the system and determine what caused the problem. You will find this problem is sometimes caused by high frequency electrical noise introduced into the CPU from an outside source. Check your system grounding and install 7 electrical noise filters if the grounding is suspected. If power cycling the system does not reset the error, or if the problem returns, you should replace the CPU. 8 If the CPU indicator is blinking, the backup battery is low (refer to page 3-8). 9 Communications Problems If you cannot establish communications with the CPU, check these items. 10 • The cable is disconnected. • The cable has a broken wire or has been wired incorrectly. 11 • The cable is improperly terminated or grounded. • The device connected is not operating at the correct baud rate (9600 baud). 12 • The device connected to the port is sending data incorrectly, or another application is running on the device. 13 • A grounding difference exists between the two devices. • Electrical noise is causing intermittent errors. 14 • The PLC has a bad communication port and should be replaced. For problems in communicating with DirectSOFT 5 on a personal computer, refer to the DirectSOFT 5 programming user manual. It includes a troubleshooting section that can help A you diagnose PC problems in communications port setup, address or interrupt conflicts, etc. B C D DL06 Micro PLC User Manual, 3rd Edition Rev. A
9–7
Page 163
Chapter 9: Maintenance and Troubleshooting
I/O Point Troubleshooting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Possible Causes If you suspect an I/O error, there are several things that could be causing the problem. • High-Speed I/O configuration error • A blown fuse in your machine or panel (the DL06 does not have internal I/O fuses) • A loose terminal block • The auxiliary 24 VDC supply has failed • The Input or Output Circuit has failed
Some Quick Steps When troubleshooting the DL06 Micro PLCs, please be aware of the following facts which may assist you in quickly correcting an I/O problem. • HSIO configuration errors are commonly mistaken for I/O point failure during program development. If the I/O point in question is in X0–X2, or Y0–Y1, check all parameter locations listed in Chapter 3 that apply to the HSIO mode you have selected. • The output circuits cannot detect shorted or open output points. If you suspect one or more faulty points, measure the voltage drop from the common to the suspect point. Remember when using a Digital Volt Meter, leakage current from an output device such as a triac or a transistor must be considered. A point which is off may appear to be on if no load is connected the point. • The I/O point status indicators are logic-side indicators. This means the LED which indicates the on or off status reflects the status of the point with respect to the CPU. On an output point the status indicators could be operating normally while the actual output device (transistor, triac etc.) could be damaged. With an input point, if the indicator LED is on, the input circuitry is probably operating properly. Verify the LED goes off when the input signal is removed. • Leakage current can be a problem when connecting field devices to an I/O point. False input signals can be generated when the leakage current of an output device is great enough to turn on the connected input device. To correct this install a resistor in parallel with the input or output of the circuit. The value of this resistor will depend on the amount of leakage current and the voltage applied but usually a 10K to 20K resistor will work. Verify the wattage rating of the resistor is correct for your application. • Because of the removable terminal blocks on the DL06, the easiest method to determine if an I/O circuit has failed is to replace the unit if you have a spare. However, if you suspect a field device is defective, that device may cause the same failure in the replacement PLC as well. As a point of caution, you may want to check devices or power supplies connected to the failed I/O circuit before replacing the unit with a spare.
9–8
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 164
Chapter 9: Maintenance and Troubleshooting Output points can be set on or off in the DL06 series CPUs. If you want to do an I/O checkout independent of the application program, follow the procedure below: Step
Action
1 2 3
Use a handheld programmer or DirectSOFT 5 to communicate online to the PLC. Change to Program Mode. Go to address 0.
4
Insert an “END” statement at address 0. (This will cause program execution to occur only at address 0 and prevent the application program from turning the I/O points on or off).
5 6 7
Change to Run Mode. Use the programming device to set (turn) on or off the points you wish to test. When you finish testing I/O points delete the “END” statement at address 0.
WARNING: Depending on your application, forcing I/O points may cause unpredictable machine operation that can result in a risk of personal injury or equipment damage. Make sure you have taken all appropriate safety precautions prior to testing any I/O points.
Handheld Programmer Keystrokes Used to Test an Output Point END
X0
X2
X1
X3
X5
X7
Y2
Insert an END statement at the beginning of the program. This disables the remainder of the program.
X4 END
From a clear display, use the following keystrokes ST AT
16P STATUS BIT REF X
ENT
Use the PREV or NEXT keys to select the Y data type NEXT
A 0
Y 10
ENT
Y2 is now on
Use arrow keys to select point, then use ON and OFF to change the status SHFT
ON INS
Y0
Y 10
Y0
DL06 Micro PLC User Manual, 3rd Edition Rev. A
9–9
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Page 165
Chapter 9: Maintenance and Troubleshooting
Noise Troubleshooting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Electrical Noise Problems Noise is one of the most difficult problems to diagnose. Electrical noise can enter a system in many different ways and they fall into one of two categories, conducted or radiated. It may be difficult to determine how the noise is entering the system but the corrective actions for either of the types of noise problems are similar. • Conducted noise is when the electrical interference is introduced into the system by way of an attached wire, panel connection ,etc. It may enter through an I/O circuit, a power supply connection, the communication ground connection, or the chassis ground connection. • Radiated noise is when the electrical interference is introduced into the system without a direct electrical connection, much in the same manner as radio waves.
Reducing Electrical Noise
9–10
While electrical noise cannot be eliminated it can be reduced to a level that will not affect the system. • Most noise problems result from improper grounding of the system. A good earth ground can be the single most effective way to correct noise problems. If a ground is not available, install a ground rod as close to the system as possible. Ensure all ground wires are single point grounds and are not daisy chained from one device to another. Ground metal enclosures around the system. A loose wire can act as a large antenna, introducing noise into the system. Therefore, tighten all connections in your system. Loose ground wires are more susceptible to noise than the other wires in your system. Review Chapter 2 Installation, Wiring, and Specifications if you have questions regarding how to ground your system. • Electrical noise can enter the system through the power source for the PLC and I/O circuits. Installing an isolation transformer for all AC sources can correct this problem. DC sources should be well-grounded good quality supplies. • Separate input wiring from output wiring. Never run low-voltage I/O wiring close to high voltage wiring.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 166
Chapter 9: Maintenance and Troubleshooting
Machine Startup and Program Troubleshooting
1 2 • Program Syntax Check • Duplicate Reference Check 3 • Special Instructions • Run Time Edits 4 • Forcing I/O Points Syntax Check 5 Even though the Handheld Programmer and Direct SOFT 5 provide error checking during program entry, you may want to check a program that has been modified. Both programming 6 devices offer a way to check the program syntax. For example, you can use AUX 21, CHECK PROGRAM to check the program syntax from a Handheld Programmer, or you can use the 7 PLC Diagnostics menu option within Direct SOFT 5. This check will find a wide variety of programming errors. The following example shows how to use the syntax check with a Handheld Programmer. 8 Use AUX 21 to perform syntax check 9 AUX 21 CHECK PRO 1:SYN 2:DUP REF 10 Select syntax check (default selection) 11 (You may not get the busy display BUSY if the program is not very long.) 12 One of two displays will appear 13 Error Display (example) $00050 E401 MISSING END 14 (shows location in question) A Syntax OK display NO SYNTAX ERROR B ? See the Error Codes Section for a complete listing of programming error codes. If you get an C error, just press CLR and the Handheld will display the instruction where the error occurred. Correct the problem and continue running the Syntax check until the NO SYNTAX ERROR D message appears. The DL06 Micro PLCs provide several features that can help you debug your program before and during machine startup. This section discusses the following topics which can be very helpful.
CLR
C
B
2
1
AUX
ENT
ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
9–11
Page 167
Chapter 9: Maintenance and Troubleshooting
Special Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 9–12
There are several instructions that can be used to help you debug your program during machine startup operations. • END • PAUSE • STOP
END Instruction: If you need a way to quickly disable part of the program, just insert an END statement prior to the portion that should be disabled. When the CPU encounters the END statement, it assumes that is the end of the program. The following diagram shows an example. New END disables X10 and Y1
Normal Program X0
X2
X1
X3
Y0 X4
X0
X2
X1
X3
Y0 X4
Y1
X10
END
Y1
X10 END
END
PAUSE Instruction: This instruction provides a quick way to allow the inputs (or other logic) to operate while disabling selected outputs. The output image register is still updated, but the output circuits are not. For example, you could make this conditional by adding an input contact or CR to control the instruction with a switch or a programming device. Or, you could just add the instruction without any conditions so the selected outputs would be disabled at all times. PAUSE disables Y0 and Y1
Normal Program X0
X2
X1
X3
Y0
Y0 – Y1 PAUSE
X10
X4 Y1
X0
X2
X1
X3
X10
Y0 X4 Y1
END
END
STOP Instruction: Sometimes during machine startup you need a way to quickly turn off all the outputs and return to Program Mode. You can use the STOP instruction. When this instruction is executed the CPU automatically exits Run Mode and enters Program Mode. Remember, all outputs are turned off during Program Mode. The following diagram shows an example of a condition that returns the CPU to Program Mode.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 168
Chapter 9: Maintenance and Troubleshooting STOP puts CPU in Program Mode
Normal Program X0
X2
X1
X3
Y0
1 2 3 4 In the example shown above, you could trigger X7 which would execute the STOP instruction. The CPU would enter Program Mode and all outputs would be turned off. 5 Duplicate Reference Check 6 You can also check for multiple uses of the same output coil. Both programming devices offer a way to check for this condition.. For example, you can AUX 21, CHECK PROGRAM to check for duplicate references from a Handheld Programmer, or you can use the PLC 7 Diagnostics menu option within DirectSOFT 5. The following example shows how to perform the duplicate reference check with a Handheld Programmer. 8 Use AUX 21 to perform syntax check AUX 21 CHECK PRO 9 1:SYN 2:DUP REF 10 Select duplicate reference check (You may not get the busy BUSY display if the program is not 11 very long.) 12 One of two displays will appear $00024 E471 Error Display (example) 13 DUP COIL REF (shows location in question) 14 NO DUP REFS Syntax OK display ? A If you get an error, just press CLR and the Handheld will display the instruction where the B error occurred. Correct the problem and continue running the Duplicate Reference check until no duplicate references are found. C NOTE: You can use the same coil in more than one location, especially in programs containing Stage instructions and / or OROUT instructions. The Duplicate Reference check will find occurrences, even though D they are acceptable. X7
ST OP
X4
Y1
X5
X0
X2
X1
X3
X5
Y0
X4
Y1
END
END
CLR
C
B
2
1
AUX
ENT
ENT
DL06 Micro PLC User Manual, 3rd Edition Rev. A
9–13
Page 169
Chapter 9: Maintenance and Troubleshooting
Run Time Edits
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 9–14
The DL06 Micro PLC allows you to make changes to the application program during Run Mode. These edits are not “bumpless.” Instead, CPU scan is momentarily interrupted (and the outputs are maintained in their current state) until the program change is complete. This means if the output is off, it will remain off until the program change is complete. If the output is on, it will remain on. WARNING: Only authorized personnel fully familiar with all aspects of the application should make changes to the program. Changes during Run Mode become effective immediately. Make sure you thoroughly consider the impact of any changes to minimize the risk of personal injury or damage to equipment. There are some important operational changes during Run Time Edits. 1. If there is a syntax error in the new instruction, the CPU will not enter the Run Mode. 2. If you delete an output coil reference and the output was on at the time, the output will remain on until it is forced off with a programming device. 3. Input point changes are not acknowledged during Run Time Edits, so, if you’re using a highspeed operation and a critical input comes on, the CPU may not see the change.
Not all instructions can be edited during a Run Time Edit session. The following list shows the instructions that can be edited. Mnemonic TMR TMRF TMRA TMRAF CNT UDC SGCNT STR, STRN AND, ANDN OR, ORN STRE, STRNE ANDE, ANDNE ORE, ORNE STR, STRN AND, ANDN
Description Timer Fast timer Accumulating timer Accumulating fast timer Counter Up / Down counter Stage counter Store, Store not (Boolean) And, And not (Boolean) Or, Or not (Boolean) Store equal, Store not equal And equal, And not equal Or equal, Or not equal Store greater than or equal Store less than (Comparative Boolean) And greater than or equal And less than (Comparative Boolean)
Mnemonic OR, ORN LD LDD ADDD SUBD MUL DIV CMPD ANDD ORD XORD LDF OUTF SHFR SHFL NCON
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Description Or greater than or equal or less than (Comparative Boolean) Load data (constant) Load data double (constant) Add data double (constant) Subtract data double (constant) Multiply (constant) Divide (constant) Compare accumulator (constant) And accumulator (constant) Or accumulator (constant) Exclusive or accumulator (constant) Load discrete points to accumulator Output accumulator to discrete points Shift accumulator right Shift accumulator left Numeric constant