Spec sheet · AutomationDirect
AutomationDirect PX-901 Spec Sheet
Spec sheet4 pagesPDF 4.7 MB
All 4 pages are below, each with its text.
Covers · 1 model
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
AutomationDirect catalog pages for the Protos X PX-901 Bus End Terminal and the PX-902 Bus Expansion End Terminal, followed by general installation pages for the Protos X system. They give the terminal specifications, how units snap onto and come off the DIN rail, the spacing and dimensions, and the five basic terminal types.
- What it is
- Protos X bus end terminal, fitted at the end of a terminal assembly; required for I/O bus communication p. 1
- Terminal type
- Type 3: does not pass the terminal power bus or PE, and interrupts both p. 1, 4
- Current draw
- None from the I/O bus p. 1
- Isolation
- 500Vms (I/O bus/signal voltage) p. 1
- Mounting
- 35mm DIN rail, no orientation restrictions p. 3
- Terminals per coupler
- Up to 64 bus terminals per bus coupler, including the bus end terminal p. 2
- Bus connection
- Six slide contacts on the upper right side of each unit p. 2
- Expansion
- PX-902: takes the place of a PX-901 at the end of a PX-MOD or PX-TCP1 assembly and links to a PX-903 by RJ45 p. 1
What this sheet walks you through
- Snapping a bus coupler and bus terminals onto DIN rail p. 2
- Removing a bus coupler or bus terminal from the rail p. 2
- Wiring the spring clamp terminals p. 2
- Terminal dimensions and spacing for airflow p. 3
- The five terminal types and how they pass the power bus and PE p. 4
Good to know
- Units cannot be joined by sliding them together along the DIN rail; each is pressed gently onto the rail until it snaps on. p. 2
- A type 3 terminal such as the PX-901 interrupts the terminal power bus and PE. p. 1, 4
- Units need minimum spacing around them for cooling airflow. p. 3
Questions this sheet answers
What does the PX-901 do?
It is the bus end terminal installed at the end of a Protos X terminal assembly, and it is required for proper I/O bus communication. p. 1
Does the PX-901 draw current from the I/O bus?
No, its current consumption from the I/O bus is listed as none. p. 1
How do I expand a Protos X assembly that ends in a PX-901?
A PX-902 Bus Expansion End Terminal goes at the end of a PX-MOD or PX-TCP1 assembly instead, and connects by RJ45 to a PX-903 Bus Expansion Coupler Terminal. p. 1
How many terminals can one Protos X bus coupler take?
Up to 64 bus terminals, counting the bus end terminal. p. 2
How do I remove a Protos X terminal from the DIN rail?
Pull the orange DIN rail release tab firmly to unlatch it; if it is attached to other units, slide it forward until it is released. p. 2
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
For the latest prices, please check AutomationDirect.com.
Bus End/Expansion Terminals PX-901 $13.00 Bus End Terminal
PX-901 Terminal Specifications Current Consumption None (from I/O Bus) Electrical Isolation
500Vms (I/O bus/signal voltage)
PX-901 General Specifications Operating Temp Storage Temp Relative Humidity Environment Air Mounting/Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*
PX-901
The PX-901 (type 3) Bus End Terminal is installed at the end of a terminal assembly and is required for proper I/O Bus communication.
PX-902 $55.00 Bus Expansion End Terminal
32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN61000-6-4 IP20 50g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in) Yes
Yes No No UL/cUL File No. E157382, CE
- obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.
PX-902 Terminal Specifications Power Source
I/O Bus power (approx. 6V)
Current Consumption 70mA (from I/O Bus) Electrical Isolation
500Vms (I/O bus/field potential)
Heat Dissipation Status Indicators Number of Expansion Coupler Terminals Supported Configuration Maximum Distance Between Each Expansion Coupler Connection Type
1W max None
Recommended Cable Placement PX-902
The PX-902 (type 3) Bus Expansion End Terminal enables expansion of terminal assemblies. The PX-902 is installed at the end of a PX-MOD or PX-TCP1 assembly and connects the I/O Bus to a PX-903 Bus Expansion Coupler Terminal via the RJ45 port. No configuration is required.
www.automationdirect.com/fieldIO
31 max. (Using PX-903) Automatic 16.5 ft. (5m) Ethernet, RJ45 Shielded, Twisted Pair, Cat5e Used only with Bus Coupler, replaces a PX-901 End Terminal
PX-902 General Specifications Operating Temp Storage Temp Relative Humidity Environment Air Mounting/Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*
32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None Conforms to EN 60068-2-6 Conforms to EN 60068-2-27 Conforms to EN 61000-6-2 IP20 146g 27.5 x 100 x 68.8 mm (1.08 x 3.94 x 2.71 in) Yes
Yes No No UL/cUL File No. E157382, CE
- obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.
Universal Field I/O
tFED-27
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
For the latest prices, please check AutomationDirect.com.
System Installation and Removal Bus Coupler and Bus Terminal Installation Bus Coupler Installation:
2
1. a Bus Coupler by snapping it onto 35mm DIN rail and securing it into position using the DIN rail locking wheel (where applicable) located on the left side of the coupler.
Insert unit using tongue and groove molded guide and press gently until it becomes firmly seated on DIN rail. Where applicable, rotate Locking Wheel to lock Bus Coupler
Bus Terminal Installation: 2. To add a bus terminal, insert unit onto right side of Bus Coupler using the tongue and groove at the top and bottom of the unit, pressing gently until it snaps onto the DIN rail. A proper connection cannot be made by sliding the units together on the DIN rail. When correctly installed, no significant gap can be seen between the attached units. Bus connection is made through the six slide contacts located on the upper right side of the units. Add up to 64 bus terminals per Bus Coupler, including a bus end terminal.
1
Align tab with molded guide
Wiring Connections Wire connection is made through a spring clamp style terminal. This terminal is designed for a single-conductor solid or stranded wire. Wire connection is made by firmly pushing the screwdriver into the screwdriver slot, inserting the wire into the wire slot and removing the screwdriver, locking the wire into position. Screwdriver Slot Wire Slot
Removing Bus Coupler and Bus Terminals
Wiring Specifications Connection Type
Spring Clamp Terminals
Wire Gauge
28–14 AWG (0.08–2.5 mm2)
Screwdriver Width
2.5 mm (0.10 in) such as P/N TW-SD-MSL-2
Wire Stripping Length
8mm
- For Thermocouple terminals, thermocouple extension wire is recommended
Where applicable, rotate Locking Wheel to unlock Bus Coupler
A locking mechanism prevents individual units from being pulled off. For bus terminal removal, pull the orange DIN rail release tab firmly to unlatch the unit from the rail. If attached to other terminal units, slide unit forward until released. For Bus Couplers with locking wheels, release the DIN rail locking wheel, then pull firmly on DIN rail release tab.
Firmly pull DIN Rail Release Tab to unlatch unit from rail.
tFED-24Universal Field I/O1-800-633-0405
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
For the latest prices, please check AutomationDirect.com.
Installation Considerations Terminal Dimensions and Spacing Requirements
1.4” 35mm min
Use the following diagrams to make sure the Protos X system can be installed in your application. Protos X terminals require 35mm DIN rail for mounting; there are no orientation restrictions.
0.8” 20mm min 0.8” 20mm min
1.4” 35mm min
To ensure proper airflow for cooling purposes, units should be spaced, at a minimum, as shown. It is also important to check the Protos X dimensions against the conditions required for your application.
1.4” 35mm min
1.4” 35mm min
See the Enclosures section for an enclosure that may be suitable for your application
PX-TCP2
PX-TCP1 / PX-MOD /PX-EIP1
PX-903PX-902Standard TerminalEthernet TCP/IP COM1 2 3 4ERROR WDG24V 0V24V 0V Us GNDs100 mm [3.94”]I/O RUN I/O ERR515Up2626GNDp37374848TMDIP1 2 3 4 5 6 7 8PE PEPE PE.PE1 2ON51 mm [2.01”]100 mm [3.94”]+ +ON
1 2 3 4 5 6 7 8 9 10 ON
PX-TCP21+ +44 mm [1.73”]PX-TCP1PX-90324.5 mm [.96”]
www.automationdirect.com/fieldIO
PX-90227.5 mm [.96”]12 mm [.47”]68.8 mm [2.71”]Universal Field I/OtFED-25
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
For the latest prices, please check AutomationDirect.com.
Installation Considerations Terminal Types
8
TYPE 2
Terminal power bus contact Terminal power bus contact
15263748TYPE 3I/O Bus contactsI/O Bus contacts
Terminal power bus pass through
Terminal power bus contact
Terminal power bus pass through
Terminal power bus contact Terminal PE bus contact
Type 1: This terminal passes the terminal power bus from the preceding terminal to the next terminal and therefore it must be mounted to a preceding terminal that passes bus power.
15263748
Terminal power bus pass through Terminal power bus pass through Terminal PE bus pass through
Type 2: This terminal passes the terminal power bus and PE from the preceding terminal to the next terminal and therefore it must be preceded by a terminal that passes both terminal power bus and PE.
TYPE 4I/O Bus contactsI/O B conta1515262637483748
Note, bus contacts do not exist on this module
Note, bus and pass through contacts do not exist on this module
Type 3: This terminal does not pass the terminal power bus or PE and can be preceded by any terminal, however it will interrupt the terminal power bus and PE.
Five Basic Terminal Types
PX-970TYPE 3I/O Bus contactsI/O Bus contacts
Terminal power bus pass through Terminal power bus pass through Terminal PE bus pass through
inal passes the us and PE from the al to the next termiit must be precedhat passes both us and PE.
TYPE 41515262637483748
Note, bus contacts do not exist on this module
Note, bus and pass through contacts do not exist on this module
Type 3: This terminal does not pass the terminal power bus or PE and can be preceded by any terminal, however it will interrupt the terminal power bus and PE.
tFED-26Universal Field I/OTYPE 5I/O Bus contactsPX-970I/O Bus contacts
Terminal power bus supply Terminal power bus supply
Terminal power bus supply
Type 4: This terminal requires external voltage connection and supplies the terminal power bus to terminals located to its right. The terminals to its right must support the same power bus of 120/230 VAC or 24VDC. This terminal will not pass terminal power or PE from any preceding terminals.
Termi power bus suTermi power bus suTermi power bus su
Type 4: This terminal requires exte nal voltage connection and supplie the terminal power bus to terminal located to its right. The terminals t right must support the same powe bus of 120/230 VAC or 24VDC. Th terminal will not pass terminal pow or PE from any preceding terminal
Protos XTM is a trademark of Automationdirect.com Incorporated
57TMTYPE 1PE 26
Protos X Five Basic Terminal Ty
Note, bus and pass through contacts do not exist on this module
Type 5: This terminal is used to separate the terminal power bus and PE from other terminals and can mounted next to any terminal.