Page 101

Troubleshooting

Chapter

5

In This Chapter... Diagnostic LEDs.......................................................................................................... 5–2 Fieldbus Errors.......................................................................................................... 5–15 Watchdog Enable/Activate. ..................................................................................... 5–17 Resetting Watchdog Errors...................................................................................... 5–18 Protos X Configuration Software Troubleshooting................................................ 5–32

Page 102

Chapter 5: Troubleshooting

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Diagnostic LEDs

5–2

All Protos X Bus Couplers have LED lights which can be used to troubleshoot errors. For instance, the I/O BUS Diagnostics LEDs will indicate the status of the bus terminals and their connections. The green LED will light up in order to indicate a fault-free operation. The red LED will blink with two different frequencies to indicate an error. The error is encoded in the blinks as follows: Blink Code Fast Blinking

Start of the Error Code

First Slow Sequence Second Slow Sequence

Error Code Error Code Argument

Below is an example of an I/O Error showing Error Code 6 (Bus Coupler Error) and Error Argument 4 (DIP Switch incorrect for Boot IP) from Terminal Bus Coupler PX-TCP2.

Below is an example of an I/O Error showing Error Code 4 (I/O Bus Data Error) and Error Argument 1 (Break behind bus terminal n, in this case number 1) from Terminal Bus Coupler PX-TCP2.

Protos X Installation and I/O Manual, 1st Edition, Rev. D

Page 103

Chapter 5: Troubleshooting

PX-TCP2 Diagnostics LEDs a. Power Supply Diagnostic LEDs PX-TCP2 Power Supply Diagnostic LEDs LED Meaning No Bus Coupler power Left LED = OFF Right LED = OFF No 24VDC Terminal Bus Power

Protos X Installation and I/O Manual, 1st Edition, Rev. D

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–3

Page 104

Chapter 5: Troubleshooting b. Ethernet Diagnostics LEDs

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–4

PX-TCP2 Ethernet Diagnostic LEDs LED

ON

OFF

COM

ON/Flashing = data received No data received The LED flashes slowly if DHCP or BootP is active but the Bus Coupler has not yet received an IP Address

ERROR

The LED flashes rapidly (5 times, only when switching ON); the Bus Coupler is addressed with ARP The settings on the DIP Switch are not valid

No error

WDG

Watchdog is active (No error)

Watchdog error or no communication (start communication or reset WD error)

c. I/O Bus Diagnostics LEDs PX-TCP2 I/O Bus Diagnostic LEDs LED

Meaning

I/O RUN

ON or Flashing: I/O Bus Running

I/O ERR

Flashing: See error codes below

PX-TCP2 Error Codes for I/O Bus Diagnostics Error Code

Error Code Description Argument

Persistent, continuous blinking

1 Pulse

EMC Problems

0

EEPROM Checksum Error

1

Code Buffer Overflow

2

Unknown Data type

Remedy • Power Supply for over-voltage peaks • Implement EMC measures • I/O Bus Error is present, it can be localized by a restart of the Coupler (switching it OFF and then ON again) • ADC Returns Department at (800) 633-0405 • fewer Bus Terminals, the programmed configuration has too many entries in the table • ADC Returns Department at (800) 633-0405

Protos X Installation and I/O Manual, 1st Edition, Rev. D

Page 105

Chapter 5: Troubleshooting PX-TCP2 Error Codes for I/O Bus Diagnostics Error Code

Error Code Description Argument 0

2 Pulses n(n>0)

3 Pulses

0

0

4 Pulses n

5 Pulses n 0 1

6 Pulses

2 4 8

Remedy

Programmed Configuration has • programmed configuration for an incorrect entry Table comparison (Bus Terminal (n))

correctness • Incorrect table entry

• No Bus Terminal inserted • of the Bus Terminals is defective; remove half of the Bus Terminals I/O Bus Command Error attached and check whether the error is still present with the remaining Bus Terminals. Repeat until the defective Bus Terminal is located • whether the n+1 Bus Terminal I/O Bus Data Error, break is correctly connected ; replace if behind the Bus Coupler necessary Break behind Bus Terminal (n) • whether the Bus End Terminal PX-901 is connected I/O Bus Error in register communication with Bus Terminal (n)

Exchange the nth Bus Terminal

Error at installation

• Internal Data Error • Exchange Bus Coupler • D IP Switch changed after a • a hardware reset on the Bus software reset Coupler (switch OFF and ON again) Other device with this IP • Change the IP Address Address in the network • Set 1-8 to ON or OFF, see BootIP DIP Switch incorrect for BootIP • a hardware reset on the Bus Coupler (switch OFF and ON again) Internal Data Error

16

Error in IP socket

14 Pulses n nth Bus Terminals is no longer Start the Bus Coupler again, if the Error occurs again, then exchange the Bus correct

15 Pulses n

16 Pulses n

Terminal Check the number of terminals for Bus Number of Bus Terminals is no Coupler assembly to make sure the longer correct maximum number of terminals has not been exceeded Length of the I/O Bus data is no longer correct

Check the amount of bytes consumed by terminals to make sure the 512 bytes Input and 512 bytes output has not been exceeded d. Switch Diagnostics LEDs PX-TCP2 Switch Diagnostic LEDs LED

ON

Flashing

OFF

LINK/ACT

Link is OK

Communication OK

No Link

10/100 Baud 100 MBaud

-

10 MBaud

Protos X Installation and I/O Manual, 1st Edition, Rev. D

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–5

Page 106

Chapter 5: Troubleshooting

PX-TCP1 Diagnostics LEDs

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–6 a. Us/Up LEDs PX-TCP1 Power Supply Diagnostic LEDs LED (Power LEDs) Meaning OFF: No Bus Coupler 24VDC Power LED Us Power LED Up

OFF: No Terminal Power Bus 24VDC b. I/O Bus Diagnostics LEDs PX-TCP1 I/O Bus Diagnostic LEDs LED (I/O Bus) I/O Bus RUN

Meaning ON or Flashing: I/O Bus Running

I/O Bus ERR

Flashing: See error codes on following page

Protos X Installation and I/O Manual, 1st Edition, Rev. D

Page 107

Chapter 5: Troubleshooting PX-TCP1 Error Codes for I/O Bus Diagnostics Error Code

-

1 Pulse

Error Code Description Argument Flashing EMC Problems Continuously

0

EEPROM Checksum Error

1

Code Buffer Overflow

Remedy • Power Supply for over-voltage peaks • Implement EMC measures • I/O Bus Error is present, it can be localized by a restart of the Coupler (switching it OFF and then ON again) • ADC Returns Department at (800) 633-0405 • fewer Bus Terminals, the programmed configuration has too many entries in the table • ADC Returns Department at (800) 633-0405

2

Unknown Data type

2 Pulses

-

Reserve

3 Pulses

0

I/O Bus Command Error

0

I/O Bus Data Error, break behind the Bus Coupler n

Break behind Bus Terminal (n)

n 0

I/O Bus Error in register communication with Bus Terminal (n) Error at installation

1

Internal Data Error

2

DIP Switch changed after a software reset

0

Cycle Time was exceeded

0

Checksum Error in Flash program

1

Incorrect or faulty library implemented

• Transmit program to the Coupler again • Remove the faulty library

10 Pulses n

Bust Terminal n is not consistent with the configuration that existed when the boot project was created

Check the nth Bus Terminal. The boot project must be deleted if the insertion of an nth Bus Terminal is intentional

14 Pulses n nth Bus Terminals has the wrong format

Start the Bus Coupler again, if the Error occurs again, then exchange the Bus Terminal

15 Pulses n

Number of Bus Terminals is no longer correct

Check the number of terminals for Bus Coupler assembly to make sure the maximum number of terminals has not been exceeded

4 Pulses 5 Pulses 6 Pulses

7 Pulses

9 Pulses

• No Bus Terminal inserted • of the Bus Terminals is defective; remove half of the Bus Terminals attached and check whether the error is still present with the remaining Bus Terminals. Repeat until the defective Bus Terminal is located • whether the n+1 Bus Terminal is correctly connected ; replace if necessary • whether the Bus End Terminal PX-901 is connected Exchange the nth Bus Terminal

• Exchange Bus Coupler • a hardware reset on the Bus Coupler (switch OFF and ON again) Warning: The set cycle time was exceeded. This indication (flashing LEDs) can only be cleared by booting the Bus Coupler again Remedy: Increase the cycle time

Protos X Installation and I/O Manual, 1st Edition, Rev. D

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–7

Page 108

Chapter 5: Troubleshooting

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–8 c. WD/COM/Error LEDs PX-TCP1 Ethernet Diagnostic LEDs LED (Ethernet)

Meaning

WD ERR

ON: Watchdog Error

COM

ON or Flashing: communication with controller

ERROR

Flashing: DHCP or BootP active, waiting for an IP Address

RTE

ON: Hard real time is switched ON at TC. No ADS communication is possible at the same time . All TCP, UDP and ICMP telegrams (e.g., ping) will not be answered

LINK/ACT

ON: LINK available Flashing: LINK available and communicating

Protos X Installation and I/O Manual, 1st Edition, Rev. D

Page 109

Chapter 5: Troubleshooting

PX-EIP1 Diagnostics LEDs Us

EIP ERR 1 5 EIP RUN 2 6 3 7 DIAG ERR 4 8

DIAG RUN

Up I/O BUS RUN

24V 0V

LINK/ACT

1 2 3 4

I/O BUS ERR

5 6 7 8

Us GNDs

Up

GNDp

TM

.PE

PX-TCP1 a. Us/Up LEDs PX-EIP1 Power Supply Diagnostic LEDs LED (Power LEDs) Meaning OFF: No Bus Coupler 24VDC Power LED Us Power LED Up

OFF: No Terminal Power Bus 24VDC b. I/O Bus Diagnostics LEDs PX-EIP1 I/O Bus Diagnostic LEDs LED (I/O Bus) I/O Bus RUN

ON or Flashing: I/O Bus Running

Meaning

I/O Bus ERR

Flashing: See error codes on following page

Protos X Installation and I/O Manual, 1st Edition, Rev. D

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–9

Page 110

Chapter 5: Troubleshooting

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–10

PX-EIP1 Error Codes for I/O Bus Diagnostics Error Code

-

1 Pulse

Error Code Description Argument Flashing EMC Problems Continuously

0

EEPROM Checksum Error

1

Code Buffer Overflow

Remedy • Power Supply for over-voltage peaks • Implement EMC measures • I/O Bus Error is present, it can be localized by a restart of the Coupler (switching it OFF and then ON again) • ADC Returns Department at (800) 633-0405 • fewer Bus Terminals, the programmed configuration has too many entries in the table • ADC Returns Department at (800) 633-0405

2

Unknown Data type

2 Pulses

-

Reserved

3 Pulses

0

I/O Bus Command Error

0

I/O Bus Data Error, break behind the Bus Coupler n

Break behind Bus Terminal (n)

n 0

I/O Bus Error in register communication with Bus Terminal (n) Error at installation

1

Internal Data Error

2

DIP Switch changed after a software reset

0

Cycle Time was exceeded

0

Checksum Error in Flash program

1

Incorrect or faulty library implemented

• Transmit program to the Coupler again • Remove the faulty library

10 Pulses n

Bust Terminal n is not consistent with the configuration that existed when the boot project was created

Check the nth Bus Terminal. The boot project must be deleted if the insertion of an nth Bus Terminal is intentional

14 Pulses n nth Bus Terminals has the wrong format

Start the Bus Coupler again, if the Error occurs again, then exchange the Bus Terminal

15 Pulses n

Number of Bus Terminals is no longer correct

Check the number of terminals for Bus Coupler assembly to make sure the maximum number of terminals has not been exceeded

4 Pulses 5 Pulses 6 Pulses

7 Pulses

9 Pulses

• No Bus Terminal inserted • of the Bus Terminals is defective; remove half of the Bus Terminals attached and check whether the error is still present with the remaining Bus Terminals. Repeat until the defective Bus Terminal is located • whether the n+1 Bus Terminal is correctly connected ; replace if necessary • whether the Bus End Terminal PX-901 is connected Exchange the nth Bus Terminal

• Exchange Bus Coupler • a hardware reset on the Bus Coupler (switch OFF and ON again) Warning: The set cycle time was exceeded. This indication (flashing LEDs) can only be cleared by booting the Bus Coupler again Remedy: Increase the cycle time

Protos X Installation and I/O Manual, 1st Edition, Rev. D