Page 101
Troubleshooting
Chapter
5
In This Chapter... Diagnostic LEDs.......................................................................................................... 5–2 Fieldbus Errors.......................................................................................................... 5–15 Watchdog Enable/Activate. ..................................................................................... 5–17 Resetting Watchdog Errors...................................................................................... 5–18 Protos X Configuration Software Troubleshooting................................................ 5–32
Page 102
Chapter 5: Troubleshooting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Diagnostic LEDs
5–2
All Protos X Bus Couplers have LED lights which can be used to troubleshoot errors. For instance, the I/O BUS Diagnostics LEDs will indicate the status of the bus terminals and their connections. The green LED will light up in order to indicate a fault-free operation. The red LED will blink with two different frequencies to indicate an error. The error is encoded in the blinks as follows: Blink Code Fast Blinking
Start of the Error Code
First Slow Sequence Second Slow Sequence
Error Code Error Code Argument
Below is an example of an I/O Error showing Error Code 6 (Bus Coupler Error) and Error Argument 4 (DIP Switch incorrect for Boot IP) from Terminal Bus Coupler PX-TCP2.
Below is an example of an I/O Error showing Error Code 4 (I/O Bus Data Error) and Error Argument 1 (Break behind bus terminal n, in this case number 1) from Terminal Bus Coupler PX-TCP2.
Protos X Installation and I/O Manual, 1st Edition, Rev. D
Page 103
Chapter 5: Troubleshooting
PX-TCP2 Diagnostics LEDs a. Power Supply Diagnostic LEDs PX-TCP2 Power Supply Diagnostic LEDs LED Meaning No Bus Coupler power Left LED = OFF Right LED = OFF No 24VDC Terminal Bus Power
Protos X Installation and I/O Manual, 1st Edition, Rev. D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–3
Page 104
Chapter 5: Troubleshooting b. Ethernet Diagnostics LEDs
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–4
PX-TCP2 Ethernet Diagnostic LEDs LED
ON
OFF
COM
ON/Flashing = data received No data received The LED flashes slowly if DHCP or BootP is active but the Bus Coupler has not yet received an IP Address
ERROR
The LED flashes rapidly (5 times, only when switching ON); the Bus Coupler is addressed with ARP The settings on the DIP Switch are not valid
No error
WDG
Watchdog is active (No error)
Watchdog error or no communication (start communication or reset WD error)
c. I/O Bus Diagnostics LEDs PX-TCP2 I/O Bus Diagnostic LEDs LED
Meaning
I/O RUN
ON or Flashing: I/O Bus Running
I/O ERR
Flashing: See error codes below
PX-TCP2 Error Codes for I/O Bus Diagnostics Error Code
Error Code Description Argument
Persistent, continuous blinking
1 Pulse
EMC Problems
0
EEPROM Checksum Error
1
Code Buffer Overflow
2
Unknown Data type
Remedy • Power Supply for over-voltage peaks • Implement EMC measures • I/O Bus Error is present, it can be localized by a restart of the Coupler (switching it OFF and then ON again) • ADC Returns Department at (800) 633-0405 • fewer Bus Terminals, the programmed configuration has too many entries in the table • ADC Returns Department at (800) 633-0405
Protos X Installation and I/O Manual, 1st Edition, Rev. D
Page 105
Chapter 5: Troubleshooting PX-TCP2 Error Codes for I/O Bus Diagnostics Error Code
Error Code Description Argument 0
2 Pulses n(n>0)
3 Pulses
0
0
4 Pulses n
5 Pulses n 0 1
6 Pulses
2 4 8
Remedy
Programmed Configuration has • programmed configuration for an incorrect entry Table comparison (Bus Terminal (n))
correctness • Incorrect table entry
• No Bus Terminal inserted • of the Bus Terminals is defective; remove half of the Bus Terminals I/O Bus Command Error attached and check whether the error is still present with the remaining Bus Terminals. Repeat until the defective Bus Terminal is located • whether the n+1 Bus Terminal I/O Bus Data Error, break is correctly connected ; replace if behind the Bus Coupler necessary Break behind Bus Terminal (n) • whether the Bus End Terminal PX-901 is connected I/O Bus Error in register communication with Bus Terminal (n)
Exchange the nth Bus Terminal
Error at installation
• Internal Data Error • Exchange Bus Coupler • D IP Switch changed after a • a hardware reset on the Bus software reset Coupler (switch OFF and ON again) Other device with this IP • Change the IP Address Address in the network • Set 1-8 to ON or OFF, see BootIP DIP Switch incorrect for BootIP • a hardware reset on the Bus Coupler (switch OFF and ON again) Internal Data Error
16
Error in IP socket
14 Pulses n nth Bus Terminals is no longer Start the Bus Coupler again, if the Error occurs again, then exchange the Bus correct
15 Pulses n
16 Pulses n
Terminal Check the number of terminals for Bus Number of Bus Terminals is no Coupler assembly to make sure the longer correct maximum number of terminals has not been exceeded Length of the I/O Bus data is no longer correct
Check the amount of bytes consumed by terminals to make sure the 512 bytes Input and 512 bytes output has not been exceeded d. Switch Diagnostics LEDs PX-TCP2 Switch Diagnostic LEDs LED
ON
Flashing
OFF
LINK/ACT
Link is OK
Communication OK
No Link
10/100 Baud 100 MBaud
-
10 MBaud
Protos X Installation and I/O Manual, 1st Edition, Rev. D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–5
Page 106
Chapter 5: Troubleshooting
PX-TCP1 Diagnostics LEDs
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–6 a. Us/Up LEDs PX-TCP1 Power Supply Diagnostic LEDs LED (Power LEDs) Meaning OFF: No Bus Coupler 24VDC Power LED Us Power LED Up
OFF: No Terminal Power Bus 24VDC b. I/O Bus Diagnostics LEDs PX-TCP1 I/O Bus Diagnostic LEDs LED (I/O Bus) I/O Bus RUN
Meaning ON or Flashing: I/O Bus Running
I/O Bus ERR
Flashing: See error codes on following page
Protos X Installation and I/O Manual, 1st Edition, Rev. D
Page 107
Chapter 5: Troubleshooting PX-TCP1 Error Codes for I/O Bus Diagnostics Error Code
-
1 Pulse
Error Code Description Argument Flashing EMC Problems Continuously
0
EEPROM Checksum Error
1
Code Buffer Overflow
Remedy • Power Supply for over-voltage peaks • Implement EMC measures • I/O Bus Error is present, it can be localized by a restart of the Coupler (switching it OFF and then ON again) • ADC Returns Department at (800) 633-0405 • fewer Bus Terminals, the programmed configuration has too many entries in the table • ADC Returns Department at (800) 633-0405
2
Unknown Data type
2 Pulses
-
Reserve
3 Pulses
0
I/O Bus Command Error
0
I/O Bus Data Error, break behind the Bus Coupler n
Break behind Bus Terminal (n)
n 0
I/O Bus Error in register communication with Bus Terminal (n) Error at installation
1
Internal Data Error
2
DIP Switch changed after a software reset
0
Cycle Time was exceeded
0
Checksum Error in Flash program
1
Incorrect or faulty library implemented
• Transmit program to the Coupler again • Remove the faulty library
10 Pulses n
Bust Terminal n is not consistent with the configuration that existed when the boot project was created
Check the nth Bus Terminal. The boot project must be deleted if the insertion of an nth Bus Terminal is intentional
14 Pulses n nth Bus Terminals has the wrong format
Start the Bus Coupler again, if the Error occurs again, then exchange the Bus Terminal
15 Pulses n
Number of Bus Terminals is no longer correct
Check the number of terminals for Bus Coupler assembly to make sure the maximum number of terminals has not been exceeded
4 Pulses 5 Pulses 6 Pulses
7 Pulses
9 Pulses
• No Bus Terminal inserted • of the Bus Terminals is defective; remove half of the Bus Terminals attached and check whether the error is still present with the remaining Bus Terminals. Repeat until the defective Bus Terminal is located • whether the n+1 Bus Terminal is correctly connected ; replace if necessary • whether the Bus End Terminal PX-901 is connected Exchange the nth Bus Terminal
• Exchange Bus Coupler • a hardware reset on the Bus Coupler (switch OFF and ON again) Warning: The set cycle time was exceeded. This indication (flashing LEDs) can only be cleared by booting the Bus Coupler again Remedy: Increase the cycle time
Protos X Installation and I/O Manual, 1st Edition, Rev. D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–7
Page 108
Chapter 5: Troubleshooting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–8 c. WD/COM/Error LEDs PX-TCP1 Ethernet Diagnostic LEDs LED (Ethernet)
Meaning
WD ERR
ON: Watchdog Error
COM
ON or Flashing: communication with controller
ERROR
Flashing: DHCP or BootP active, waiting for an IP Address
RTE
ON: Hard real time is switched ON at TC. No ADS communication is possible at the same time . All TCP, UDP and ICMP telegrams (e.g., ping) will not be answered
LINK/ACT
ON: LINK available Flashing: LINK available and communicating
Protos X Installation and I/O Manual, 1st Edition, Rev. D
Page 109
Chapter 5: Troubleshooting
PX-EIP1 Diagnostics LEDs Us
EIP ERR 1 5 EIP RUN 2 6 3 7 DIAG ERR 4 8
DIAG RUN
Up I/O BUS RUN
24V 0V
LINK/ACT
1 2 3 4
I/O BUS ERR
5 6 7 8
Us GNDs
Up
GNDp
TM
.PE
PX-TCP1 a. Us/Up LEDs PX-EIP1 Power Supply Diagnostic LEDs LED (Power LEDs) Meaning OFF: No Bus Coupler 24VDC Power LED Us Power LED Up
OFF: No Terminal Power Bus 24VDC b. I/O Bus Diagnostics LEDs PX-EIP1 I/O Bus Diagnostic LEDs LED (I/O Bus) I/O Bus RUN
ON or Flashing: I/O Bus Running
Meaning
I/O Bus ERR
Flashing: See error codes on following page
Protos X Installation and I/O Manual, 1st Edition, Rev. D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–9
Page 110
Chapter 5: Troubleshooting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–10
PX-EIP1 Error Codes for I/O Bus Diagnostics Error Code
-
1 Pulse
Error Code Description Argument Flashing EMC Problems Continuously
0
EEPROM Checksum Error
1
Code Buffer Overflow
Remedy • Power Supply for over-voltage peaks • Implement EMC measures • I/O Bus Error is present, it can be localized by a restart of the Coupler (switching it OFF and then ON again) • ADC Returns Department at (800) 633-0405 • fewer Bus Terminals, the programmed configuration has too many entries in the table • ADC Returns Department at (800) 633-0405
2
Unknown Data type
2 Pulses
-
Reserved
3 Pulses
0
I/O Bus Command Error
0
I/O Bus Data Error, break behind the Bus Coupler n
Break behind Bus Terminal (n)
n 0
I/O Bus Error in register communication with Bus Terminal (n) Error at installation
1
Internal Data Error
2
DIP Switch changed after a software reset
0
Cycle Time was exceeded
0
Checksum Error in Flash program
1
Incorrect or faulty library implemented
• Transmit program to the Coupler again • Remove the faulty library
10 Pulses n
Bust Terminal n is not consistent with the configuration that existed when the boot project was created
Check the nth Bus Terminal. The boot project must be deleted if the insertion of an nth Bus Terminal is intentional
14 Pulses n nth Bus Terminals has the wrong format
Start the Bus Coupler again, if the Error occurs again, then exchange the Bus Terminal
15 Pulses n
Number of Bus Terminals is no longer correct
Check the number of terminals for Bus Coupler assembly to make sure the maximum number of terminals has not been exceeded
4 Pulses 5 Pulses 6 Pulses
7 Pulses
9 Pulses
• No Bus Terminal inserted • of the Bus Terminals is defective; remove half of the Bus Terminals attached and check whether the error is still present with the remaining Bus Terminals. Repeat until the defective Bus Terminal is located • whether the n+1 Bus Terminal is correctly connected ; replace if necessary • whether the Bus End Terminal PX-901 is connected Exchange the nth Bus Terminal
• Exchange Bus Coupler • a hardware reset on the Bus Coupler (switch OFF and ON again) Warning: The set cycle time was exceeded. This indication (flashing LEDs) can only be cleared by booting the Bus Coupler again Remedy: Increase the cycle time
Protos X Installation and I/O Manual, 1st Edition, Rev. D