The text of a manual · part 2 of 14
Protos X Installation and I/O Manual, pages 11 to 20
Pages 11 to 20 of 138
The original document is the PDF (45 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect PX-901
Page 11
Getting Started
Chapter
1
In This Chapter... About This Manual..................................................................................................... 1–2 Conventions Used. ..................................................................................................... 1–3 Introduction. .............................................................................................................. 1–4 Protos X I/O System Components............................................................................. 1–5 Protos X I/O System Example ................................................................................... 1–7
Page 12
Chapter 1: Getting Started
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
About This Manual
1–2
The Purpose of this Manual
TM
This manual is written for the user of the Protos X line of I/O products. This manual shows you how to install and wire the equipment. It also provides specifications for the couplers, input and output modules.
Supplemental Manuals In some cases you may need an additional manual such as the master PLC User Manual or perhaps the manual for the PC-based control software you may be using.
Technical Support We strive to make our manuals the best in the industry. We rely on your feedback to let us know if we are reaching our goal. If you cannot find the solution to your particular application, or, if for any reason you need technical assistance, please call us at: 770–844–4200 Our technical support group will be pleased to work with you to answer your questions. They are available Monday through Friday from 9:00 A.M. to 6:00 P.M. Eastern Time. We also encourage you to visit our web site where you can find technical and non-technical information about our products and our company. http://www.automationdirect.com
Protos X Installation and I/O Manual, 1st Edition, Rev. D
Page 13
Chapter 1: Getting Started
Conventions Used
1 2 When you see the “exclamation mark” icon in the left-hand margin, the paragraph to its immediate right will be a warning. This information could prevent injury, loss of property, or even death (in extreme 3 cases). The word WARNING: in boldface will mark the beginning of the text. 4 5 Key Topics for Each Chapter C The beginning of each chapter will list the key topics 1 6 that can be found in that chapter. 7 8 9 10 11 12 13 14 A B C D When you see the “notepad” icon in the left-hand margin, the paragraph to its immediate right will be a special note. The word NOTE: in boldface will mark the beginning of the text.
Getting Started!
HAPTER
In This Chapter...
Introduction .............................................................................1-2 Purpose of this Manual ....................................................................1-2 About Getting Started! ......................................................................1-2 Supplemental Manuals and Other Help ............................................1-2 Technical Support .............................................................................1-2
Conventions Used ....................................................................1-3
Protos X Installation and I/O Manual, 1st Edition, Rev. D
1–3
Page 14
Chapter 1: Getting Started
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Introduction
1–4
The Protos X™ I/O system allows a user to install remote field I/O devices without having to invest in another PLC. The small footprint of the Protos X I/O system allows it to be installed in tight locations at or in the vicinity of the equipment it is monitoring and/or controlling. The multiple I/O count options give the user the ability to monitor/control just a few points to a couple hundred points depending on the number of terminals used. Communications to the bus couplers is done by Modbus communications. There are two Modbus TCP couplers (PX-TCP1 and PX-TCP2) and one RS-485 serial Modbus RTU\ASCII coupler ( PX-MOD). Modbus addressing for the Field I/O can be easily identified by using the Protos X configuration software PX-CFGSW. The Modbus addressing can then be used by any controller that can communicate via Modbus to read/write data to the Protos X I/O. To communicate using Ethernet an EtherNet/IP coupler (PX-EIP1) is available. This performs as an EtherNet/IP server in a EtherNet/IP network. Communication to the client is via an RJ45 Ethernet port. The maximum distance from client to the PX-EIP1 is 330 feet (100 meters) using 24AWG shielded, twisted pair Cat5e cable. It is highly recommended that a dedicated network be used for the Protos X system. As shown below, the Protos X I/O system is a modular, field I/O system consisting of a Bus Coupler and its associated input/output Terminals. The Protos X field I/O series offers: • 2, 4, 8, and 16-point discrete I/O terminals • 2, 4 and 8-channel analog I/O terminals • Bus Couplers that utilize the Modbus protocol with Modbus RTU/ASCII and Modbus TCP option • An EtherNet/IP Bus Coupler that communicates via EtherNet/IP network • Bus expansion terminals for expansion up to 255 I/O terminals per specific Bus Couplers • And a variety of power supply options.
Protos X Installation and I/O Manual, 1st Edition, Rev. D
Page 15
Chapter 1: Getting Started
Protos X I/O System Components
1 Bus Couplers are available in four configurations. The PX-MOD provides EtherNet/IP or Modbus RTU/ASCII over RS485. The PX-EIP1 offers EtherNet/IP. The PX-TCP1 and 2 PX-TCP2 modules offer Modbus TCP over Ethernet. The PX-TCP2 provides an additional port which can act as a switch to other couplers of the same type. 3 I/O Terminals There are twelve discrete input and output terminals available offering 2 points, 4 points, 8 4 points or 16 points per terminal and include AC, DC and relay form factors. There are also eighteen analog input and output terminals available offering 2 channels, 5 4 channels or 8 channels per terminal and include 4–20 mA, PT100 RTD, Type J and K thermocouple and 0–10 VDC or ±10VDC form factors. 6 Bus End Terminal/Bus Expansion Coupler Terminals A Bus End Terminal, located at the end of a terminal assembly, is required for proper I/O bus 7 communication. Bus expansion is available for the PX-MOD, PX-TCP1 and PX-EIP1 Bus Couplers. Bus expansion requires that a Bus Expansion End Terminal be used in place of the 8 Bus End Terminal and a Bus Expansion Coupler Terminal be used in place of the PX-MOD, PX-TCP1 or PX-EIP1 at each expansion assembly. 9 Power Distribution Terminal A Power Distribution Terminal is available to provide access to the integrated 24VDC 10 Terminal Power Bus. The terminal provides 8 connection points each of 24V and 0V. Power Separation Terminal 11 A Power Separation Terminal is available to provide interruption of power along the Terminal Power Bus. 12 Power Feed Terminals Two Power Feed Terminals, 24VDC or 120–230 VAC, are available to add or change 13 supply power to the Terminal Power Bus. 14 Protos X Bus Couplers Bus Expansion Terminals Part Number Description Part Number Description A PX-MOD PX-901 PX-TCP1 PX-902 B PX-TCP2 PX-903 PX-EIP1 Power Distribution Terminal C Power Feed Terminals Part Number Description Part Number Description D PX-949 PX-940 Bus Couplers
Modbus RTU/ASCII Bus Coupler
Bus End Terminal
Modbus TCP Bus Coupler (1 port)
Bus Expansion End Terminal
Modbus TCP Bus Coupler (2 ports)
Bus Expansion Coupler Terminal
EtherNet/IP Bus Coupler (1 port)
PX-970
24VDC Power Feed Terminal 120-230 VAC Power Feed Terminal
24VDC Power Distribution Terminal
Protos X Installation and I/O Manual, 1st Edition, Rev. D
1–5
Page 16
Chapter 1: Getting Started
Protos X I/O System Components, (cont’d)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Analog Input/Output Terminals
Discrete Input/Output Terminals Part Number PX-144 PX-148 PX-149 PX-172-1 PX-172-2 PX-244-1 PX-244-2 PX-248 PX-249 PX-272-1 PX-272-2 PX-549
1–6
Description 24VDC 4-point Input Terminal 24VDC 8-point Input Terminal 24VDC 16-point Input Terminal 120–230 VAC 2-point Input Terminal 120 VAC/VDC 2-point Input Terminal 24VDC 4-point Output Terminal (0.5 A per point) 24VDC 4-point Output Terminal (2A per point) 24VDC 8-point Output Terminal (0.5 A per point) 24VDC 16-point Output Terminal (0.5 A per point) 230VAC/VDC 2-point Output Terminal (0.3 A per point) 230VAC / 30VDC 2-point Output Terminal (2A per point) 24VDC 8-point Input/ 24VDC 8-point Output Combination Terminal
Part Number PX-302 PX-304 PX-308 PX-312 PX-314 PX-318 PX-322-1 PX-324-1 PX-332-J PX-332-K PX-334-J PX-334-K PX-402
Description
PX-414
4–20 mA 2-channel Current Input Terminal 4–20 mA 4-channel Current Input Terminal 4–20 mA 8-channel Current Input Terminal ±10VDC 2-channel Voltage Input Terminal ±10VDC 4-channel Voltage Input Terminal ±10VDC 8-channel Voltage Input Terminal 2 Channel RTD Terminal 4 Channel RTD Terminal 2 Channel Thermocouple Terminal (J type) 2 Channel Thermocouple Terminal (K type) 4 Channel Thermocouple Terminal (J type) 4 Channel Thermocouple Terminal (K type) 4–20 mA 2-channel Current Output Terminal 4–20 mA 4-channel Current Output Terminal 4–20 mA 8-channel Current Output Terminal 0–10 VDC 2-channel Voltage Output Terminal 0–10 VDC 4-channel Voltage Output Terminal
PX-418
±10VDC 8-channel Voltage Output Terminal
PX-404 PX-408 PX-412
Configuration Cable (USB v2.0) A communications cable is available for configuration of the Bus Couplers. The cable has a USB type A connector for the PC and a 4-pin custom micro connector for the bus coupler. Configuration Cable (USB) Part Number PX-USB-232
Description Configuration Cable 3m (9.8 ft)
Software Configuration Tool The software configuration tool (PX-CFGSW) auto-configures the Modbus addresses and the interface allows the user to: Run the configurator • View the configured Modbus addresses • Modify the baud rate • Change the Modbus offset • Reboot the coupler • Disable or modify Watchdog timer • Configure first three octets of the IP address
Protos X Installation and I/O Manual, 1st Edition, Rev. D
Page 17
Chapter 1: Getting Started
Protos X I/O System Example Typical System Setup An example of a typical Protos X I/O system can be seen below. An I/O Bus, powered through the Bus Coupler, provides data communication across the terminal assembly via six contacts located on the side walls of the terminals. A Terminal Power Bus provides power for the I/O terminals via two power contacts. A power source of 24VAC or 24VDC must be connected to the Bus Coupler from an external supply. If additional 24VDC supply is required for terminal wiring, eight points of 24VDC power can be distributed from the Terminal Power Bus using a Power Distribution Terminal (PX-949). This terminal must be mounted to the right of a terminal that passes 24VDC on the power bus. Both I/O Bus communication and terminal bus power are passed through to adjoining terminals. For expansion beyond a 64 terminal assembly, a Bus Expansion End Terminal (PX-902) is used in place of a standard Bus End Terminal (PX-901). A Bus Expansion Coupler Terminal (PX-903) is used at each expansion assembly in place of a PX-MOD or PX-TCP1 Bus Coupler. Up to 31 Expansion couplers can be used in a group of assemblies. Connection is made between the Expansion Coupler Terminals via standard RJ45 Ethernet patch cable. Note: The PX-TCP2 Bus Coupler does not support expansion.
Bus Coupler PX-MOD
I/O-Bus
Power Distribution Terminal
Bus End Terminal
0V Us GNDs
1
5
2
6
3
7
4
8
+ + Up
GNDp
78
23
90 1
456
78
.nc
23
90 1
.nc
PX-MOD
Terminal Power Bus
PX-901
Power Bus Isolation
Protos X Installation and I/O Manual, 1st Edition, Rev. D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
1–7
456
Page 18
Chapter 1: Getting Started
Notes
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 1–8
Protos X Installation and I/O Manual, 1st Edition, Rev. D
Page 19
Specifications
Chapter
2
In This Chapter... Bus Coupler: PX-MOD................................................................................................ 2–2 Bus Coupler: PX-TCP1................................................................................................ 2–6 Bus Coupler: PX-TCP2.............................................................................................. 2–10 Bus Coupler: PX-EIP1................................................................................................ 2–14 Protos X Terminal Types.......................................................................................... 2–18 Bus End/Expansion Terminals.................................................................................. 2–20 Power Terminals....................................................................................................... 2–24 Discrete Terminals.................................................................................................... 2–28 Analog Terminals. .................................................................................................... 2–40 Protos X Modbus Communication. ......................................................................... 2–58 Protos X EtherNet/IP Communication. ................................................................... 2–59
Page 20
Chapter 2: Specifications
Bus Coupler: PX-MOD
The PX-MOD Modbus RTU/ASCII Slave Bus Coupler allows 1 connection of up to 64 terminals per assembly, 255 terminals total, in a Modbus RTU/ASCII serial network. The PX-MOD 2 communicates using high-level Modbus commands and automatically assigns Modbus addresses for inputs and outputs. The maximum amount of data is 512 bytes of input data and 512 bytes 3 of output data, with up to 1020 inputs, 1020 outputs, 256 analog inputs and 256 analog outputs, when using bus expansion. 4 The PX-MOD has one RS-485 D-sub 9-pin port that functions in half duplex for connection to a Modbus master. The maximum 5 distance from master to the PX-MOD is 4000 feet (1200 meters) using 24 AWG shielded, twisted pair. Termination resistors are required at the beginning and end of the network. It is highly 6 recommended that a dedicated network be used for the Protos X system. A minimal assembly consists of a PX-MOD Bus Coupler, 7 I/O Terminals and a Bus End Terminal. 8 PX-MOD I/O Bus Specifications PX-MOD Modbus Port Specifications Supply Power for I/O Bus Number of Stations 9 Input Current from Power Station Configuration Supply Protocol 10 Recommended Fuse Data Transfer Rates I/O Bus Current Supply 11 Number of Bus Terminals Maximum Cable Length Connector Type Recommended Cable 12 Supported Number of Discrete Inputs/Outputs PX-MOD Terminal Power Bus Specifications 13 Number of Analog Inputs/ Supply Power for Outputs Terminal Bus 14 Maximum Number of Maximum Current Data Bytes* Number of Power Contacts A B IMPORTANT! Hot-Swapping Information C D 24V 0V 5
1
+ + 6
2
– – 7
3
4
8
D PX-MO
24VDC (-15%/+20%)
99
Rotary Switches
70mA + (total I/O bus current) / 4
Modbus RTU/ASCII (default = RTU)
10A Max
150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 baud
1000mA Max
4000 ft. (1,200m) 9-pin, D-Sub, RS-485 24AWG, Shielded, Twisted Pair
64 per assembly, 255 w/ I/O Bus Expansion (based on power budget) 1020 Inputs and 1020 Outputs with 255 terminals 256 inputs and 256 outputs
512 Input Bytes and 512 Output Bytes
* Number of Terminals can not exceed 512 input bytes and 512 output bytes.
24 VAC/VDC 10A
2 (+24 VAC/DC, 0V)
Note: This device cannot be Hot Swapped.
2–2
Protos X Installation and I/O Manual, 1st Edition, Rev. C