Page 111
4–15 I/O Memory Map and Analog Module Resolution
Memory Map of 16-Channel Analog Output Module Decimal Bit
07
06
05
04
03
02
01
00
Octal Bit
07
06
05
04
03
02
01
00
Size Read Byte 1
Analog Value Channel 1
Write Byte 1
Analog Value Channel 1
Write Byte 2 not used
Byte3
Module Control Byte
Write Byte 4
Analog Value Channel 2
Write Byte 5
Analog Value Channel 2
Write Byte 6 not used
Byte7 reserved for future use
Byte8
Analog Value Channel 3
Write Byte 9
Analog Value Channel 3
Write Byte 10 not used
Byte11 reserved for future use
Byte12
Analog Value Channel 4
Write Byte 13
Analog Value Channel 4
Write Byte 14 not used
Byte15 reserved for future use
Byte16
Analog Value Channel 5
Write Byte 17
Analog Value Channel 5
Write Byte 18 not used
Byte19 reserved for future use
Byte20
Analog Value Channel 6
Write Byte 21
Analog Value Channel 6
Write Byte 22 not used
Byte23 reserved for future use
Byte24
Analog Value Channel 7
Write Byte 25
Analog Value Channel 7
Write Byte 26 not used
Byte27 reserved for future use
Byte28
Analog Value Channel 8
Write Byte 29
Analog Value Channel 8
Write Byte 30 not used
Byte31 reserved for future use
Byte32
I/O Memory Map and Analog Module Resolution
Not Used
Page 112
4–16
I/O Memory Map and Analog Module Resolution
I/O Memory Map and Analog Module Resolution
Decimal Bit
07
06
05
04
03
02
01
00
Octal Bit
07
06
05
04
03
02
01
00
Size
Analog Value Channel 9
Write Byte 33
Analog Value Channel 9
Write Byte 34 not used
Byte35 reserved for future use
Byte36
Analog Value Channel 10
Write Byte 37
Analog Value Channel 10
Write Byte 38 not used
Byte39 reserved for future use
Byte40
Analog Value Channel 11
Write Byte 41
Analog Value Channel 11
Write Byte 42 not used
Byte43 reserved for future use
Byte44
Analog Value Channel 12
Write Byte 45
Analog Value Channel 12
Write Byte 46 not used
Byte47 reserved for future use
Byte48
Analog Value Channel 13
Write Byte 49
Analog Value Channel 13
Write Byte 50 not used
Byte51 reserved for future use
Byte52
Analog Value Channel 14
Write Byte 53
Analog Value Channel 14
Write Byte 54 not used
Byte55 reserved for future use
Byte56
Analog Value Channel 15
Write Byte 57
Analog Value Channel 15
Write Byte 58 not used
Byte59 reserved for future use
Byte60
Analog Value Channel 16
Write Byte 61
Analog Value Channel 16
Write Byte 62 not used
Byte63 reserved for future use
Byte64
Page 113
4–17 I/O Memory Map and Analog Module Resolution
8-Channel Analog Input / 4–Channel Analog Output Module (T1F–8AD4DA–x) Input Image Table Mapping Input Size Read 2 to 32 Bytes
Module Image Input Data Channel 1
Input Data Channel 2 Note: When using the T1F–8AD4DA–x module in an ERM/EBC network, refer to Appendix E in the Ethernet Remote Master Module Manual (H24–ERM–M) for module configuration information.
Input Data Channel 3
Input Data Channel 4
Input Data Channel 5
Input Data Channel 6
Input Data Channel 8
Output Size Write
0 Byte
Outputs–– N/A
I/O Memory Map and Analog Module Resolution
Input Data Channel 7
Page 114
4–18 I/O Memory Map and Analog Module Resolution
8-Channel Analog Input / 4–Channel Analog Output Module (T1F–8AD4DA–x) Output Image Table Mapping
Read
Intput Size
Module Image
0 Byte
Inputs–– N/A
Output Size Write 2 to 32 Bytes
Output Data Channel 1
Module Control Byte Output Data Channel 2
Output Data Channel 3
I/O Memory Map and Analog Module Resolution
Output Data Channel 4
Page 115
4–19 I/O Memory Map and Analog Module Resolution
Memory Map of the 8 Analog Input Channels of the T1F–8AD4DA–x Decimal Bit
07
06
05
04
03
02
01
00
Octal Bit
07
06
05
04
03
02
01
00
Size
Analog Value Channel 1
Read Byte 1
Analog Value Channel 1
Read Byte 2 not used
Byte3 reserved for future use
Byte4
Analog Value Channel 2
Read Byte 5
Analog Value Channel 2
Read Byte 6 not used
Byte7 reserved for future use
Byte8
Analog Value Channel 3
Read Byte 9
Analog Value Channel 3
Read Byte 10 not used
Byte11 reserved for future use
Byte12
Analog Value Channel 4
Read Byte 13
Analog Value Channel 4
Read Byte 14 not used
Byte15 reserved for future use
Byte16
Analog Value Channel 5
Read Byte 17
Analog Value Channel 5
Read Byte 18 Byte19 Byte20
Analog Value Channel 6
Read Byte 21
Analog Value Channel 6
Read Byte 22 not used
Byte23 reserved for future use
Byte24
Analog Value Channel 7
Read Byte 25
Analog Value Channel 7
Read Byte 26 not used
Byte27 reserved for future use
Byte28
Analog Value Channel 8
Read Byte 29
Analog Value Channel 8
Read Byte 30 not used
Byte31 reserved for future use
Byte32
Not Used
Write Byte 1
I/O Memory Map and Analog Module Resolution not used reserved for future use
Page 116
4–20 I/O Memory Map and Analog Module Resolution
I/O Memory Map and Analog Module Resolution
Memory Map of the 4 Analog Output Channels of the T1F–8AD4DA–x Decimal Bit
07
06
05
04
03
02
01
00
Octal Bit
07
06
05
04
03
02
01
00
Size
Not Used
Read Byte 1
Analog Value Channel 1
Write Byte 1
Analog Value Channel 1
Write Byte 2 not used
Byte3
Module Control Byte
Write Byte 4
Analog Value Channel 2
Write Byte 5
Analog Value Channel 2
Write Byte 6 not used
Byte7 reserved for future use
Byte8
Analog Value Channel 3
Write Byte 9
Analog Value Channel 3
Write Byte 10 not used
Byte11 reserved for future use
Byte12
Analog Value Channel 4
Write Byte 13
Analog Value Channel 4
Write Byte 14 not used
Byte15 reserved for future use
Byte16
Page 117
4–21 I/O Memory Map and Analog Module Resolution
Analog Output Module Control Byte Channel 1 Memory Map of 8&16-Channel Analog Output Module Decimal Bit
07
06
05
04
03
02
01
00
Octal Bit
07
06
05
04
03
02
01
00
Size
Analog Value Channel 1
Write Byte 1
Analog Value Channel 1
Write Byte 2 not used
Byte3
Module Control Byte
Write Byte 4
Module Control Byte of 8&16-Channel Analog Output Module Decimal Bit
31
30
29
28
27
26
25
24
Octal Bit
37
36
35
34
33
32
31
30
Read/Write
Outputs Enable 0 = All outputs OFF 1 = All outputs Enabled
Write
Bit 25
Unipolar / Bipolar 0 = Unipolar selected 1 = Bipolar selected
Write
Bit 26
5V / 10V Range 0 = 5V range 1 = 10V range
Write
Bit 27
0 – 20mA / 4–20mA Range 0 = 0 – 20mA range 1 = 4 – 20mA range
Write
Bit 28 – 31
Reserved for system use
–
I/O Memory Map and Analog Module Resolution
Bit 24
Page 118
4–22 I/O Memory Map and Analog Module Resolution
Analog Output Module Resolution Ouput Module Resolution
Since the module has 12-bit resolution, the analog signal is converted into 4096 counts ranging from 0-4095 (212). For example, with a 0 to 10V scale, a 0V signal would be 0, and a 10V signal would be 4095. This is equivalent to a a binary value of 0000 0000 0000 to 1111 1111 1111, or 000 to FFF hexadecimal. The following diagram shows how this relates to each signal range. Current Output Module Resolution 4 – 20mA
0 – 20mA 20mA
20mA
4mA 0mA 0
0
4095
4095
Voltage Output Module Resolution 0V – 5V 5V
0V
0V
I/O Memory Map and Analog Module Resolution
0
Channel Data Bits
4095
–5V to +5V
0V – 10V 10V
0
4095
The first twelve bits represent the analog data in binary format. Bit Value Bit Value 0 1 6 64 1 2 7 128 2 4 8 256 3 8 9 512 4 16 10 1024 5 32 11 2048
–10V to +10V
+5V
+10V
0V
0V –10V
–5V
0 (+2047) +4095
0 (+2047)+4095
MSB
LSB
1 1 1 1 11 9 8 7 6 5 4 3 2 1 0 5 4 3 2 10
– data bits
NOTE: Each Analog channel uses 4 bytes. The first and second byte contain the analog data. The third and fourth byte are not used at this time.
Page 119
4–23 I/O Memory Map and Analog Module Resolution
Each count can also be expressed in terms of the signal level by using the equation shown. The following table shows the smallest signal levels that will result in a change in the data value for each signal range. Range
Analog and Digital Value Conversions
SmallestDetectableChange +
H*L Resolution
H = high limit of the signal range L = low limit of the signal range
Signal Span (H - L)
Divide By
Smallest Detectable Change
$10V
20 V
4095
4.88 mV
$5V
10 V
4095
2.44 mV
0 to 5V
5V
4095
1.22 mV
0 to 10V
10 V
4095
2.44 mV
0 to 20mA
20 mA
4095
4.88 mA
4 to 20mA
16 mA
4095
3.91 mA ometimes it is helpful to be able to quickly convert between the voltage or current signal levels and the digital values. This is especially helpful during machine startup or troubleshooting. The following table provides formulas to make this conversion easier. Range
If you know the digital value ...
If you know the analog signal level ...
A + 5D 4095
D + 4095 (A) 5
0 to 10V
A + 10D 4095
D + 4095 (A) 10
$5V
A + 10D * 5 4095
D + 4095 (A ) 5) 10
$10V
A + 20D * 10 4095
D + 4095 (A ) 10) 20
0 to 20mA
A + 20D 4095
D + 4095 (A) 20
4 to 20mA
A + 16D ) 4 4095
D + 4095 (A * 4) 16
For example, if you are using the –10 to +10V range and you know you need a 6V signal level, you would use the following formula to determine the digital value that should be stored in the V-memory location that contains the data.
D + 4095 (A ) 10) 20 D + 4095 (6V ) 10) 20 D + (204.75) (16) D + 3276
I/O Memory Map and Analog Module Resolution
0 to 5V
Page 120
European Union Directives (CE) In This Appendix. . . .
Ċ European Union (EU) Directives Ċ Basic EMC Installation Guidelines
1A