Page 87
Chapter 5: Specifications - Discrete I/O Modules
T1K-08TRS - Isolated Relay Output Specifications
9.2 (0.36)
Outputs Per Module Output Type Commons Per Module (3.5) Operating Voltage89Range
8 Relay Form A (SPST) normally open T1K-08TRS 8, 1pt. / common (isolated) 6–240 VAC (47–63 Hz), 6–27 VDC 5–264 VAC (47–63 Hz) min. / max. 0 1 2 3 4 5 6 5–30 VDC min. / max. 0 1 2 3 4 5 6 7A / pt. common (Subject to derating) 0.1 mA @ 264VAC 8A for 10ms 5mA @ 5VDC < 15ms < 10ms 400mA @ 5VDC Logic Side FU1 / FU2 ON = fuse 1 or fuse 2 blown Output Points FU3 / FU4 ON = fuse 3 or fuse 4 blown FU5 / FU6 ON = fuse 5 or Note: fuse 6 blown Apply the labels that come 0 1 2 3 with 4 the5 I / O 6 FU7 / FU8 ON = fuse 7 or fuse 8 blown module to the I / O base to properly identify the 8 (10A, 250V / common), (1 pt. / fuse) terminal points. NQ3-10 SOC Corp. 185g Output Points mm (in.)
8.1 (0.32)
Output Voltage Range
27 VDC 240 VAC
Fuses (User Replaceable)
8.1 (0.32) T1K-FUSE-3
Weight
0
Typical Relay Life (Operations) 83.3 (3.28) at Room Temperature
To LED
Load Current 2A 5A
1A
24VDC Resistive 24VDC Solenoid 110VAC Resistive 110VAC Resistive 220VAC Resistive 220VAC Resistive
1000K 300K 1000K 300K 500K 300K
FU5
FU7
FU4
FU6
FU8
7
7
54.3(2.14) 80 (3.15)
Error Status Indicators (LEDs)
Voltage & Type of Load
FU3
FU2
25.7(1.01)
Fuses located under top cover
Max. Load Current Max. Leakage Current Max. 08TRS Inrush Current Min. Load OFF to ON Response ON to OFF Response Base Power Requirements Status Indicators
FU1
1
C0 C1 C2 C3 C4 2 3 4 5 6
C5 7
7
C6
Top Row
9.2 (0.36)
C7 Fuses located under top cover
Commons 6-27 VDC 6-240 VAC
7A
V0
V1
Bottom Row V2
V3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
500K 200K 100K C0 C1 C2 C3 C4 C5 C6 C7 Note: V 0 – V 3 not used on Relay Output Modules 100K * * Note: See other Commons 500K 200K 100K side for wiring VDC Note: Apply the labels that come with6–27 the I/O 6–240 VAC 100K * * example. module to the I / O base to properly identify the 250K 125K 60K terminal V0 V 1 points. V2 V3 8.1 (0.32) 100K * * Note: V 0 – V 3 not used on Relay Output Modules Side View *Solenoid (inductive) loads > 2A cannot be used.
Equivalent Output Circuit Derating Chart Points 8
5A
6
6A
4
Internal Module Circuitry
4A
+V
Output
L
7A
2 0 0 32
10 20 30 40 50 55 °C 50 68 86 104 122 131 °F Ambient Temperature ( °C/°F)
To LED AC or DC Supply
10A
COM 6–27 VDC 6–240 VAC
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
5–19
Page 88
Chapter 5: Specifications - Discrete I/O Modules
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Notes:
5–20
Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 89
Specifications - Analog I/O Modules
Chapter
16
In This Chapter: Analog I/O Module Overview............................................................................... 6–2 Analog I/O Modules.............................................................................................. 6–6
Page 90
Chapter 6: Specifications - Analog I/O Modules
Analog I/O Modules Overview There are 13 analog I/O modules available. The specifications and wiring diagrams for these modules are found in this chapter. Each analog I/O module is identified as an “Input”, 1 “Output” or “Input/Output” module using the color coding scheme shown below. A blue dot on the front panel signifies an Input module, a red dot signifies an Output module and a 2 white dot signifies an Input/Output module. 3 Analog Input Modules Analog Input Modules Number of 4 Part Number Description See Page Channels T1F-08AD-1 5 T1F-08AD-2 T1F-16AD-1 6 T1F-16AD-2 7 T1F-16RTD T1F-16TMST 8 T1F-14THM Analog Output Modules 9 Analog Output Modules 10 Number of Part Number Description See Page Channels 11 T1F-08DA-1 T1F-08DA-2 12 T1F-16DA-1 13 T1F-16DA-2 14 Analog Input/Output Module A Analog Input/Output Modules B Number of Part Number Description See Page Channels C T1F-8AD4DA-1 D T1F-8AD4DA-2 Module Part Number
T1F-08AD-1
0
Module Part Number
3
4
5
6
7
1
2
1
0
2
8
Analog Current Input
6-6
8
Analog Voltage Input
6-7
16
Analog Current Input
6-8
16
Analog Voltage Input
6-9
16
RTD
6-10
16
Thermistor
6-12
14
Thermocouple
6-14
8
Analog Current Output
6-17
8
Analog Voltage Output
6-18
16
Analog Current Output
6-19
16
Analog Voltage Output
6-20
8/4
Analog Current Input/Output
6-21
8/4
Analog Voltage Input/Output
6-23
Module Type (Red: Output)
3
4
5
6
7
T1F-8AD4DA-1
0
6–2
2
T1F-08DA-1
0
Module Part Number
1
Module Type (Blue: Input)
3
1
Module Type (White: Input/Output)
4
5
2
6
7
3
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 91
Chapter 6: Specifications - Analog I/O Modules
Analog I/O Modules Overview- continued
1 2 How to Access the Analog I/O Modules With the Do-more PLC, the WX and WY memory addresses are assigned to exchange analog 3 data with the analog I/O modules (WX = Analog input data, WY = Analog output data). X addresses are assigned to analog input modules and Y addresses are assigned to configure 4 analog output modules. The following table shows how many X, Y, WX and WY addresses are assigned to each analog 5 I/O module type. 6 Analog I/O Module Addressing 7 Part Number Module ID WX Y WY X T1F-08AD-1 8 T1F-08AD-2 9 T1F-16AD-1 T1F-16AD-2 10 T1F-08DA-1 T1F-08DA-2 11 T1F-16DA-1 12 T1F-16DA-2 T1F-8AD4DA-1 13 T1F-8AD4DA-2 T1F-16RTD 14 T1F-16TMST A T1F-14THM B C NOTE 1: his module can be configured to operate in unipolar mode which generates a range of values from 0 to 65535 (instead of -32768 to 32767). Use the “:U”(unsigned) cast operator to get the proper representation of the data when using a module that is configured for unipolar. For D example: WX0:U, WX1:U. WARNING: The T1H Series PLC does not support any Hot-Swap features.
(see Note 1)
0x2532
8*
8
-
-
0x2532
8*
8
-
-
0x2533
16*
16
-
-
0x2533
16*
16
-
-
0x2628
-
-
8
8
0x2628
-
-
8
8
0x262C
-
-
8
16
0x262C
-
-
8
16
0x2736
8*
8
8
4
0x2736
8*
8
8
4
0x2573
16**
16
-
-
0x2573
16**
16
-
-
0x2573
16**
16
-
-
* X addresses assigned to this module are not used. ** X addresses assigned to this module indicate a broken transmitter.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
6–3
Page 92
Chapter 6: Specifications - Analog I/O Modules
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Analog I/O Modules Overview- continued
6–4
Module Control Byte Analog output modules have a Module Control Byte that is used to configure some options for the outputs. In the module addressing, this byte shows up as eight Discrete Output (Y) Bits. • Y0 = Outputs Enabled • Y(0+1) = Unipolar/Bipolar • Y(0+2) = 5V/10V Range • Y(0+3) = 0–20mA/4–20mA • Y((0+4) through (0+7)) = Reserved
When an analog output module is added to a Do-more project, a Module Configuration with default Module Control Byte values is created. Its settings can be changed under Module Configuration by double-clicking the Module Name or by selecting the New Config or Edit Config buttons on the right hand side.
The Do-more T1H Series CPU will write the settings from the Module Configuration into the modules before going to Run mode. The Y Bits can optionally be used to change the Module Control Byte setting within the program.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 93
Chapter 6: Specifications - Analog I/O Modules
Analog I/O Modules Overview- continued You can check which X, Y, WX and WY addresses are assigned to each analog I/O module in the I/O Mapping tab of the System Configuration window, as shown below.
Select the pull-down menu PLC > System Configuration to open the System Configuration window and click the I/O Mapping tab.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
6–5
Page 94
Chapter 6: Specifications - Analog I/O Modules
T1F-08AD-1 - 8 Channel Analog Current Input
1 Number of Channels Specifications Input Ranges Resolution 2 Module Addressing Frequency Response 3 Input Resistance Absolute Maximum Ratings 4 Conversion Time 5 (Default: Normal Mode) Error 6 Linearity Input Stability Full Scale Error 7 (Offset Error not included) Input Range/Resolution Input Signal Ranges Offset Error Full Scale Inaccuracy 8 Max. (% of full scale); all errors included Update Rate 9 CPU Base Power Required External Module Power 10 Supply Req. Recommended Fuse Temperature 11 Operating Storage Temperature Accuracy vs. Temperature Humidity 12 Relative Environmental Air 13 Vibration Shock Noise Immunity 14 Weight Equivalent Circuit Equivalent InputInput Circuit A B C D 8, single ended (1 common) 0–20mA, 4–20mA, -20 to 20mA 14 bit (13 bit plus sign bit) 8 input bits (X-not used); 8 input words (WX) -3db @ 500Hz, -20db / decade 250q 8V max. Input Normal Mode: 5ms per channel Fast Mode: 0.5 ms per channel (Fast Mode supported in module hardware version B or later, and only when using this analog module with the T1H-EBC(100) or T1H-PBC control module) ±2 count max. ±1 count
T1F-08AD-1
0
1
2
3
4
5
6
7
16 counts max. 2 counts max.
0 – 20mA
4 – 20mA
20mA
20mA
1 channel per scan 75mA @ 5VDC
0mA
18–30 VDC, 50mA, class 2
4–Wire Current Transmitter
Transmitter Supply 18-30 VDC
Module Supply 24 VDC
COM 0
COM 1
V0
V1
2–Wire Current Transmitter
0
1638
8191
48 (1.89)
8.1 (0.32)
–20 to 20mA
20mA
T1F–08AD–1
0
1
2
3
–20mA –8191
4
5
6
54.3(2.14)
0mA
7
0 1 2 3 4 5 6 7
0
Note: V1 internally connected to Commons
8.1 (0.32)
mm (in.)
83.3 (3.28) NOTES: 1. Shields should be grounded at the signal source. 2. More than one external power supply can be used, provided all the power supply commons are connected. 3. A Series 217, 0.032 A fast-acting fuse is recommended 4–20 mA 1st Edition, Rev. A - T1H-DM-M Do-more T1H Series PLC User for Manual, current loops. 4. If the power supply common of an external power supply is not connected
6–6
8191
25.7(1.01)
Fuse
0.032 A @ 5VDC, Series 217 Fast Acting 0 to 60!C (32 to 140!F) 9.2 (0.36) -20 to 70!C (-4 to 158!F) Input points ±50ppm / !C max. full scale 5 to 95% (non-condensing) 0 1 2 3 4 5 6 7 No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 Fuse NEMA ICS3-304 Commons 136g(not isolated)
4mA
80 (3.15)
0.18% @ 25!C 0.36% @ 60!C
8191
Page 95
Chapter 6: Specifications - Analog I/O Modules
T1F-08AD-2 - 8 Channel Analog Voltage Input Specifications Number of Channels Input Ranges Resolution Module Addressing Frequency Response Input Resistance
8, single ended (1 common) 0–5 V, 0–10 V, ±5V, ±10V 14 bit (13 bit plus sign bit) 8 input bits (X-not used); 8 input words (WX) -3db @ 500Hz, -20db / decade 200kq min.
T1F-08AD-2
0
1
2
3
4
5
6
7
Absolute Maximum Ratings Fault Protected Input, 130V (rms)/ 100VDC Normal Mode: 5ms per channel Fast Mode: 0.5 ms per channel (Fast Mode supported in module hardware version B or later, and only when using this analog module with the T1HEBC(100) or T1H-PBC control module) ±2 count max. Linearity Error ±1 count Input Stability Calibration Full Scale Error 8 counts max. 2 counts max. Calibration Offset Error
Conversion Time (Default: Normal Mode)
0 – 10V
0 – 5V 5V
10V
0V
0V 0
4095
0
–5 to 5V
–10 to 10V
48 (1.89)
5V
10V
8.1 (0.32)
0V
0V
4095
–10V –8192
Module Supply 24 VDC
COM 0
COM 1
V0
V1
0
1
2
3
4
5
7
6
0 1 2 3 4 5 6 7 25.7(1.01)
Transmitter Supply 18-30 VDC
Equivalent Input Circuit Equivalent Input Circuit
0
80 (3.15)
–5V T1F–08AD–2 –4095 0
Commons (not isolated)
4–Wire Voltage Transmitter
8191
54.3(2.14)
Max. Full Scale Inaccuracy 0.08% @ 25!C (% of full scale); 0.26% @ 60!C all errors included 1 channel per scan CPU Update Rate 75mA @ 5VDC Base Power Required External Module Power 18–30 VDC, 50mA, class 2 Supply Req. 0 to 60!C (32 to 140!F) Operating Temperature -20 to 70!C (-4 to 158!F) 9.2 (0.36) Storage Temperature / !C max. full scale Accuracy vs. Temperature ±50ppm Input points 5 to 95% (non-condensing) Relative Humidity No corrosive gases permitted Environmental Air 0 1 2 3 4 5 6 7 MIL STD 810C 514.2 Vibration MIL STD 810C 516.2 Shock NEMA ICS3-304 Noise Immunity 136g Weight
Input InputRange/Resolution Signal Ranges
Note: V1 internally connected to Commons
8.1 (0.32)
mm (in.)
NOTES: 1. Shields should be grounded at the signal source. 83.3 (3.28) 2. Unused inputs should be connected to Common (0 VDC). 3. More than one external power supply can be used, provided all the power supply commons are connected. Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
8191
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
6–7