Do-more T1H Series PLC Hardware User Manual: Chapter 5. Specifications - Discrete I/O Modules, pages 87 to 95

Pages 87 to 95 of 168, from Do-more T1H Series PLC Hardware User Manual

The original document is the PDF (40 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect T1K-08B, Konnect-It T1K-08B and Koyo T1K-08B

Page 87

Chapter 5: Specifications - Discrete I/O Modules

T1K-08TRS - Isolated Relay Output Specifications

9.2 (0.36)

Outputs Per Module Output Type Commons Per Module (3.5) Operating Voltage89Range

8 Relay Form A (SPST) normally open T1K-08TRS 8, 1pt. / common (isolated) 6–240 VAC (47–63 Hz), 6–27 VDC 5–264 VAC (47–63 Hz) min. / max. 0 1 2 3 4 5 6 5–30 VDC min. / max. 0 1 2 3 4 5 6 7A / pt. common (Subject to derating) 0.1 mA @ 264VAC 8A for 10ms 5mA @ 5VDC < 15ms < 10ms 400mA @ 5VDC Logic Side FU1 / FU2 ON = fuse 1 or fuse 2 blown Output Points FU3 / FU4 ON = fuse 3 or fuse 4 blown FU5 / FU6 ON = fuse 5 or Note: fuse 6 blown Apply the labels that come 0 1 2 3 with 4 the5 I / O 6 FU7 / FU8 ON = fuse 7 or fuse 8 blown module to the I / O base to properly identify the 8 (10A, 250V / common), (1 pt. / fuse) terminal points. NQ3-10 SOC Corp. 185g Output Points mm (in.)

8.1 (0.32)

Output Voltage Range

27 VDC 240 VAC

Fuses (User Replaceable)

8.1 (0.32) T1K-FUSE-3

Weight

0

Typical Relay Life (Operations) 83.3 (3.28) at Room Temperature

To LED

Load Current 2A 5A

1A

24VDC Resistive 24VDC Solenoid 110VAC Resistive 110VAC Resistive 220VAC Resistive 220VAC Resistive

1000K 300K 1000K 300K 500K 300K

FU5

FU7

FU4

FU6

FU8

7

7

54.3(2.14) 80 (3.15)

Error Status Indicators (LEDs)

Voltage & Type of Load

FU3

FU2

25.7(1.01)

Fuses located under top cover

Max. Load Current Max. Leakage Current Max. 08TRS Inrush Current Min. Load OFF to ON Response ON to OFF Response Base Power Requirements Status Indicators

FU1

1

C0 C1 C2 C3 C4 2 3 4 5 6

C5 7

7

C6

Top Row

9.2 (0.36)

C7 Fuses located under top cover

Commons 6-27 VDC 6-240 VAC

7A

V0

V1

Bottom Row V2

V3

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

500K 200K 100K C0 C1 C2 C3 C4 C5 C6 C7 Note: V 0 – V 3 not used on Relay Output Modules 100K * * Note: See other Commons 500K 200K 100K side for wiring VDC Note: Apply the labels that come with6–27 the I/O 6–240 VAC 100K * * example. module to the I / O base to properly identify the 250K 125K 60K terminal V0 V 1 points. V2 V3 8.1 (0.32) 100K * * Note: V 0 – V 3 not used on Relay Output Modules Side View *Solenoid (inductive) loads > 2A cannot be used.

Equivalent Output Circuit Derating Chart Points 8

5A

6

6A

4

Internal Module Circuitry

4A

+V

Output

L

7A

2 0 0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 °F Ambient Temperature ( °C/°F)

To LED AC or DC Supply

10A

COM 6–27 VDC 6–240 VAC

Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M

5–19

Page 88

Chapter 5: Specifications - Discrete I/O Modules

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Notes:

5–20

Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M

Page 89

Specifications - Analog I/O Modules

Chapter

16

In This Chapter: Analog I/O Module Overview............................................................................... 6–2 Analog I/O Modules.............................................................................................. 6–6

Page 90

Chapter 6: Specifications - Analog I/O Modules

Analog I/O Modules Overview There are 13 analog I/O modules available. The specifications and wiring diagrams for these modules are found in this chapter. Each analog I/O module is identified as an “Input”, 1 “Output” or “Input/Output” module using the color coding scheme shown below. A blue dot on the front panel signifies an Input module, a red dot signifies an Output module and a 2 white dot signifies an Input/Output module. 3 Analog Input Modules Analog Input Modules Number of 4 Part Number Description See Page Channels T1F-08AD-1 5 T1F-08AD-2 T1F-16AD-1 6 T1F-16AD-2 7 T1F-16RTD T1F-16TMST 8 T1F-14THM Analog Output Modules 9 Analog Output Modules 10 Number of Part Number Description See Page Channels 11 T1F-08DA-1 T1F-08DA-2 12 T1F-16DA-1 13 T1F-16DA-2 14 Analog Input/Output Module A Analog Input/Output Modules B Number of Part Number Description See Page Channels C T1F-8AD4DA-1 D T1F-8AD4DA-2 Module Part Number

T1F-08AD-1

0

Module Part Number

3

4

5

6

7

1

2

1

0

2

8

Analog Current Input

6-6

8

Analog Voltage Input

6-7

16

Analog Current Input

6-8

16

Analog Voltage Input

6-9

16

RTD

6-10

16

Thermistor

6-12

14

Thermocouple

6-14

8

Analog Current Output

6-17

8

Analog Voltage Output

6-18

16

Analog Current Output

6-19

16

Analog Voltage Output

6-20

8/4

Analog Current Input/Output

6-21

8/4

Analog Voltage Input/Output

6-23

Module Type (Red: Output)

3

4

5

6

7

T1F-8AD4DA-1

0

6–2

2

T1F-08DA-1

0

Module Part Number

1

Module Type (Blue: Input)

3

1

Module Type (White: Input/Output)

4

5

2

6

7

3

Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M

Page 91

Chapter 6: Specifications - Analog I/O Modules

Analog I/O Modules Overview- continued

1 2 How to Access the Analog I/O Modules With the Do-more PLC, the WX and WY memory addresses are assigned to exchange analog 3 data with the analog I/O modules (WX = Analog input data, WY = Analog output data). X addresses are assigned to analog input modules and Y addresses are assigned to configure 4 analog output modules. The following table shows how many X, Y, WX and WY addresses are assigned to each analog 5 I/O module type. 6 Analog I/O Module Addressing 7 Part Number Module ID WX Y WY X T1F-08AD-1 8 T1F-08AD-2 9 T1F-16AD-1 T1F-16AD-2 10 T1F-08DA-1 T1F-08DA-2 11 T1F-16DA-1 12 T1F-16DA-2 T1F-8AD4DA-1 13 T1F-8AD4DA-2 T1F-16RTD 14 T1F-16TMST A T1F-14THM B C NOTE 1: his module can be configured to operate in unipolar mode which generates a range of values from 0 to 65535 (instead of -32768 to 32767). Use the “:U”(unsigned) cast operator to get the proper representation of the data when using a module that is configured for unipolar. For D example: WX0:U, WX1:U. WARNING: The T1H Series PLC does not support any Hot-Swap features.

(see Note 1)

0x2532

8*

8

-

-

0x2532

8*

8

-

-

0x2533

16*

16

-

-

0x2533

16*

16

-

-

0x2628

-

-

8

8

0x2628

-

-

8

8

0x262C

-

-

8

16

0x262C

-

-

8

16

0x2736

8*

8

8

4

0x2736

8*

8

8

4

0x2573

16**

16

-

-

0x2573

16**

16

-

-

0x2573

16**

16

-

-

* X addresses assigned to this module are not used. ** X addresses assigned to this module indicate a broken transmitter.

Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M

6–3

Page 92

Chapter 6: Specifications - Analog I/O Modules

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Analog I/O Modules Overview- continued

6–4

Module Control Byte Analog output modules have a Module Control Byte that is used to configure some options for the outputs. In the module addressing, this byte shows up as eight Discrete Output (Y) Bits. • Y0 = Outputs Enabled • Y(0+1) = Unipolar/Bipolar • Y(0+2) = 5V/10V Range • Y(0+3) = 0–20mA/4–20mA • Y((0+4) through (0+7)) = Reserved

When an analog output module is added to a Do-more project, a Module Configuration with default Module Control Byte values is created. Its settings can be changed under Module Configuration by double-clicking the Module Name or by selecting the New Config or Edit Config buttons on the right hand side.

The Do-more T1H Series CPU will write the settings from the Module Configuration into the modules before going to Run mode. The Y Bits can optionally be used to change the Module Control Byte setting within the program.

Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M

Page 93

Chapter 6: Specifications - Analog I/O Modules

Analog I/O Modules Overview- continued You can check which X, Y, WX and WY addresses are assigned to each analog I/O module in the I/O Mapping tab of the System Configuration window, as shown below.

Select the pull-down menu PLC > System Configuration to open the System Configuration window and click the I/O Mapping tab.

Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

6–5

Page 94

Chapter 6: Specifications - Analog I/O Modules

T1F-08AD-1 - 8 Channel Analog Current Input

1 Number of Channels Specifications Input Ranges Resolution 2 Module Addressing Frequency Response 3 Input Resistance Absolute Maximum Ratings 4 Conversion Time 5 (Default: Normal Mode) Error 6 Linearity Input Stability Full Scale Error 7 (Offset Error not included) Input Range/Resolution Input Signal Ranges Offset Error Full Scale Inaccuracy 8 Max. (% of full scale); all errors included Update Rate 9 CPU Base Power Required External Module Power 10 Supply Req. Recommended Fuse Temperature 11 Operating Storage Temperature Accuracy vs. Temperature Humidity 12 Relative Environmental Air 13 Vibration Shock Noise Immunity 14 Weight Equivalent Circuit Equivalent InputInput Circuit A B C D 8, single ended (1 common) 0–20mA, 4–20mA, -20 to 20mA 14 bit (13 bit plus sign bit) 8 input bits (X-not used); 8 input words (WX) -3db @ 500Hz, -20db / decade 250q 8V max. Input Normal Mode: 5ms per channel Fast Mode: 0.5 ms per channel (Fast Mode supported in module hardware version B or later, and only when using this analog module with the T1H-EBC(100) or T1H-PBC control module) ±2 count max. ±1 count

T1F-08AD-1

0

1

2

3

4

5

6

7

16 counts max. 2 counts max.

0 – 20mA

4 – 20mA

20mA

20mA

1 channel per scan 75mA @ 5VDC

0mA

18–30 VDC, 50mA, class 2

4–Wire Current Transmitter

Transmitter Supply 18-30 VDC

Module Supply 24 VDC

COM 0

COM 1

V0

V1

2–Wire Current Transmitter

0

1638

8191

48 (1.89)

8.1 (0.32)

–20 to 20mA

20mA

T1F–08AD–1

0

1

2

3

–20mA –8191

4

5

6

54.3(2.14)

0mA

7

0 1 2 3 4 5 6 7

0

Note: V1 internally connected to Commons

8.1 (0.32)

mm (in.)

83.3 (3.28) NOTES: 1. Shields should be grounded at the signal source. 2. More than one external power supply can be used, provided all the power supply commons are connected. 3. A Series 217, 0.032 A fast-acting fuse is recommended 4–20 mA 1st Edition, Rev. A - T1H-DM-M Do-more T1H Series PLC User for Manual, current loops. 4. If the power supply common of an external power supply is not connected

6–6

8191

25.7(1.01)

Fuse

0.032 A @ 5VDC, Series 217 Fast Acting 0 to 60!C (32 to 140!F) 9.2 (0.36) -20 to 70!C (-4 to 158!F) Input points ±50ppm / !C max. full scale 5 to 95% (non-condensing) 0 1 2 3 4 5 6 7 No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 Fuse NEMA ICS3-304 Commons 136g(not isolated)

4mA

80 (3.15)

0.18% @ 25!C 0.36% @ 60!C

8191

Page 95

Chapter 6: Specifications - Analog I/O Modules

T1F-08AD-2 - 8 Channel Analog Voltage Input Specifications Number of Channels Input Ranges Resolution Module Addressing Frequency Response Input Resistance

8, single ended (1 common) 0–5 V, 0–10 V, ±5V, ±10V 14 bit (13 bit plus sign bit) 8 input bits (X-not used); 8 input words (WX) -3db @ 500Hz, -20db / decade 200kq min.

T1F-08AD-2

0

1

2

3

4

5

6

7

Absolute Maximum Ratings Fault Protected Input, 130V (rms)/ 100VDC Normal Mode: 5ms per channel Fast Mode: 0.5 ms per channel (Fast Mode supported in module hardware version B or later, and only when using this analog module with the T1HEBC(100) or T1H-PBC control module) ±2 count max. Linearity Error ±1 count Input Stability Calibration Full Scale Error 8 counts max. 2 counts max. Calibration Offset Error

Conversion Time (Default: Normal Mode)

0 – 10V

0 – 5V 5V

10V

0V

0V 0

4095

0

–5 to 5V

–10 to 10V

48 (1.89)

5V

10V

8.1 (0.32)

0V

0V

4095

–10V –8192

Module Supply 24 VDC

COM 0

COM 1

V0

V1

0

1

2

3

4

5

7

6

0 1 2 3 4 5 6 7 25.7(1.01)

Transmitter Supply 18-30 VDC

Equivalent Input Circuit Equivalent Input Circuit

0

80 (3.15)

–5V T1F–08AD–2 –4095 0

Commons (not isolated)

4–Wire Voltage Transmitter

8191

54.3(2.14)

Max. Full Scale Inaccuracy 0.08% @ 25!C (% of full scale); 0.26% @ 60!C all errors included 1 channel per scan CPU Update Rate 75mA @ 5VDC Base Power Required External Module Power 18–30 VDC, 50mA, class 2 Supply Req. 0 to 60!C (32 to 140!F) Operating Temperature -20 to 70!C (-4 to 158!F) 9.2 (0.36) Storage Temperature / !C max. full scale Accuracy vs. Temperature ±50ppm Input points 5 to 95% (non-condensing) Relative Humidity No corrosive gases permitted Environmental Air 0 1 2 3 4 5 6 7 MIL STD 810C 514.2 Vibration MIL STD 810C 516.2 Shock NEMA ICS3-304 Noise Immunity 136g Weight

Input InputRange/Resolution Signal Ranges

Note: V1 internally connected to Commons

8.1 (0.32)

mm (in.)

NOTES: 1. Shields should be grounded at the signal source. 83.3 (3.28) 2. Unused inputs should be connected to Common (0 VDC). 3. More than one external power supply can be used, provided all the power supply commons are connected. Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M

8191

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

6–7