Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 1 of 1

Relay Output Modules T1K-08TRS, pages 1 to 6

Pages 1 to 6 of 6

The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect T1K-08TRS, Konnect-It T1K-08TRS and Koyo T1K-08TRS

Page 1

Relay Output Modules T1K-08TRS

<--->

8-point, isolated relay output module The 8-point relay output module uses a T1K-16B or T1K-16B-1 base, which is purchased separately.

T1K-08TRS Output Specification Outputs per Module Commons Operating Voltage Range

8 normally open

Output Voltage Range

5-264 VAC (47-63 Hz), 5-30 VDC min./max.

Max. Load Current Max. Leakage Current Max. Inrush Current Min. Load OFF to ON Response ON to OFF Response Base Power Required Status Indicators

7A / pt. (subject to derating)

8, 1 pt. / common (isolated) 6-240 VAC (47-63 Hz), 6-27 VDC

0.1 mA @ 264 VAC 8A for 10 ms 5 mA @ 5 VDC < 15 ms < 10 ms 400 mA @ 5 VDC Logic side FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown FU5/FU6 ON = fuse 5 or 6 blown FU7/FU8 ON = fuse 7 or 8 blown

Error Status Indications(LEDS) Fuses (User Replaceable) T1K-FUSE-3 Weight

8, (10 A, 250 V / common), 1 pt. / fuse NQ3-10 SOC Corp. 185 g

Typical Relay Life (Operations) Voltage and Load Type 24 VDC Resistive 24 VDC Solenoid 110 VAC Resistive 110 VAC Solenoid 220 VAC Resistive 220 VAC Solenoid

1A

Load Current 2A 5A

7A

1000 K

500 K

200 K

100 K

300 K

100 K see note see note

1000 K

500 K

200 K

100 K

300 K

100 K see note see note

500 K

250 K

125 K

60 K

300 K

100 K see note see note

Note: Solenoid (inductive) loads >2A cannot be used.

Equivalent Output Circuit

Volume 13 e8-42

Universal Field I/O

1 - 80 0 - 633 - 0405

Page 2

Dimensions and Installation It is important to understand the installation requirements for your Terminator I/O system. This will ensure that the Terminator I/O products work within their environmental and electrical limits.

See the Enclosures section for an enclosure that may be suitable for your application

Plan for safety This catalog should never be used as a replacement for the technical data sheet that comes with the products or the T1K-INST-M Installation and I/O Manual (available online at www.automationdirect.com.) The technical data sheet contains information that must be followed. The system installation should comply with all appropriate electrical codes and standards.

Unit dimensions and mounting orientation Use the following diagrams to make sure the Terminator I/O system can be installed in your application. Terminator I/O units should be mounted horizontally. To ensure proper airflow for cooling purposes, units should not be mounted upside-down. It is important to check the Terminator I/O dimensions against the conditions required for your application. For example, it is recommended to leave 2” depth for ease of access and cable clearance. However, your distance may be greater or less. Also, check the installation guidelines for the recommended cabinet clearances.

48mm (1.89in)

32°F to 131°F (0°C to 55°C)

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

Vibration Resistance Shock Resistance Voltage Withstand (Dielectric) Insulation Resistance

MIL STD 810C, Method 514.2

5% to 95% (Non-condensing)

MIL STD 810C, Method 516.2 1500 VAC, 1 minute 500 VDC, 10

Noise Immunity Agency Approvals

UL, CE, FCC class A, NEC Class 1 Division 2

48mm (1.89in)

80mm (3.15in)

Network Interface Module

-4°F to 158°F (-20°C to 70°C)

NEMA ICS3-304 Impulse noise 1µs, 1000 V FCC class A RFI (144 MHz, 430 MHz 10 W, 10 cm)

48mm (1.89in)

80mm (3.15in)

Power Supply

Terminator I/O Environmental Specifications Ambient Operating Temperature Storage Temperature Ambient Humidity

89mm (3.5in)

80mm (3.15in)

Half-size I/O Module with Base

83.3mm (3.28in)

80mm (3.15in)

Full-size I/O Module with Base

System Depth

Volume 13 e8-12

Universal Field I/O

1 - 80 0 - 633 - 0405

Page 3

I/O Module Installation

Company Information

Terminator I/O modules feature separate terminal bases for easy installation.

Systems Overview

DN-ASB-1 angled mounting bracket

I/O module installation 1

To install I/O modules: 1. Slide the module into its terminal base (until it clicks into position) 2. Hook upper DIN rail tabs over the top of DIN rail, and press the assembly firmly onto the DIN rail. 3. Slide the module along the DIN rail until it engages with the adjacent module.

Programmable Controllers

Field I/O

Great for mounting in upper locations

Software C-more & other HMI

Great for mounting in lower locations

Drives Soft Starters

Optional angled support bracket raises and tilts the mounting rail for easier access and wiring. Use with 35 mm DIN rail. See the Connection Systems in this catalog for details.

2

Motors & Gearbox Steppers/ Servos Motor Controls Proximity Sensors Photo Sensors

3

Limit Switches Encoders Current Sensors Pressure Sensors Temperature Sensors Pushbuttons/ Lights Process Relays/ Timers

Removing I/O modules is a snap Grip the locking handle, as shown, and pull gently to eject the I/O module from its base. The module will slide out for easy replacement. This procedure does not apply to network interface modules or power supplies, which have integral bases.

Hot-swappable I/O modules You can remove I/O modules under power, but exercise caution while doing so. Do not touch the terminals with your hands or any conductive material. Always remove power when possible.

Comm. Terminal Blocks & Wiring Power Circuit Protection Enclosures Tools Pneumatics Appendix Product Index Part # Index

Volume 13 w w w. a u to m at i o n d i re c t . c o m / f i e l d I O

Universal Field I/O e8-13

Page 4

Power Supplies and Power Requirements Power supplies

Power requirements

The Terminator I/O product line offers two power supply options: AC or DC. The power supplies are always positioned to the left of the modules to which they supply power. Consult the system configuration examples and the power budgeting example for more information on positioning power supplies.

Module

5VDC 24VDC

Interface Modules

DC Output Modules 200

0

T1F-08AD-1

75

50*

T1H-EBC100

300

0

T1K-08TD1

100

200*

T1F-08AD-2

75

50*

T1H-PBC

530

0

T1K-16TD1

200

400*

T1F-16AD-1

75

50*

T1K-DEVNETS

250

45

T1K-08TD2-1

200

0

T1F-16AD-2

75

50*

T1K-RSSS

250

0

T1K-16TD2-1

200

0

T1F-14THM

60

70*

T1K-MODBUS

300

0

AC Output Modules

T1F-16RTD

150

0

250

0

Analog Output Modules

T1K-08ND3

35

0

T1K-16TA

450

0

T1F-08DA-1

75

75*

T1K-16ND3

70

0

T1K-08TAS

300

0

T1F-08DA-2

75

75*

Relay Output Modules

T1F-16DA-1

75

150*

75

150*

T1K-08NA-1

35

0

T1K-08TR

350

0

T1F-16DA-2

T1K-16NA-1

70

0

T1K-16TR

700

0

Combination Analog Modules

T1K-08TRS

400

0

T1F-8AD4DA-1

75

60*

T1F-8AD4DA-2

75

70*

Specialty Modules

T1K-01DC <--->

T1K-01AC <--->

T1K-08TA

T1H-CTRIO

To calculate the power budget, read the available power (current rating) from the Power Supply Specifications table and subtract the power consumed by each module to the right of the power supply. Do not include modules to the right of an additional power supply.

30 W

Max. Inrush Current 20 A

10 A

Insulation Resistance

> 10 @ 500 VDC

Voltage Withstand

1 min. @ 1500 VAC between primary, secondary and field ground

Voltage

5VDC PWR

5.25 VDC

5.25 VDC

2000 mA max current Current Rating (see option note 2000 mA max below)

Ripple

5% max.

5% max.

Voltage

24 VDC

N/A

300 mA max.

24VDC Current Rating (see current option note PWR

N/A below)

Ripple

Fuse

10% max.

400

0

* Use either internal or external source for 24VDC

* Use either internal or external source for 24VDC

Input Frequency Maximum Power

50 VA

Analog Input Modules

T1H-08TDS

Calculating the power budget

N/A

5VDC 24VDC

0

Input Voltage Range 110/220 VAC 12/24 VDC 50/60 Hz

Module

350

AC Input Modules

Power Supply Specifications

5VDC 24VDC

T1H-EBC

DC Input Modules

Power supply specifications

Module

Adding additional power supplies Each power supply furnishes power only to the network interface and I/O modules to its right. Inserting a second power supply closes the power loop for the power supply to the left, while also powering the modules to its right. Perform a power budget calculation for each power supply in the system.

Power Budget Example Module

5VDC

24VDC

T1K-01AC

+2000 mA

+300 mA

T1H-EBC

-350 mA

-0 mA

T1K-16ND3

-70 mA

-0 mA

T1K-16TD2

-200 mA

-0 mA

T1F-08AD-1

-75 mA

-50 mA

Remaining

+1305 mA

+250 mA

Accessories available for Terminator I/O are listed in the Terminator Field I/O section of the Price List

N/A

1 (primary), not replaceable

Note: 500 mA @ 24 VDC can be achieved by lowering the 5VDC from 2000 mA to 1500 mA .

This power supply powers the network interface module and This power supply powers these three I/O the next two I/O modules modules

Volume 13 e8-14

Universal Field I/O

1 - 80 0 - 633 - 0405

Page 5

Expansion I/O Configurations T1K-05CBL-LL T1K-05CBL-LL-1* Left side to left side expansion cable

Expansion cables T1K-10CBL <---> T1K-10CBL-1* <---> Right side to left side expansion cable The T1K-10CBL(-1) connects the right side of an I/O base to the left side of the next I/O base. A maximum of two T1K-10CBL(-1) cables can be used per expansion system.

Company Information

T1K-05CBL-RR <---> T1K-05CBL-RR-1* <---> Right side to right side expansion cable

<---> <--->

Systems Overview Programmable Controllers

Field I/O

The T1K-05CBL-LL(-1) connects the left side of an I/O base to the left side of the next I/O base. Only one T1K-05CBL-LL (-1) cable can be used per expansion system and must be used with a T1K-05CBL-RR(-1) cable. This cable cannot be connected to the left side of the network interface base.

The T1K-05CBL-RR(-1) connects the right side of an I/O base to the right side of the next I/O base. A maximum of one T1K-05CBL-RR(-1) cable can be used per expansion system. Note: When this cable is used, the expansion I/O assignments are from right to left (reversed).

Software C-more & other HMI Drives Soft Starters Motors & Gearbox

Cable length = 1.0m

Cable length = 0.5m

Cable length = 0.5m

Steppers/ Servos Motor Controls

*Note: The (-1) versions of the expansion cables pass 24 VDC through on an isolated wire. (All cables pass the 5 VDC base power.) Any local expansion DC input module configured for “internal power” (current sourcing) must either have a power supply preceding it on the same base or, have a (-1) version cable pass 24 VDC from a power supply on the preceeding base.

Using two T1K-10CBL expansion cables

Encoders

Power supplies can be used anywhere in the first two bases, but not in the last expansion base. T1K-10CBL(-1)

Photo Sensors Limit Switches

Using T1K-10CBL expansion cable and T1K-05CBL-RR expansion cable

In the system below, power supplies can be used anywhere.

Proximity Sensors

Current Sensors Pressure Sensors

I/O Addressing

A power supply can be used on either base.

Temperature Sensors

I/O Addressing T1K-10CBL(-1)

Pushbuttons/ Lights

T1K-10CBL(-1) Process

A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR(-1).

T1K-05CBL-RR(-1) See Note above

Relays/ Timers Comm.

Using T1K-05CBL-RR expansion cable and T1K-05CBL-LL expansion cable

Using T1K-05CBL-RR expansion cable

Power supplies can be used anywhere in the first and third bases, but not in the second base. Do not connect a T1K-05CBL-LL(-1) to the left side of the network interface base.

Terminal Blocks & Wiring

Power supplies can be used anywhere in the first base, but not in the second base.

Power Circuit Protection Enclosures

I/O Addressing I/O Addressing

T1K-05CBL-RR(-1) See Note above

T1K-05CBL-RR(-1) See Note above

Tools Pneumatics Appendix

T1K-05CBL-LL

A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR(-1).

A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR(-1). Volume 13 w w w. a u to m at i o n d i re c t . c o m / f i e l d I O

Universal Field I/O e8-15

Product Index Part # Index

Page 6

Field Device Wiring and Power Options Terminal base specifications

T1K-08B <--->

T1K-08B-1 <--->

Terminator I/O terminal bases are available in screw clamp and spring clamp versions for both half-size and full-size modules. Hot stamp silkscreen labeling is used for numbering I/O points, commons, and all power terminals. Screw clamp, half-size

Terminal Base Specifications Terminal Type

Screw type

Recommended 1.77-3.54 lb-in (0.2 - 0.4 Nm) Torque Wire Gauge

Solid: 25-12 AWG Stranded: 26-12 AWG

T1K-16B <--->

Spring clamp, half-size

T1K-16B-1 <--->

Spring clamp n/a Solid: 25-14 AWG Stranded: 26-14 AWG Spring clamp, full-size

Screw clamp, full-size

Field device wiring options Power your DC input devices from the integrated 24 VDC power supply bus. T1K-08ND3 and T1K-16ND3 DC input modules include jumpers for selecting the internal 24 VDC power supply available for 2- and 3-wire field devices. Clearly labeled triple stack terminals make it easy to wire 2- and 3-wire devices ensuring clean wiring with only one wire per termination.

2 and 3-wire DC input devices using bussed 24 VDC power

External user supplied 24 VDC power, or auxiliary 24 VDC terminals from T1K-01AC, can be easily applied directly to one end of the terminal rows and jumpered across each base in the system. This is a convenient solution for powering analog I/O and discrete DC output devices whose modules do not have direct access to the internal bussed 24 VDC. If current consumption increases, simply add additional T1K-01AC power supplies into the system.

Use externally supplied 24 VDC power or 24 VDC auxiliary power from T1K-01AC

Do not jumper modules together to create a 24 VDC bus when using the “hot swap” feature. See Note below.

Hot-swap feature The hot-swap feature allows Terminator I/O modules to be replaced while system power is on. Be careful not to touch the terminals with your hands or other conductive material to avoid the risk of personal injury or equipment damage. Always remove power if it is equally convenient to do so.

Note: Before hot-swapping analog or DC output modules in a Terminator I/O system, make sure that each of the analog and DC output module’s 24 VDC and 0 VDC base terminals are wired directly to the external power supply individually. If the external 24 VDC and 0 VDC is jumpered from base to base in a daisy chain fashion, and an analog or DC output module is removed from its base, the risk of disconnecting the external 24 VDC and 0 VDC to the subsequent I/O modules exists.

Volume 13 e8-16

Universal Field I/O

1 - 80 0 - 633 - 0405