Spec sheet · AutomationDirect
Relay Output Modules T1K-08TRS
Spec sheet6 pagesPDF 3.4 MB
Catalog pages for the T1K-08TRS 8-point isolated relay output module of the Terminator I/O system, with installation and power data.
Covers · 3 models
The models it covers
Summary
What is in it
Catalog pages for the T1K-08TRS, an 8-point isolated relay output module for the Terminator I/O system. They give its output specifications, typical relay life and fusing, then general Terminator I/O information: dimensions and environmental specifications, installing and hot-swapping I/O modules, power supplies and power budgeting, expansion cable configurations, and terminal bases and field device wiring options.
Its parts
- Relay Output Modules
- Dimensions and Installation
- I/O Module Installation
- Power Supplies and Power Requirements
- Expansion I/O Configurations
- Field Device Wiring and Power Options
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Pages from the AutomationDirect Universal Field I/O catalog for the T1K-08TRS 8-point isolated relay output module of the Terminator I/O family. Besides the module's own specification page it covers installation, power supplies and the power budget, expansion cables and terminal base wiring for Terminator I/O systems.
- Device
- 8-point, isolated relay output module for Terminator I/O p. 1, 4
- Terminal base
- T1K-16B or T1K-16B-1, purchased separately p. 1
- Base power
- 400 mA at 5VDC; 0 at 24VDC p. 4
- Fuses
- User replaceable T1K-FUSE-3, one point per fuse p. 1
- Fuse LEDs
- FU1/FU2 lit means fuse 1 or 2 blown, and likewise FU3/FU4, FU5/FU6, FU7/FU8 p. 1
- Inductive loads
- Solenoid (inductive) loads above 2A cannot be used p. 1
- Hot swap
- I/O modules can be removed and replaced with system power on p. 3, 6
- Terminal wiring
- Screw type bases: 1.77-3.54 lb-in (0.2 - 0.4 Nm), solid 25-12 AWG, stranded 26-12 AWG; spring clamp bases: solid 25-14 AWG, stranded 26-14 AWG p. 6
- Mounting
- On DIN rail, horizontally, never upside-down p. 2, 3
- Power supply example
- T1K-01AC supplies 2000 mA at 5VDC and 300 mA at 24VDC in the power budget example p. 4
- Expansion cables
- T1K-10CBL(-1), T1K-05CBL-RR(-1) and T1K-05CBL-LL(-1); the (-1) versions also pass 24 VDC p. 5
What this sheet walks you through
- Installing an I/O module in its terminal base and on DIN rail p. 3
- Removing an I/O module from its base p. 3
- Checking unit dimensions and mounting orientation p. 2
- Calculating the power budget for each power supply p. 4
- Laying out expansion bases with expansion cables p. 5
- Powering field devices from the bussed or an external 24 VDC supply p. 6
Good to know
- Solenoid (inductive) loads over 2A cannot be used on this module. p. 1
- When hot swapping, do not touch the terminals, and remove power when it is just as convenient. p. 6
- Do not jumper modules together into a 24 VDC bus when using hot swap; wire each module to the external supply. p. 6
- The catalog does not replace the product's technical data sheet or the T1K-INST-M Installation and I/O Manual. p. 2
Questions this sheet answers
What base does the T1K-08TRS need?
A T1K-16B or T1K-16B-1 terminal base, which is purchased separately. p. 1
What fuse does the T1K-08TRS use?
User replaceable T1K-FUSE-3 fuses; LEDs such as FU1/FU2 light when a fuse in that pair is blown. p. 1
Can the T1K-08TRS drive solenoid valves?
Only solenoid (inductive) loads of 2A or less; larger inductive loads cannot be used. p. 1
How much power does the T1K-08TRS draw from the supply?
400 mA at 5VDC and none at 24VDC, per the power requirements table. p. 4
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 1 part
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.