The text of a spec sheet · part 1 of 1
DeviceNet Slave T1K-DEVNETS, pages 1 to 7
Pages 1 to 7 of 7
The original document is the PDF (3.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect T1K-DEVNETS
Page 1
TM
DeviceNet Slave T1K-DEVNETS <--->
Here’s how it works: The T1K-DEVNETS module is a DeviceNet slave. This module maintains a database with all the identification data, diagnostic information, and parameters that control the module operation. The T1K-DEVNETS module scans and reports all discrete and analog I/O data to a DeviceNet master. The AC power supply provides a 24 VDC output for simple wiring of sensors and actuators into the Terminator I/O modules. Using our Terminator I/O DeviceNet sub-system will increase installation flexibility as well as save on wiring costs. The T1K-DEVNETS module supports all Terminator I/O discrete and analog I/O modules.
TM
The T1K-DEVNETS also offers the following features: • Cost-effective: With a single network for devices, hardwiring costs are reduced. • Easy connectivity: Low-cost four wire installation is easy to implement and maintain. • Innovative technology: Power is integrated into the device wiring. • Diagnostics: The module provides advanced error diagnostics not commonly available in traditional control systems. • Highly dependable: Fast response for demanding applications. • LED indicators: Provide quick indication of Terminator I/O power and operating mode.
General Specifications
DeviceNet I/O system overview If you are already using or planning to implement a DeviceNet controller network, our Terminator I/O sub-system will help further reduce the cost of your overall application. We now offer the T1K-DEVNETS (slave) module, which allows our Terminator I/O sub-system to be linked with a DeviceNet master controller. DeviceNet is a low-cost control network that provides a common method to connect on a single network. This advanced communications media and software is referred to as DeviceNet and significantly reduces hardwiring costs. DeviceNet provides specifications for information exchanged between nodes, such as controller data associated with low-level devices and configuration parameters individually related to system operations.
DeviceNet Compatibility Maximum Field Devices per Bus
Predefined Group 2 master/slave communications 64 (see table next page)
Maximum I/O Points per DEVNETS
1024 input bits (analog or discrete 1024 output bits (analog or discrete as specified by DeviceNet Slave Polling Specification
Communication to Field Devices
Standard 4-wire shielded cable to cabinet connector, molded 4-wire cable @ up to 500Kbps to field devices
Serial Port Module Connector Operating Temperature Storage Temperature Relative Humidity Environmental Air Vibration Shock
RS232C, RJ12, Protocol support: K-sequence, ASCII
Noise Immunity
NEMA ICS3-304,Impulse noise 1ms, 1000V FCC class A, RFI (144Mhz, 430Mhz 10W, 10cm)
TM
5-position removable terminal (European style) 0 to 55°C (32 to 131°F) -20 to 70°C (-4 to 158°F) 5 to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2
Connect our Terminator I/O to your DeviceNet network.
Volume 13 e8-22
Universal Field I/O
1 - 80 0 - 633 - 0405
Page 2
DeviceNet Slave
Company Information Systems Overview Programmable Controllers
Field I/O Software C-more & other HMI Drives Soft Starters Motors & Gearbox Steppers/ Servos Motor Controls Proximity Sensors Photo Sensors Limit Switches Encoders
Please Note:
Recommended cable: Belden 3085A, YR-29832 (or equivalent)
Current Sensors
1. For use with Think & Do Software, we recommend the SST DeviceNet PCI Master Card, part number 5136-DNP-PCI. (AutomationDirect does not provide this interface). See www.mysst.com for more information. 2. Terminator I/O DeviceNet slave network interface module T1K-DEVNETS is an ODVA certified DeviceNet-compliant slave I/O interface product. See www.odva.com for more information.
DeviceNet cable
Pressure Sensors Temperature Sensors Pushbuttons/ Lights Process Relays/ Timers Comm.
Trunk Length
Comm Speed
Branch Length
Devices
Feet
Meters
Baud
Feet
Meters
Maximum
328
100
500 Kbps
20
6
64
820
250
250 Kbps
20
6
64
1,640
500
125 Kbps
20
6
64
Terminal Blocks & Wiring Power Circuit Protection
For other DeviceNet specifications, compatible products and latest DeviceNet information, contact: Open DeviceNet Vendor Association Contact: Executive Director Katherine Voss Phone: 734/975-8840 • Fax: 734/922-0027 Internet address: http://www.odva.org e-mail: odva@odva.org ODVA, Inc. • 1099 Highland Drive, Suite A, Ann Arbor, MI. 48108
Enclosures Tools Pneumatics Appendix Product Index Part # Index
Volume 13 w w w. a u to m at i o n d i re c t . c o m / f i e l d I O
Universal Field I/O e8-23
Page 3
Dimensions and Installation It is important to understand the installation requirements for your Terminator I/O system. This will ensure that the Terminator I/O products work within their environmental and electrical limits.
See the Enclosures section for an enclosure that may be suitable for your application
Plan for safety This catalog should never be used as a replacement for the technical data sheet that comes with the products or the T1K-INST-M Installation and I/O Manual (available online at www.automationdirect.com.) The technical data sheet contains information that must be followed. The system installation should comply with all appropriate electrical codes and standards.
Unit dimensions and mounting orientation Use the following diagrams to make sure the Terminator I/O system can be installed in your application. Terminator I/O units should be mounted horizontally. To ensure proper airflow for cooling purposes, units should not be mounted upside-down. It is important to check the Terminator I/O dimensions against the conditions required for your application. For example, it is recommended to leave 2” depth for ease of access and cable clearance. However, your distance may be greater or less. Also, check the installation guidelines for the recommended cabinet clearances.
48mm (1.89in)
32°F to 131°F (0°C to 55°C)
Atmosphere
No corrosive gases. The level of environmental pollution = 2 (UL 840)
Vibration Resistance Shock Resistance Voltage Withstand (Dielectric) Insulation Resistance
MIL STD 810C, Method 514.2
5% to 95% (Non-condensing)
MIL STD 810C, Method 516.2 1500 VAC, 1 minute 500 VDC, 10
Noise Immunity Agency Approvals
UL, CE, FCC class A, NEC Class 1 Division 2
48mm (1.89in)
80mm (3.15in)
Network Interface Module
-4°F to 158°F (-20°C to 70°C)
NEMA ICS3-304 Impulse noise 1µs, 1000 V FCC class A RFI (144 MHz, 430 MHz 10 W, 10 cm)
48mm (1.89in)
80mm (3.15in)
Power Supply
Terminator I/O Environmental Specifications Ambient Operating Temperature Storage Temperature Ambient Humidity
89mm (3.5in)
80mm (3.15in)
Half-size I/O Module with Base
83.3mm (3.28in)
80mm (3.15in)
Full-size I/O Module with Base
System Depth
Volume 13 e8-12
Universal Field I/O
1 - 80 0 - 633 - 0405
Page 4
I/O Module Installation
Company Information
Terminator I/O modules feature separate terminal bases for easy installation.
Systems Overview
DN-ASB-1 angled mounting bracket
I/O module installation 1
To install I/O modules: 1. Slide the module into its terminal base (until it clicks into position) 2. Hook upper DIN rail tabs over the top of DIN rail, and press the assembly firmly onto the DIN rail. 3. Slide the module along the DIN rail until it engages with the adjacent module.
Programmable Controllers
Field I/O
Great for mounting in upper locations
Software C-more & other HMI
Great for mounting in lower locations
Drives Soft Starters
Optional angled support bracket raises and tilts the mounting rail for easier access and wiring. Use with 35 mm DIN rail. See the Connection Systems in this catalog for details.
2
Motors & Gearbox Steppers/ Servos Motor Controls Proximity Sensors Photo Sensors
3
Limit Switches Encoders Current Sensors Pressure Sensors Temperature Sensors Pushbuttons/ Lights Process Relays/ Timers
Removing I/O modules is a snap Grip the locking handle, as shown, and pull gently to eject the I/O module from its base. The module will slide out for easy replacement. This procedure does not apply to network interface modules or power supplies, which have integral bases.
Hot-swappable I/O modules You can remove I/O modules under power, but exercise caution while doing so. Do not touch the terminals with your hands or any conductive material. Always remove power when possible.
Comm. Terminal Blocks & Wiring Power Circuit Protection Enclosures Tools Pneumatics Appendix Product Index Part # Index
Volume 13 w w w. a u to m at i o n d i re c t . c o m / f i e l d I O
Universal Field I/O e8-13
Page 5
Power Supplies and Power Requirements Power supplies
Power requirements
The Terminator I/O product line offers two power supply options: AC or DC. The power supplies are always positioned to the left of the modules to which they supply power. Consult the system configuration examples and the power budgeting example for more information on positioning power supplies.
Module
5VDC 24VDC
Interface Modules
DC Output Modules 200
0
T1F-08AD-1
75
50*
T1H-EBC100
300
0
T1K-08TD1
100
200*
T1F-08AD-2
75
50*
T1H-PBC
530
0
T1K-16TD1
200
400*
T1F-16AD-1
75
50*
T1K-DEVNETS
250
45
T1K-08TD2-1
200
0
T1F-16AD-2
75
50*
T1K-RSSS
250
0
T1K-16TD2-1
200
0
T1F-14THM
60
70*
T1K-MODBUS
300
0
AC Output Modules
T1F-16RTD
150
0
250
0
Analog Output Modules
T1K-08ND3
35
0
T1K-16TA
450
0
T1F-08DA-1
75
75*
T1K-16ND3
70
0
T1K-08TAS
300
0
T1F-08DA-2
75
75*
Relay Output Modules
T1F-16DA-1
75
150*
75
150*
T1K-08NA-1
35
0
T1K-08TR
350
0
T1F-16DA-2
T1K-16NA-1
70
0
T1K-16TR
700
0
Combination Analog Modules
T1K-08TRS
400
0
T1F-8AD4DA-1
75
60*
T1F-8AD4DA-2
75
70*
Specialty Modules
T1K-01DC <--->
T1K-01AC <--->
T1K-08TA
T1H-CTRIO
To calculate the power budget, read the available power (current rating) from the Power Supply Specifications table and subtract the power consumed by each module to the right of the power supply. Do not include modules to the right of an additional power supply.
30 W
Max. Inrush Current 20 A
10 A
Insulation Resistance
> 10 @ 500 VDC
Voltage Withstand
1 min. @ 1500 VAC between primary, secondary and field ground
Voltage
5VDC PWR
5.25 VDC
5.25 VDC
2000 mA max current Current Rating (see option note 2000 mA max below)
Ripple
5% max.
5% max.
Voltage
24 VDC
N/A
300 mA max.
24VDC Current Rating (see current option note PWR
N/A below)
Ripple
Fuse
10% max.
400
0
* Use either internal or external source for 24VDC
* Use either internal or external source for 24VDC
Input Frequency Maximum Power
50 VA
Analog Input Modules
T1H-08TDS
Calculating the power budget
N/A
5VDC 24VDC
0
Input Voltage Range 110/220 VAC 12/24 VDC 50/60 Hz
Module
350
AC Input Modules
Power Supply Specifications
5VDC 24VDC
T1H-EBC
DC Input Modules
Power supply specifications
Module
Adding additional power supplies Each power supply furnishes power only to the network interface and I/O modules to its right. Inserting a second power supply closes the power loop for the power supply to the left, while also powering the modules to its right. Perform a power budget calculation for each power supply in the system.
Power Budget Example Module
5VDC
24VDC
T1K-01AC
+2000 mA
+300 mA
T1H-EBC
-350 mA
-0 mA
T1K-16ND3
-70 mA
-0 mA
T1K-16TD2
-200 mA
-0 mA
T1F-08AD-1
-75 mA
-50 mA
Remaining
+1305 mA
+250 mA
Accessories available for Terminator I/O are listed in the Terminator Field I/O section of the Price List
N/A
1 (primary), not replaceable
Note: 500 mA @ 24 VDC can be achieved by lowering the 5VDC from 2000 mA to 1500 mA .
This power supply powers the network interface module and This power supply powers these three I/O the next two I/O modules modules
Volume 13 e8-14
Universal Field I/O
1 - 80 0 - 633 - 0405
Page 6
Expansion I/O Configurations T1K-05CBL-LL T1K-05CBL-LL-1* Left side to left side expansion cable
Expansion cables T1K-10CBL <---> T1K-10CBL-1* <---> Right side to left side expansion cable The T1K-10CBL(-1) connects the right side of an I/O base to the left side of the next I/O base. A maximum of two T1K-10CBL(-1) cables can be used per expansion system.
Company Information
T1K-05CBL-RR <---> T1K-05CBL-RR-1* <---> Right side to right side expansion cable
<---> <--->
Systems Overview Programmable Controllers
Field I/O
The T1K-05CBL-LL(-1) connects the left side of an I/O base to the left side of the next I/O base. Only one T1K-05CBL-LL (-1) cable can be used per expansion system and must be used with a T1K-05CBL-RR(-1) cable. This cable cannot be connected to the left side of the network interface base.
The T1K-05CBL-RR(-1) connects the right side of an I/O base to the right side of the next I/O base. A maximum of one T1K-05CBL-RR(-1) cable can be used per expansion system. Note: When this cable is used, the expansion I/O assignments are from right to left (reversed).
Software C-more & other HMI Drives Soft Starters Motors & Gearbox
Cable length = 1.0m
Cable length = 0.5m
Cable length = 0.5m
Steppers/ Servos Motor Controls
*Note: The (-1) versions of the expansion cables pass 24 VDC through on an isolated wire. (All cables pass the 5 VDC base power.) Any local expansion DC input module configured for “internal power” (current sourcing) must either have a power supply preceding it on the same base or, have a (-1) version cable pass 24 VDC from a power supply on the preceeding base.
Using two T1K-10CBL expansion cables
Encoders
Power supplies can be used anywhere in the first two bases, but not in the last expansion base. T1K-10CBL(-1)
Photo Sensors Limit Switches
Using T1K-10CBL expansion cable and T1K-05CBL-RR expansion cable
In the system below, power supplies can be used anywhere.
Proximity Sensors
Current Sensors Pressure Sensors
I/O Addressing
A power supply can be used on either base.
Temperature Sensors
I/O Addressing T1K-10CBL(-1)
Pushbuttons/ Lights
T1K-10CBL(-1) Process
A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR(-1).
T1K-05CBL-RR(-1) See Note above
Relays/ Timers Comm.
Using T1K-05CBL-RR expansion cable and T1K-05CBL-LL expansion cable
Using T1K-05CBL-RR expansion cable
Power supplies can be used anywhere in the first and third bases, but not in the second base. Do not connect a T1K-05CBL-LL(-1) to the left side of the network interface base.
Terminal Blocks & Wiring
Power supplies can be used anywhere in the first base, but not in the second base.
Power Circuit Protection Enclosures
I/O Addressing I/O Addressing
T1K-05CBL-RR(-1) See Note above
T1K-05CBL-RR(-1) See Note above
Tools Pneumatics Appendix
T1K-05CBL-LL
A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR(-1).
A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR(-1). Volume 13 w w w. a u to m at i o n d i re c t . c o m / f i e l d I O
Universal Field I/O e8-15
Product Index Part # Index
Page 7
Field Device Wiring and Power Options Terminal base specifications
T1K-08B <--->
T1K-08B-1 <--->
Terminator I/O terminal bases are available in screw clamp and spring clamp versions for both half-size and full-size modules. Hot stamp silkscreen labeling is used for numbering I/O points, commons, and all power terminals. Screw clamp, half-size
Terminal Base Specifications Terminal Type
Screw type
Recommended 1.77-3.54 lb-in (0.2 - 0.4 Nm) Torque Wire Gauge
Solid: 25-12 AWG Stranded: 26-12 AWG
T1K-16B <--->
Spring clamp, half-size
T1K-16B-1 <--->
Spring clamp n/a Solid: 25-14 AWG Stranded: 26-14 AWG Spring clamp, full-size
Screw clamp, full-size
Field device wiring options Power your DC input devices from the integrated 24 VDC power supply bus. T1K-08ND3 and T1K-16ND3 DC input modules include jumpers for selecting the internal 24 VDC power supply available for 2- and 3-wire field devices. Clearly labeled triple stack terminals make it easy to wire 2- and 3-wire devices ensuring clean wiring with only one wire per termination.
2 and 3-wire DC input devices using bussed 24 VDC power
External user supplied 24 VDC power, or auxiliary 24 VDC terminals from T1K-01AC, can be easily applied directly to one end of the terminal rows and jumpered across each base in the system. This is a convenient solution for powering analog I/O and discrete DC output devices whose modules do not have direct access to the internal bussed 24 VDC. If current consumption increases, simply add additional T1K-01AC power supplies into the system.
Use externally supplied 24 VDC power or 24 VDC auxiliary power from T1K-01AC
Do not jumper modules together to create a 24 VDC bus when using the “hot swap” feature. See Note below.
Hot-swap feature The hot-swap feature allows Terminator I/O modules to be replaced while system power is on. Be careful not to touch the terminals with your hands or other conductive material to avoid the risk of personal injury or equipment damage. Always remove power if it is equally convenient to do so.
Note: Before hot-swapping analog or DC output modules in a Terminator I/O system, make sure that each of the analog and DC output module’s 24 VDC and 0 VDC base terminals are wired directly to the external power supply individually. If the external 24 VDC and 0 VDC is jumpered from base to base in a daisy chain fashion, and an analog or DC output module is removed from its base, the risk of disconnecting the external 24 VDC and 0 VDC to the subsequent I/O modules exists.
Volume 13 e8-16
Universal Field I/O
1 - 80 0 - 633 - 0405