Spec sheet · B & R Automation
X20(c)DI4371
Spec sheet7 pagesPDF 457 KB
Data sheet for the B&R X20DI4371 and coated X20cDI4371 4-channel 24 VDC sink digital input modules with event counters.
Covers · 1 model
The models it covers
Summary
What is in it
The data sheet for the B&R X20DI4371 digital input module and its coated X20cDI4371 version: four 24 VDC sink inputs for 3-wire sensors, with sensor supply and four 1 kHz event counters. It gives order data and required accessories, technical data and certifications, status LEDs, pinout, a connection example, the input circuit and filter, and the register description for the standard, event counter and bus controller function models, with minimum cycle and I/O update times.
Its parts
- General Information
- Coated modules
- Order data
- Technical data
- Status LEDs
- Pinout
- Connection example
- Input circuit diagram
- Input filter
- Register description
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
This is the B&R data sheet (V 3.13) for the X20DI4371 digital input module and its coated twin, the X20cDI4371. It gives order data and required accessories, technical data, status LEDs, pinout, the input filter, and the registers for the standard, event counter and bus controller function models.
- What it is
- X20 digital input module: 4 inputs, 24 VDC, sink, configurable input filter, 3-wire connections p. 1
- Sensor supply
- 24 VDC and GND for sensor supply; sensors may draw at most 12 W in total p. 1, 3
- Counter inputs
- 4 counter inputs, 1 kHz counter frequency p. 1
- Event counters
- From hardware variant F0 and firmware version 801: four software counters, rising, falling or both edges, values 0 to 65535 p. 6
- Input filter
- Software filter for the entire module, off or 0.2 ms to 25 ms; inputs sampled every 200 μs p. 1, 6
- Required accessories
- 1x X20TB12 terminal block (12-pin, 24 VDC keyed) and 1x X20BM11 or X20cBM11 bus module, ordered separately p. 1, 3
- Coated version
- X20cDI4371: protective coating against condensation and corrosive gases; electronics fully compatible p. 1
- Function models
- 0 Standard, 1 Event counter, 254 Bus Controller p. 5
- CAN I/O
- Occupies 1 digital logical slot on CAN-I/O p. 5
What this sheet walks you through
- Order data and required accessories p. 1
- Technical data and environmental conditions p. 2, 3
- Reading the status LEDs p. 3
- Pinout and sensor connection example p. 3, 4
- Setting the input filter p. 4, 6
- Registers for the standard, event counter and bus controller function models p. 5
- Reading, resetting and configuring the event counters p. 6, 7
- Minimum cycle time and minimum I/O update time p. 7
Good to know
- The sensors connected to the module may draw no more than 12 W in total. p. 3
- A counter is reset only on a positive edge of its reset bit; a reset bit left set does not stop counting. p. 7
- Filter values above 25 ms are limited to 25 ms, and steps of 2 make sense because inputs are sampled every 200 μs. p. 6
- Very fast bus cycles leave less idle time for monitoring, diagnostics and acyclic commands. p. 7
Questions this sheet answers
What terminal block and bus module does the X20DI4371 need?
One X20TB12 terminal block and one X20BM11 or X20cBM11 bus module, each ordered separately. p. 3
Can the X20DI4371 count pulses?
Yes. From hardware variant F0 and firmware version 801 it has four edge counters; the counter inputs run at 1 kHz. p. 1, 6
What is the difference between the X20DI4371 and the X20cDI4371?
The X20cDI4371 has a protective coating against condensation and corrosive gases; its electronics are fully compatible. p. 1
How is the X20DI4371 input filter set?
With register ConfigOutput01, in steps of 100 μs from no filter up to 25 ms, for all inputs at once. p. 6
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 1 part
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file