For the B & R Automation X20DI4371

Page 1

X20(c)DI4371

X20(c)DI4371 1 General Information The module is equipped with four inputs for 3-wire connections. • • • • • •

4 digital inputs Sink connection 3-wire connections 4 counter inputs with 1 kHz counter frequency 24 VDC and GND for sensor supply Software input filter can be configured for entire module

2 Coated modules Coated modules are X20 modules with a protective coating for the electronics component. This coating protects X20c modules from condensation and corrosive gases. The modules' electronics are fully compatible with the corresponding X20 modules. For simplification purposes, only images and module IDs of uncoated modules are used in this data sheet. The coating has been certified according to the following standards: • Condensation: BMW GS 95011-4, 2x 1 cycle • Corrosive gas: EN 60068-2-60, Method 4, exposure 21 days

3 Order data Model number X20DI4371 X20cDI4371

X20BM11 X20cBM11

X20TB12

Short description Digital inputs X20 digital input module, 4 inputs, 24 VDC, sink, configurable input filter, 3-wire connections X20 digital input module, coated, 4 inputs, 24 VDC, sink, configurable input filter, 3-wire connections Required accessories Bus modules X20 bus module, 24 VDC keyed, internal I/O supply continuous X20 bus module, coated, 24 VDC keyed, internal I/O supply continuous Terminal blocks X20 terminal block, 12-pin, 24 VDC keyed

Figure

Table 1: X20DI4371, X20cDI4371 - Order data

Data sheet V 3.13

1

Page 2

X20(c)DI4371

4 Technical data Model number Short description I/O module General information B&R ID code Status indicators Diagnostics Module run/error Power consumption Bus Internal I/O Additional power dissipation caused by the actuators (resistive) [W] Electrical isolation Channel - Bus Channel - Channel Certification CE KC UL HazLoc

ATEX DNV GL

LR GOST-R Digital inputs Nominal voltage Input voltage Input current at 24 VDC Input filter Hardware Software Connection type Input circuit Input resistance Switching threshold Low High Isolation voltage between channel and bus Event counter Quantity Signal form Evaluation Input frequency Counter 1 Counter 2 Counter 3 Counter 4 Counter frequency Counter size Sensor supply Power consumption Voltage Voltage drop for short circuit protection at 500 mA Summation current Short circuit protection Operating conditions Mounting orientation Horizontal Vertical Installation at elevations above sea level 0 to 2000 m >2000 m

X20DI4371

X20cDI4371

4 digital inputs 24 VDC for 3-wire connections 0x1B92 0xE21F I/O function per channel, operating state, module status Yes, using status LED and software 0.14 W 0.59 W -

Yes No Yes Yes cULus E115267 Industrial Control Equipment cCSAus 244665 Process Control Equipment for Hazardous Locations Class I, Division 2, Groups ABCD, T5 Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta = 0 - max. 60°C FTZÚ 09 ATEX 0083X Temperature: B (0 - 55°C) Humidity: B (up to 100%) Vibration: B (4g) EMC: B (Bridge and open deck) ENV1 Yes

-

24 VDC 24 VDC -15 % / +20 % Typ. 3.75 mA ≤100 μs Default 1 ms, configurable between 0 and 25 ms in 0.2 ms intervals 3-wire connections Sink Typ. 6.4 kΩ <5 VDC >15 VDC 500 Veff 4 Square wave pulse Configurable edge event, cyclic counter Max. 1 kHz Input 1 Input 2 Input 3 Input 4 Max. 1 kHz (when input filter switched off) 16-bit Max. 12 W 1) Module supply minus voltage drop for short circuit protection Max. 2 VDC 0.5 A Yes

Yes Yes No limitations Reduction of ambient temperature by 0.5°C per 100 m

Table 2: X20DI4371, X20cDI4371 - Technical data 2

Data sheet V 3.13

Page 3

X20(c)DI4371 Model number EN 60529 protection Environmental conditions Temperature Operation Horizontal installation Vertical installation Derating Storage Transport Relative humidity Operation Storage Transport Mechanical characteristics Note

X20DI4371

IP20

X20cDI4371

-25 to 60°C -25 to 50°C -40 to 85°C -40 to 85°C 5 to 95%, non-condensing

Up to 100%, condensing 5 to 95%, non-condensing 5 to 95%, non-condensing

Order 1x X20TB12 terminal block separately Order 1x X20TB12 terminal block separately Order 1x X20BM11 bus module separately Order 1x X20cBM11 bus module separately 12.5+0.2 mm

Spacing

Table 2: X20DI4371, X20cDI4371 - Technical data 1)

The power consumption of the sensors connected to the module is not permitted to exceed 12 W.

5 Status LEDs For a description of the various operating modes, see section "Additional information - Diagnostic LEDs" of the X20 system user's manual. Image

LED r e e+r 1-4

Color Green

Status Off Single flash Blinking On Red Off Red on / Green single flash Green

Description No power to module RESET mode PREOPERATIONAL mode RUN mode Module supply not connected or everything OK Invalid firmware Input status of the corresponding digital input

X20 DI 4371

6 Pinout

Data sheet V 3.13 r e 1 2 3 4

DI 1

DI 2

+24 VDC

+24 VDC

GND

GND

DI 3

DI 4

+24 VDC

+24 VDC

GND

GND

3

Page 4

X20(c)DI4371

7 Connection example

Sensor 2 Sensor 4

Sensor 3

Sensor 1

DI

+24 VDC GND

+24 VDC GND

8 Input circuit diagram Input x VDR

GND I/O status LED (green)

PTC

Input status

24 V

24 V GND GND

9 Input filter An input filter is available for each input. The input delay can be set using register "ConfigOutput01" on page 6. Disturbance pulses which are shorter than the input delay are suppressed by the input filter. Input signal time Signal after the filter tDelay tDelay tDelay time tDelay ⇒ Input delay

4

Data sheet V 3.13

Page 5

X20(c)DI4371

10 Register description 10.1 General data points In addition to the registers listed in the register description, the module also has other more general data points. These registers are not specific to the module but contain general information such as serial number and hardware version. These general data points are listed in section "Additional information - General data points" of the X20 system user's manual.

10.2 Function model 0 - Standard Register

Fixed offset

0

1

18

-

Name DigitalInput DigitalInput01 ... DigitalInput04 ConfigOutput01

Data type USINT Bit 0 ... Bit 3 USINT

Cyclic ●

Read

Acyclic

Cyclic

Write

Acyclic

●

Fixed modules require their data points to be in a specific order in the X2X frame. Cyclic access occurs according to a predefined offset, not based on the register address. Acyclic access continues to be based on the register numbers.

10.3 Function model 1 - Event counter Register

Fixed offset

0

1

4 6 8 10 12

2 4 6 8 0

18 14

-

Name Input status of digital inputs 1 to 4 DigitalInput01 ... DigitalInput04 Counter01 Counter02 Counter03 Counter04 Resets the counter registers ResetCounter01 ... ResetCounter04 ConfigOutput01 ConfigOutput02

Data type USINT Bit 0 ... Bit 3 UINT UINT UINT UINT USINT Bit 0 ... Bit 3 USINT USINT

Cyclic ●

Read

Acyclic

Cyclic

Write

Acyclic

● ● ● ● ●

● ●

Fixed modules require their data points to be in a specific order in the X2X frame. Cyclic access occurs according to a predefined offset, not based on the register address. Acyclic access continues to be based on the register numbers.

10.4 Function model 254 - Bus Controller

1)

Register

Offset1)

0

0

18

-

Name Input status of digital inputs 1 to 4 DigitalInput01 ... DigitalInput04 ConfigOutput01

Data type USINT Bit 0 ... Bit 3 USINT

Cyclic ●

Read

Acyclic

Cyclic

Write

Acyclic

●

The offset specifies where the register is within the CAN object.

10.4.1 CAN I/O bus controller The module occupies 1 digital logical slot on CAN-I/O 1.

Data sheet V 3.13

5

Page 6

X20(c)DI4371

10.5 Digital inputs Unfiltered The input state is collected with a fixed offset to the network cycle and transferred in the same cycle. Filtered The filtered status is collected with a fixed offset to the network cycle and transferred in the same cycle. Filtering takes place asynchronously to the network in multiples of 200 µs with a network-related jitter of up to 50 µs. 10.5.1 Digital input filter Name: ConfigOutput01 This register can be used to specify the filter value for all digital inputs. The filter value can be configured in steps of 100 μs. It makes sense to enter values in steps of 2, however, since the input signals are sampled every 200 μs. Data type USINT

Value 0 2 ... 250

Filter No software filter 0.2 ms ... 25 ms - Higher values are limited to this value

10.5.2 Input status of digital inputs 1 to 4 Name: DigitalInput or DigitalInput01 to DigitalInput04 The input status of digital inputs 1 to 4 is mapped in this register. Function model 0 - Standard only: The "Packed inputs" setting in the Automation Studio I/O configuration is used to determine whether all of the bits from these registers should be set up individually as data points in the Automation Studio I/O mapping ("DigitalInput01" through "DigitalInput04") or whether this register should be displayed as an individual USINT data point ("DigitalInput"). Data type USINT

Value 0 to 15 See bit structure

Information Packed inputs = on Packed inputs = off or function model <> 0 - Standard

Bit structure: Bit 0 ... 3

Name DigitalInput01

Value 0 or 1 ... 0 or 1

DigitalInput04

Information Input status - Digital input 1 Input status - Digital input 4

10.6 The event counter function model Starting with hardware variant F0 and firmware version 801, the module has four software counters for signal edges. Each counter register can be configured individually for falling, rising or both edges. 10.6.1 Counter register Name: Counter01 to Counter04 These registers provide the current counter value for the configured events. Data type UINT

6

Value 0 to 65535

Data sheet V 3.13

Page 7

X20(c)DI4371 10.6.2 Resets the counter registers Name: ResetCounter01 to ResetCounter04 Using these data points, the corresponding counter registers can be reset to 0. Data type USINT

Value See bit structure.

Bit structure: Bit 0

Name ResetCounter01

... 3

ResetCounter04

Value 0 1 ... 0 1

Information No change Counter register 1 is reset No change Counter register 4 is reset

Information: A counter is only reset if a positive edge is detected on the reset bit. A continually set reset bit does not prevent counting in the counter register. 10.6.3 Configuration of the edges Name: ConfigOutput02 This register is used to configure which event will be assessed on the channel input for the respective counter. Data type USINT

Value See bit structure.

Bit structure: Bit 0

Name Rising edge on input 1

... 3

Rising edge on input 4

4

Falling edge on input 1

... 7

Falling edge on input 4

Value 0 1 ... 0 1 0 1 ... 0 1

Information Event is not counted Event increments Counter01 Event is not counted Event increments Counter04 Event is not counted Event increments Counter01 Event is not counted Event increments Counter04

10.7 Minimum cycle time The minimum cycle time defines how far the bus cycle can be reduced without communication errors occurring. Note that very fast cycles decrease the idle time available for handling monitoring, diagnostics and acyclic commands. Without filtering With filtering

Minimum cycle time

100 μs 150 μs

10.8 Minimum I/O update time The minimum I/O update time defines how far the bus cycle can be reduced while still allowing an I/O update to take place in each cycle. Without filtering With filtering

Data sheet V 3.13

Minimum I/O update time

100 μs 200 μs

7