The text of a spec sheet · part 3 of 5
Compact Sensors (Photoelectrics), pages 19 to 27
Pages 19 to 27 of 42
The original document is the PDF (8.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Banner S18SN6D
Page 19
MINI-BEAM® Expert™ Series Compact Sensors
Supply Voltage and Current
10 to 30V dc (10% max. ripple) at less than 45 mA, exclusive of load
Supply Protection Circuitry
Protected against reverse polarity and transient voltages
Output Configuration
Bipolar: One current sourcing (PNP) and one current sinking (NPN) open-collector transistor. Configuration in TEACH sequence for Light Operate (LO) or Dark Operate (DO).
Output Rating
150 mA max. each output at 25° C, derated to 100 mA at 70° C (derate ≈ 1 mA per ° C) Off-state leakage current: less than 5 µA @ 30V dc Output saturation voltage (PNP output): less than 1 volt at 10 mA and less than 2 volts at 150 mA Output saturation voltage (NPN output): less than 200 millivolts at 10 mA and less than 1 volt at 150 mA
Output Protection Circuitry
Protected against false pulse on power-up and continuous overload or short-circuit of outputs
Output Response Time
Sensors will respond to either a “light” or a “dark” signal of 500 microseconds or longer duration, 1 kHz max. NOTE: 1 second delay on power-up; outputs do not conduct during this time.
Repeatability
100 microseconds (all models)
Adjustments
Push-button TEACH mode sensitivity setting; remote TEACH mode input is provided (gray wire)
Indicators
Two LEDs: Yellow and Bicolor Green/Red
PHOTOELECTRICS
MINI-BEAM® Expert™ Specifications
Green (RUN Mode):
ON when power is applied Flashes when received light level approaches the switching threshold Red (TEACH Mode): OFF when no signal is received. Pulses to indicate signal strength (received light level). Rate is proportional to signal strength (the stronger the signal, the faster the pulse rate). This is a function of Banner’s Alignment Indicating Device (AID). Yellow (TEACH Mode): ON to indicate sensor is ready to learn output ON condition OFF to indicate sensor is ready to learn output OFF condition Yellow (RUN Mode): ON when outputs are conducting Construction
Reinforced thermoplastic polyester housing, totally encapsulated, o-ring seal, acrylic lenses, and stainless steel screws.
Environmental Rating
Meets NEMA standards 1, 2, 3, 3S, 4, 4X, 6, 12, and 13; IEC IP67
Connections
PVC-jacketed 5-conductor 2 m or 9 m unterminated cable, or 5-pin Euro-style quick-disconnect (QD) fitting are available. QD cables are ordered separately. See page 382.
Operating Conditions
Temperature: -20° to +70° C
Application Notes
The first condition presented during TEACH mode becomes the output ON condition.
Relative humidity: 90% at 50° C (non-condensing)
Certifications
Hookup Diagrams
DC11 (p. 478)
More information online at bannerengineering.com
83
Page 20
MINI-BEAM® Universal Voltage Series Compact Sensors PHOTOELECTRICS
MINI-BEAM® Universal Voltage Sensors
Opposed, Retroreflective, Diffuse and Convergent Models Suffix E, EL, R, RL, LV, LP, D, CV and CV2
Popular, compact MINI-BEAM package with a SPDT electromechanical (E/M) relay
30.7 mm 12.2 mm
Universal supply voltage: 24 to 240V ac, 50/60 Hz; 24 to 240V dc
30.7 mm
Easy-tooperate sensors with few required adjustments
12.2 mm
81.0 mm 12.2 mm
66.8 mm
12.2 mm 30.7 mm
Diffuse Models Suffix W
30.7 mm
Detailed Dimensions 85.3 mm 69.8 mm
Plastic Fiber Models Suffix FP
Glass Fiber Models Suffix F and FV
MINI-BEAM® Universal Voltage, 24-240V ac or dc Models
Sensing Mode/LED*
SMU31E Emitter SMU31R SMU31EL Emitter SMU31RL
OPPOSED
SMU315LV
Excess Gain
Beam Pattern
2m
EGCO-12 (p. 428)
BPO-12 (p. 450)
30 m
2m
EGCO-13 (p. 428)
BPO-13 (p. 450)
5 m†
2m
EGCR-16 (p. 431)
BPR-15 (p. 453)
10 mm - 3 m†
2m
EGCR-17 (p. 432)
BPR-16 (p. 453)
Range
Cable**
3m
Output Type
Download PDF
Data Sheet
RETRO
SMU315LP
P POLAR RETRO
SMU315D
SPDT E/M Relay
380 mm
2m
EGCD-19 (p. 435)
BPD-18 (p. 457)
130 mm
2m
EGCD-20 (p. 435)
BPD-19 (p. 457)
16 mm
2m
EGCC-26 (p. 438)
BPC-26 (p. 460)
43 mm
2m
EGCC-27 (p. 438)
BPC-27 (p. 460)
55230
DIFFUSE DIVERGENT
SMU315W DIFFUSE
SMU315CV SMU315CV2
CONVERGENT
Infrared LED Visible Red LED * ** For 9 m cable, add suffix W/30 to the 2 m model number (example, SMU315D W/30). † Retroreflective range is specified using one model BRT-3 retroreflector. Actual sensing range may differ, depending on the efficiency and reflective area of the retroreflector used. See Accessories for more information.
84
More information online at bannerengineering.com
Page 21
MINI-BEAM® Universal Voltage Series Compact Sensors
Models
Sensing Mode/LED*
SMU315F GLASS FIBER
SMU315FV
Range
Cable** 2m
Range varies by sensing mode and fiber optics used
2m
GLASS FIBER
SMU315FP PLASTIC FIBER
Output Type
Range varies by sensing mode and fiber optics used
SPDT E/M Relay
2m
PHOTOELECTRICS
MINI-BEAM® Universal Voltage, 24-240V ac or dc (cont’d)
Download PDF
Excess Gain
Beam Pattern
EGCG-16 (p. 444) & EGCG-17 (p. 445)
BPG-16 (p. 462) & BPG-17 (p. 463)
EGCG-18 & EGCG-19 (p. 445)
BPG-18 & BPG-19 (p. 463)
EGCP-12 & EGCP-13 (p. 447)
BPP-12 & BPP-13 (p. 465)
Data Sheet
55230
Infrared LED Visible Red LED * ** For 9 m cable, add suffix W/30 to the 2 m model number (example, SMU315F W/30).
MINI-BEAM® Universal Voltage Specifications Supply Voltage
Universal voltage: 24 to 240V ac, 50/60Hz or 24 to 240V dc (1.5 watts or 2.5 VA max.)
Supply Protection Circuitry
Protected against transient voltages. DC hookup is without regard to polarity.
Output Configuration
SPDT (Single-Pole, Double Throw) (form C) electromechanical relay, ON/OFF output.
Output Rating
Max. switching power (resistive load): 90W, 250VA Max. switching voltage (resistive load): 250V ac or 30V dc Max. switching current (resistive load): 3A Min. voltage and current: 5V dc, 10 mA Mechanical life: 20,000,000 operations Electrical life at full resistive load: 100,000 operations
Output Protection Circuitry
Protected against false pulse on power-up.
Output Response Time
Closure time: 20 milliseconds max. Release time: 20 milliseconds max. Max. switching speed: 25 operations per second
Repeatability
All sensing modes: 1 millisecond
Adjustments
Light/Dark Operate select switch, and 15-turn slotted brass screw Gain (sensitivity) adjustment potentiometer (clutched at both ends of travel). Both controls are located on rear panel of sensor and are protected by a gasketed, clear acrylic cover.
Indicators
Alignment Indicator Device system (AID) lights a rear-panel-mounted LED indicator whenever the sensor sees a “light” condition, with a superimposed pulse rate proportional to the light signal strength (the stronger the signal, the faster the pulse rate).
Construction
Reinforced thermoplastic polyester housing, totally encapsulated, o-ring seal, acrylic lenses, and stainless steel screws.
Environmental Rating
Meets NEMA standards 1, 2, 3, 3S, 4, 4X, 6, 12, and 13; IEC IP67.
Connections
PVC-jacketed 5-conductor 2 m or 9 m unterminated cable. Opposed mode emitter cables are 2-conductor.
Operating Conditions
Temperature: -20° to +55° C
Application Notes
Install transient suppressor (MOV) across contacts switching inductive loads.
Relative humidity: 90% at 50° C (non-condensing)
Certifications
Hookup Diagrams
Emitters: UN02 (p. 487)
Other AC/DC Models: UN01 (p. 487)
More information online at bannerengineering.com
85
Page 22
MINI-BEAM® NAMUR Series Compact Sensors
12.2 mm
PHOTOELECTRICS
MINI-BEAM® NAMUR Sensors 30.7 mm
Intrinsically safe sensors with MINI-BEAM performance and small size 30.7 mm
For use with approved switching amplifiers with intrinsically safe input circuits
51.8 mm
Diffuse Models Suffix W
Output 1 mA or less in the dark and 2 mA or more in the light
12.2 mm
Models with integral cable or quick-disconnect
66.0 mm
12.2 mm
30.7 mm
Opposed, Retroreflective, Diffuse and Convergent Models Suffix E, R, LV, D, and CV 69.9 mm
Detailed Dimensions
Glass Fiber Models Suffix F
MINI-BEAM® NAMUR, 5-15V dc Models
Sensing Mode/LED*
Range
Download PDF
Cable** 2m 4-Pin Euro QD
MI9E Emitter MI9EQ Emitter
Output Type
MIAD9LV MIAD9LVQ MIAD9LVAG MIAD9LVAGQ MIAD9D MIAD9DQ
2m 4-Pin Euro QD
OPPOSED
EGCR-18 (p. 432)
BPR-17 (p. 454)
50 mm - 2 m
2m 4-Pin Euro QD
EGCR-19 (p. 432)
BPR-18 (p. 454)
380 mm
2m 4-Pin Euro QD
EGCD-21 (p. 435)
BPD-20 (p. 457)
EGCD-22 (p. 435)
BPD-21 (p. 457)
DIFFUSE
DIVERGENT
75 mm
MIAD9WQ
2m 4-Pin Euro QD
DIFFUSE
Constant Current ≤1.2 mA dark ≥2.1 mA light
16 mm
2m 4-Pin Euro QD
EGCC-28 (p. 438)
BPC-28 (p. 460)
CONVERGENT
43 mm
2m 4-Pin Euro QD
EGCC-29 (p. 438)
BPC-29 (p. 460)
2m 4-Pin Euro QD
EGCG-20 & EGCG-21 (p. 445)
BPG-20 & BPG-21 (p. 463)
GLASS FIBER
Range varies by sensing mode and fiber optics used
MIAD9CV MIAD9CVQ MIAD9CV2 MIAD9CV2Q
BPO-14 (p. 450)
2m 4-Pin Euro QD
POLAR RETRO
MIAD9W
EGCO-14 (p. 428)
5m RETRO
P
Beam Pattern
MIAD9F MIAD9FQ
Data Sheet, 6m MIAD9R MIAD9RQ
Excess Gain
39616
Infrared LED Visible Red LED * ** For 9 m cable, add suffix W/30 to the 2 m model number (example, MIAD9LV W/30). A model with a QD requires a special 4-pin Euro QD mating cable (see page 381). † Retroreflective range is specified using one model BRT-3 retroreflector. Actual sensing range may differ, depending on the efficiency and reflective area of the retroreflector used. See Accessories for more information.
86
More information online at bannerengineering.com
Page 23
MINI-BEAM® NAMUR Series Compact Sensors
Supply Voltage
5 to 15V dc (provided by the amplifier to which the sensor is connected)
Output
Constant current output: ≤ 1.2 mA in the “dark” condition and ≤ 2.1 mA in the “light” condition
Output Response Time
Opposed mode receiver: 2 milliseconds on/400 microseconds off All other models: 5 milliseconds on/off (does not include amplifier response)
Adjustments
15-turn slotted brass screw GAIN (sensitivity) adjustment potentiometer (clutched at both ends of travel); located on rear panel and protected by a clear gasketed acrylic cover
Indicators
Red LED Alignment Indicator Device (AID) located on rear panel lights when the sensor sees a “light” condition; pulse rate is proportional to signal strength (the stronger the signal, the faster the pulse rate).
Construction
Reinforced thermoplastic polyester housing, totally encapsulated, o-ring sealing, acrylic lenses, and stainless steel screws
Environmental Rating
Meets NEMA standards 1, 2, 3, 3S, 4, 4X, 6, 12 and 13; IEC IP67
Connections
PVC-jacketed 2-conductor 2 m or 9 m cables, or special 4-pin Euro-style quick-disconnect (QD) fitting are available; QD cables are ordered separately. See page 381.
Operating Conditions
Temperature: -40° to +70° C
Design Standards
MIAD9 Series sensors comply with the following standards: DIN 19 234, EN 50 014 Part 1. 1977, EN50 020 Part 7. 1977, Factory Mutual #3610 and 3611, CSA 22.2 #157-92 and 22.2 #213-M1987
PHOTOELECTRICS
MINI-BEAM® NAMUR Specifications
Relative humidity: 90% at 50° C (non-condensing)
Certifications LISTE D
Hookup Diagrams
SP02 (p. 489)
APPROVALS CSA:
#LR 41887
Instrinsically Safe, with Entity for Class I, Groups A-D Class I, Div. 2, Groups A-D
FM:
#J.I. 5Y3A4.AX
Intrinsically Safe, with Entity for Class I, II, III, Div. 1, Groups A-G Class I, II, III, Div. 2, Groups A-D and G
KEMA:
#03ATEX1441X
II IG EEx ia IIC T6
ETL:
#553868
More information online at bannerengineering.com
87
Page 24
Q23 Series Compact Sensors PHOTOELECTRICS
Q23 and QH23 Vertical and Horizontal Rectangular Sensors • Available with vertical and horizontal housings • Delivers high power in a small package • Features ranges up to 8 m • Uses a powerful visible red sensing beam for easy setup and alignment • Offered in opposed, polarized retroreflective, convergent, diffuse and plastic fiber optic modes • Features marginal gain indicator with alarm output
OPPOSED
P POLAR RETRO
DIFFUSE
CONVERGENT
23.0 mm
Q23 and QH23 Sensors PLASTIC FIBER
BRACKETS
PAGE 350 QD CABLES
4-Pin Pico
Dual-LED multi-function indicators
Detailed Dimensions
34.0 mm
Two housing styles
34.0 mm
2 m or 9 m integral cable, or 150 mm Pico-style quickdisconnect pigtail
23.0 mm
PAGE 378 REFLECTORS
12.0 mm
PAGE 391
PAGE 406
12.0 mm
12.0 mm
APERTURES
Opposed, Retroreflective and Diffuse Models Suffix E, R, LP and D
34.0 mm
12.0 mm
23.0 mm 25.5 mm
12.0 mm 12.0 mm
Q23 Convergent Models Suffix CV
36.5 mm
34.0 mm 23.0 mm
88
27.1 mm
38.1 mm
Q23 Plastic Fiber Optic Models Suffix FP and FPY
QH23 Plastic Fiber Optic Models Suffix FP and FPY
More information online at bannerengineering.com
QH23 Convergent Models Suffix CV
Page 25
Q23 Series Compact Sensors
Models
Sensing Mode/LED*
Range
Q236E Emitter QH236E Emitter
PHOTOELECTRICS
Q23 and QH23, 10-30V dc
Download PDF
Cable**
Output Type
Excess Gain
Pattern
Beam
Data Sheet
EGCO-15 (p. 428)
BPO-15 (p. 450)
46637
EGCR-20 (p. 432)
BPR-19 (p. 454)
46637
EGCD-23 (p. 435)
BPD-22 (p. 457)
2m
– Q236EQ Emitter QH236EQ Emitter
4-pin Pico Pigtail QD
Q23SN6R QH23SN6R
2m
NPN
8m Q23SN6RQ QH23SN6RQ
4-pin Pico Pigtail QD
OPPOSED
Q23SP6R QH23SP6R
2m
Q23SP6RQ QH23SP6RQ
4-pin Pico Pigtail QD
Q23SN6LP QH23SN6LP
2m
Q23SN6LPQ QH23SN6LPQ
4-pin Pico Pigtail QD
PNP
NPN
Q23SP6LP QH23SP6LP
P
100 mm - 2 m† 2m
POLAR RETRO
PNP Q23SP6LPQ QH23SP6LPQ
4-pin Pico Pigtail QD
Q23SN6D QH23SN6D
2m
Q23SN6DQ QH23SN6DQ
NPN
SHORT-RANGE
4-pin Pico Pigtail QD 200 mm
Q23SP6D QH23SP6D
2m
DIFFUSE
PNP Q23SP6DQ QH23SP6DQ
4-pin Pico Pigtail QD 46637
Q23SN6DL QH23SN6DL Q23SN6DLQ QH23SN6DLQ
2m
NPN
LONG-RANGE
4-pin Pico Pigtail QD EGCD-24 (p. 435)
800 mm Q23SP6DL QH23SP6DL
DIFFUSE
BPD-23 (p. 457)
2m
PNP Q23SP6DLQ QH23SP6DLQ
4-pin Pico Pigtail QD
Visible Red LED * ** For 9 m cable, add suffix W/30 to the 2 m model number (example, Q23SN6D W/30). A model with a pigtail QD requires a mating cable (see page 378). † Retroreflective range is specified using one model BRT-3 retroreflector. Actual sensing range may differ, depending on the efficiency and reflective area of the retroreflector used. See Accessories for more information.
More information online at bannerengineering.com
89
Page 26
Q23 Series Compact Sensors PHOTOELECTRICS
Q23 and QH23, 10-30V dc (cont’d) Models
Sensing Mode/LED*
Range
Q23SN6CV50 QH23SN6CV50
Cable**
Download PDF
Output Type
Excess Gain
Pattern
Beam
EGCC-30 (p. 438)
BPC-30 (p. 460)
EGCP-14 & EGCP-15 (p. 447)
BPP-14 & BP-15 (p. 465)
Data Sheet
2m
NPN Q23SN6CV50Q QH23SN6CV50Q
4-pin Pico Pigtail QD 50 mm
Q23SP6CV50 QH23SP6CV50
46637
2m
CONVERGENT
PNP Q23SP6CV50Q QH23SP6CV50Q
4-pin Pico Pigtail QD
Q23SN6FP QH23SN6FP Q23SN6FPQ QH23SN6FPQ Q23SP6FP QH23SP6FP
2m
NPN
Standard Speed: 1 ms
4-pin Pico Pigtail QD
2m
PLASTIC FIBER
PNP Q23SP6FPQ QH23SP6FPQ
Range varies by sensing mode and fiber optics used
Q23SN6FPY QH23SN6FPY Q23SN6FPYQ QH23SN6FPYQ Q23SP6FPY QH23SP6FPY
46637 2m
NPN
High Speed: 100 µs
4-pin Pico Pigtail QD
PLASTIC FIBER
Q23SP6FPYQ QH23SP6FPYQ * **
4-pin Pico Pigtail QD
EGCP-16 (p. 447) & EGCP-17 (p. 448)
2m
BPP-16 (p. 465) & BPP-17 (p. 466)
PNP 4-pin Pico Pigtail QD
Visible Red LED For 9 m cable, add suffix W/30 to the 2 m model number (example, Q23SN6CV50 W/30). A model with a pigtail QD requires a mating cable (see page 378).
Q23 and QH23 Specifications
90
Supply Voltage and Current
10 to 30V dc (10% max. ripple) at less than 25 mA for diffuse, Retroreflective, and fiber optic models (exclusive of load) Opposed emitters and receivers draw 20 mA each
Supply Protection Circuitry
Protected against reverse polarity and transient voltages
Output Configuration
Solid-state complementary (SPDT) dc switch; NPN (current sinking) or PNP (current sourcing), depending on model. The Dark Operate (DO) output may be wired as a normally open marginal signal alarm output, depending upon hookup to the power supply.
Output Rating
150 mA max. each in standard hookup; when wired for alarm output, the total load may not exceed 150 mA Off-state leakage current: less than 1 mA at 30V dc Output saturation voltage: less than 1 volt at 10 mA dc; less than 1.5V at 150 mA dc
Output Protection Circuitry
Protected against false pulse on power-up, transient voltages, and continuous overload or short-circuit of outputs
Output Response Time
All other models: 1 millisecond ON/OFF Q23FPQ high-speed models: 100 microsecond ON/OFF; protected against false pulse on power-up NOTE: 100 millisecond delay on power-up: outputs do not conduct during this time.
More information online at bannerengineering.com
Page 27
Q23 Series Compact Sensors
Repeatability
Opposed: 0.13 milliseconds; Retroreflective and Diffuse: 0.25 milliseconds FPY High-Speed Plastic Fiber Optic: 25 microseconds Response time and repeatability specifications are independent of signal strength.
Adjustments
SENSITIVITY control (single-turn, o-ring sealed potentiometer)
Indicators
Sensors except opposed mode emitters have two LEDs: Green ON steady: dc power ON Green flashing: output overload Yellow ON steady: Light Operate (LO), output is energized Yellow flashing: marginal excess gain (1 - 1.5x), LO output is energized Emitters have green power “ON” indicator
Construction
Yellow and black ABS housing, with acrylic lenses, completely sealed. Stainless steel mounting bracket and M3 mounting hardware are supplied
Environmental Rating
Meets NEMA standards 1, 2, 3, 3S, 4, 4X, 6, 12, and 13; IEC IP67. Housing materials rated UL 94 V-0
Connections
PVC-jacketed 4-conductor 2 m or 9 m cables, or 4-pin Pico-style 50 mm threaded quick-disconnect (QD) fitting are available. Mating QD cables are ordered separately. See page 378.
Operating Conditions
Temperature: -20° to +55° C
Application Notes
To avoid damage to the sensor caused by static discharge (ESD), use the plastic screwdriver supplied with each sensor (included in the hardware packet) to adjust the SENSITIVITY control. Otherwise, use a screwdriver with an insulated handle.
PHOTOELECTRICS
(cont’d) Q23 Q23 and and QH23 Specifications (cont’d) QH23 Specifications
Relative humidity: 90% at 50° C (non-condensing)
Certifications
Hookup Diagrams
Emitters: DC03 (p. 476)
NPN Models: DC07 (p. 477)
PNP Models: DC08 (p. 477)
More information online at bannerengineering.com
91