Page 162
Alarm handling
10 Alarm handling The chapter is not valid for E50 and E100. This section describes alarm management. The function is used to call the operator’s attention on events in the process that need immediate caution. This function is divided into alarm groups, alarm messages and an alarm list. The alarms can be divided into groups, for example to create an order of priorities. The alarm messages are definitions of the signals that will activate an alarm as well as the alarm message for each signal. The alarm list contains alarms caused in the run-time mode.
Alarm list 18.2.97 20:11:40 Conveyor 2 empty 18.2.97 20:35:09 Queue full 19.2.97 03:29:12 Low pressure
10.1 Alarm grouping Alarms in the terminal can be divided into different groups depending on the terminal type. Each group can be allocated a certain color (E700 and E710). Alarms can be sorted into groups in the alarm block. It is not necessary to define the alarm groups. Terminal
Number of alarm groups
E200
1
E300
4
E600
4
E700
16
E710
4-6 (depending on selected font size)
151
Page 163
Alarm handling
Defining alarm groups Alarm groups are defined under Alarm groups in the Functions menu. The attribute for alarms in this group are decided in the following dialog box.
Parameter
152
Description
Group name
Any name for the alarm group.
Summary notify
Active - Digital signal which is set to unity when there is an active alarm in the group. Unack - Digital signal which is set to unity when there is an unacknowledged alarm in the group.
Remote acknowledge
Digital signal which acknowledges all the alarms in the group simultaneously.
Colors
States the colors for active, acknowledged, inactive alarms as well as the normal state for the alarm in the alarm list. Only valid in E700 and E710.
Page 164
Alarm handling
10.2 Alarm messages Alarm messages are defined under Alarms in the Functions menu. The alarm message is entered here with a maximum of 38 characters, 18 characters in E200. More characters can be shown if a smaller font size is used in the alarm list. The message can contain dynamic data (just like a Textblock) which can be digital or analog. You can define 100-300 alarms depending on the application.
Parameter
Description
Alarm text
An alarm text containing static text, digital text and/or analog numeric.
Signal
The digital signal which when activated generates the alarm is stated here.
Alarm when signal is
Select On if a set signal should cause an alarm. Select Off if a reset signal should cause an alarm.
Acknowledge notify
Digital signal affected when the alarm is acknowledged. Normally the signal is set.
Reset
The above signal is set to zero when the alarm is acknowledged if Reset is marked.
Remote acknowledge
Digital signal which acknowledges the alarm when activated.
Alarm group
States the alarm group for the definition.
153
Page 165
Alarm handling Parameter
Description
Info block
State a block number of a text or graphic block. This makes it possible to give the operator a “help page” containing information about the alarm and possible actions. 0 means that no block are linked to the alarm. If the information block is a textblock it will be included if the alarm is sent as an email message. See the chapter Alarms in run-time mode.
Mail to address
When an alarm is activated an email can be sent to a predefined receiver. The alarmtext is then the subject. See the section “SMTP Client”.
Ack. required
States if the alarm should be acknowledged or not. A cross in the square means that the alarm must be acknowledged and no cross means that the alarm functions as an indicator alarm, that is as a form of information.
History
States when the alarm shall be taken out of the alarm list. A cross means that the alarm remains in the list until the alarm list is full. No cross means that the alarm is taken out of the list when it is acknowledged and is no longer active. If the Acknowledge parameter is not marked then the alarm is taken out of the list as soon as it is not active.
To printer
Whether the alarm message should be printed out directly if the alarm status changes is stated here.
10.3 Configuring the alarm list General settings for the alarm list are made in Alarm settings in the Setup menu. Alarms take different amounts of space in the alarm list depending on the length of the alarm text and the number of objects in the alarm message. S=19 * AO + NC S = The number of bytes. AO = The number of objects in the alarm message. NC = The number of characters in the alarm message.
154
Page 166
Alarm handling
Parameter
Description
Active signal
States the digital signal which the terminal set when there is an active alarm.
Unack signal
States the digital signal which the terminal set when there is an unacknowledged alarm.
List erase signal
States the digital signal which when set erases all not active alarms in the alarm list.
Reset
Means that the signal stated on List erase is set to zero when the alarm list is erased.
List size
States the list size in number of kbytes for E300, E600, E700 and E710 and in number of alarms in E200. Note that the real size of the alarm list is twice the stated size. The performance of the project is effected negatively if list sizes over 10 kbytes is used (100 alarms in E200).
Alarm symbol
States when the alarm symbol should be shown, see table below. ■ALARM■ is shown in the Textblock and a red bell, , in the top right-hand corner of the display is shown in the Graphicblock.
Backlight action
State when the background light shall be turned on at alarm. 0n means that the backlight is turned on when the alarm symbol is shown. Default setting. Off means that the backlight is not affected by alarms. Timer means that the backlight is on when a new alarm is activated and turns of when the time for the screen save is out.
Alarm cursor
In E700 and E710 the cursor color can be changed in the alarm list.
155
Page 167
Alarm handling
Alarm symbol shows when Option active unacknowledged
NO •
UNACK ACTIVE
•
ALL
•
•
10.4 Alarms in run-time mode Alarms are shown in the Textblock with the text ■ALARM■ in the upper right-hand corner of the display (you can select not to have this during configuration). A red bell blinks in the upper right-hand corner of the display for alarms in Graphic blocks. The alarm is presented in an alarm list with the predefined alarm texts. The alarm list contains the latest alarms which are listed according to alarm group according to definition and with the latest alarm at the top of the list. The alarm list’s size in number of kbytes is selected during configuration (number of alarms in E200). The alarm list is shown on jumping to the alarm block. The status for the alarm is shown for each alarm as well as the time when the larm was activated, deactivated or acknowledged depending on the selected display mode. Alarms can have the following status. Symbol
Status
*
Active, Not acknowledged
$
Not active, Not acknowledged
-
Active, Acknowledged
<blank>
Not active, Acknowledged
Alarms can be shown in the following format.
156
Display format
Description
S
The time when the alarm was activated
E
The time when the alarm was inactived
A
The time when the alarm was acknowledged
Page 168
Alarm handling To get to the alarm block you can either press [LIST] or define a jump to system block 990 or allow the controller system to produce a list via the Display signal for block 990. To acknowledge an alarm place the cursor on the line where the alarm is and press [ACK]. Alarms can be printed out directly as they occur or change status if a printer is connected. This should be stated when the alarm is defined. The alarm is printed out with date, time, status and the alarm text. Return to the previous block by pressing [LIST] on the terminal. The current content of the alarm list can be printed out by giving the Printer signal for block 990.
Block linked to alarms Text or graphic blocks can be linked to alarms. This means that when the operator press the INFO key at an alarm in the alarm list a block linked to the alarm is shown. This block can contain information about the alarm and reccomended actions. It is only possible to press the INFO key if current alarm is linked to a block. Return to the alarm list by pressing [PREV] on the terminal.
10.5 Graphic alarm page in run-time mode The page is graphic and can be modified by the user. The function keys can be linked to the functions in order to enlarge or reduce the text on the alarm page as well as the function for flipping through the pages. Furthermore there is the possibility to select the showing of date and time. Alarms can be sorted into groups and you can select which group is to be shown. Status is shown with different colors, the colord defined when setting the alarm group. In E300, E600 and E700 you select alarm group with the arrow keys left and right.
157
Page 169
Alarm handling E700 Alarm symbol
Alarm message
Current alarm line i
Alarm info
Increase the font size
Decrease the font size
Switch on/off the date and time stamp
Alarm groups
E710 Alarm symbol
Alarm message
Current alarm line
Leave the alarm list Page up Acknowledge Increase the font size i
Alarm info Switch on/off the date and time stamp Page down
Alarm groups