Page 196

Communication

17 Communication The chapter is not valid for E50.

17.1 Transparent mode The programming/printer port on the terminal is used in the transparent mode to connect a unit working in parallel with the PLC system. This unit can be another terminal or a personal computer with for example the programming tool for the controller system or a superior operating system. The transparent mode works together with the MELSEC CPU port and MELSEC A-series communication ports with C24 protocol. For further information see the respective C24 manual.

Connecting a personal computer or other computer system Personal computers with the MELSEC MEDOC programming tool or other computer system are connected directly to the terminal’s programming/printer port. MELSEC MEDOC Terminal

FX-system

RS-232 RS-422

Terminal with MELSEC MEDOC connected to the programming/printer port

185

Page 197

Communication

Settings in the terminal and MELSEC MEDOC The following settings must be made in the terminal and MELSEC MEDOC for the transparent mode to work.

The terminal The printer parameters are set in the Setup menu under the menu option Peripherals. The parameters should be 9600 baud, 7 data bits, 1 stop bit and even parity if the terminal is connected to an FX system. The parameters should be 9600 baud, 8 data bits, 1 stop bit and odd parity if the terminal is connected to a A-CPU or a QnA-CPU. The parameters should be 19,200 baud, 8 data bits, 1 stop bit and no parity if the terminal is connected to one of the A-series or QnA-series serial communication modules.

MELSEC MEDOC The transfer parameters should be changed to 19,200 baud, 8 data bits, 1 stop bit and no parity when transferring via the A-series communication ports. This is done under Transfer in Setup. The Interface should also be changed from CPU to C24 under Transfer. The transfer parameters should not be changed in MELSEC MEDOC for other projects. See the Installation manual for cable connections. The settings also apply for other PC-based monitoring systems such as SCADA and MELSEC MEDOC plus.

186

Page 198

Communication

Connecting two terminals in transparent mode Several terminals can be connected to the same PLC system with the function transparent mode. In this section we describe how to connect two terminals. Several terminals are connected in a analog way.

Cable connection When connecting two terminals to a PLC system the first terminal is connected according to the description in the Installation manual. Between the two terminals a cable according to the figures below is used. The cable is connected between the free port on the first terminal and the corresponding port on the second terminal. If the distance is more than 15 meters using RS-232 communication a signal amplifier must be used.

RS-422

9-pos D-sub Female

RS-232

9-pos D-sub Female

2

3

3

2

5 Cable between two terminals using RS-232

5

25-pos D-sub Male

25-pos D-sub Male

2 15

3 16

3 16 7 8

2 15 7 8

Cable between two terminals using RS-422

187

Page 199

Communication

Settings in the first terminal In MAC Programmer+ the communication settings is made in the Setup menu under Peripherals. Settings for the port connected to the PLC system is stated in the common way. Settings for the port connected to the other terminal can be freely chosen.

Settings in the second terminal In MAC Programmer+ the communication settings is made in the Setup menu under Peripherals. The PLC system should be placed on the port that is used to connect the second terminal to the first terminal. The settings for this port shall be the same as stated in the first terminal on the port where the second terminal is connected. If any of the PLC systems FX2N or QnA is used the command BSD must be stated on the command line under System Signals in the Setup menu.

Transfer speed The transfer speed can vary between 600 and 19,200 baud. The highest transfer speed between the terminals is recommended to obtain the best results. The speed of communication decreases with the number of terminals connected according to the following table.

188

Access time to the PLC

Number of terminals

Terminal 1

Terminal 2

Terminal 3

Terminal 4

1

100%

-

-

-

2

50%

50%

-

-

3

50%

25%

25%

-

4

50%

25%

12,5%

12,5%

Page 200

Communication

Connecting three terminals in transparent mode A third terminal can be connected to Terminal 2 in the network using a cable according to the figures above. The settings in the third terminal should be analog to the settings in the second terminal. Terminal 2

Terminal 1

RS-422

RS-232

Terminal 3

RS-422

17.2 The terminal as communication interface (No protocol mode) The No protocol mode is used to connect different PLC systems or connect external units such as bar code readers or weighing scales to the PLC system. The PLC system controls what is to be sent to the communication port. Data coming in to the communication port is written to the PLC register. Communication takes place with the transfer of the PLC register area according to the control block below. Any unit

Terminal

Data register 0 1 . . 100

Communication handling

PLC program

Send buffer data

101 Recieve buffer data

Ctrl

Start send buffer Command for send Start receive buffer Command for receiving RX End code pattern RX Message length

189

Page 201

Communication

Rightclick on No Protocol Mode in Peripheral Configuration under Peripherals in the Setup menu.

Register

190

Beskrivning

Ctrl reg 0

Start register for the transmission data buffer. The first register in the buffer area contains the total number of bytes to be transmitted. The following registers contains the data to be transmitted. The maximum buffer size is 127 registers = 254 bytes.

Ctrl reg 1

Command register for transmission. Set to 1 by the PLC system when transmission is required. Set to 0 by the terminal when transmission is complete.

Ctrl reg 2

Start register for the reception data buffer. The first register in the buffer area contains the total number of bytes received. The following register contains the data received. The maximum buffer size is 127 registers = 254bytes.

Page 202

Communication Register

Beskrivning

Ctrl reg 3

Command register for reception. - Set to 0 by the PLC system when it is ready to receive. - Set to 1 by the terminal when the message is available. - Set to -1 (FFFF) on error message (e.g. too short). - Set to 2 by the PLC system when clearing of the port buffer is required. - Set to 3 by the terminal when clearing of the port buffer has been carried out. The port buffer is automatically cleared on start up and when switching between transparent mode and no protocol mode, i.e. the register receives the value 3.

Ctrl reg 4

End code (1 or 2 bytes) on the message received.

Ctrl reg 5

Length of the message received. End code is used if 0.

In the Setup menu, Peripherals you drag the icon No Protocol mode to the communication port you will use. Right click to define which register will be the first control register in the transfer area. This and the five following registers are used as control registers. The PLC system can switch between no protocol and transparent/printer modes in the run-time mode using a digital signal. State the digital signal in the dialog under No protocol on signal.

Ctrl reg 0 Ctrl reg 1 Ctrl reg 2 Ctrl reg 3

Register t0 Register t1 Register t2

Send data buffer Number of bytes Data

Control block Register t0 Register r0

Reception data buffer Register r0

Number of bytes

Register r1 Register r2

Data

191

Page 203

Communication

Example of using the No Protocol mode The following example describes the use of the No Protocol mode for a weighing system. The diagram below shows a three-step block schedule for communication.

0 M100

Wait state

Transmission start

1

Queries current weight Transmission completed

M11

2

Await current weight

Receiving complete

The terminal functions as the master towards the weighing system, that is it continually asks the weighing system for the current weight. The diagram below shows the connections between the PLC system, terminal and weighing system.

192