Page 212
Network communication
18 Network communication The chapter is not valid for E50. This chapter describes how the operator terminals in the E series communicate in a network. The network communication takes place via TCP/IP (Transport Control Protocol/Internet Protocol). TCP/IP is a standardized set of protocols developed to allow cooperating computers to share resources across a network. The operator terminals can be connected in a network in many different ways. The connection can either be Ethernet or serial. If Ethernet is used the expansion cards IFC ETTP or IFC ETCX are required in all terminals. IFC ETTP is used to connect the terminals with twisted pair and IFC ETCX is used to connect the terminals with coaxial cable. If twisted pair is used an Ethernet HUB is required. For further information about TCP/IP please refer to the RFC’s published on Internet. You will find them for example on this address: ftp://ftp.sunet.se/pub/internet-documents/rfc. Information and description of concept and words used can be found on the webb address http://www.whatis.com. The terminal network is a Client/Server network and works as follows. Only Clients can access data on the network. Servers only provide access for other Clients. A terminal can be both a Client and a Server to be able to provide access and also access other terminals. Up to 20 different Clients can access data from the same Server. A Client can access data from up to 16 different Servers. Each terminal requires an IP address. Addresses from 192.168.0.0 to 192.168.254.254 are recommended for internal networks. With the terminal you can use standardized Internet tools such as browser, mail server and FTP client. You can create a webb site in a PC and load it to the terminal. The Webb page can contain real time data from the PLC system or the terminal. Via Internet and a browser you can change values, set signals, acknowledge alarms etc via script. The terminal can also send email at special events e.g. alarm and status report.
201
Page 213
Network communication
18.1 Examples of possible networks Example 1 This Ethernet network is designed for one controller together with several terminals. Terminal 1 192.168.1.1 Server
Terminal 2 192.168.1.2 Client
Terminal 3 192.168.1.3 Client
PC 192.168.1.x
Control system
Terminal 1 (192.168.1.1)
Terminal 1 must be a Server. Clients can access the controller through the Server.
202
Page 214
Network communication Terminal 2 (192.168.1.2)
Terminal 2 must be a Client. A Client can access the controller connected to a Server.
203
Page 215
Network communication Terminal 3 (192.168.1.3)
Terminal 3 must be a Client. A Client can access the controller connected to a Server.
A PC can be connected for transferring projects to the terminals. The PC can be connected either via an Ethernet card or to one of the serial ports on one of the terminals using CAB5 or CAB6. The Ethernet card is recommended.
204
Page 216
Network communication
Example 2 This Ethernet network is designed for several controllers and operator terminals in one network. The controllers in this example use different protocol drivers. The following Client/Server and Driver configuration gives following access. This example uses two drivers, driver X and driver Y. Terminal 1 192.168.1.1 Client/Server Driver X
Terminal 2 192.168.1.2 Server Driver Y
Terminal 3 192.168.1.3 Client Driver X
Control system 1
Control system 2
Control system 3
Terminal 4 192.168.1.4 Client Driver Y
Terminal 1 (192.168.1.1)
Terminal 1 is a Client with driver X and can access all the Servers with the same driver. It can also access its local controller 1. In this example terminal 1 only has access to controller 1. It can’t access controller 2 because of different drivers and not controller 3 because the terminal 3 is not a Server. Terminal 2 (192.168.1.2)
Terminal 2 is not a Client and can’t access any other stations in the network. It can only access its local controller 2. Terminal 3 (192.168.1.3)
Terminal 3 is a Client with driver X and can access all Servers with the same driver. It can also access its local controller 3. In this example terminal 3 only has access to controller 1 and 3. Terminal 3 can’t access controller 2 because of different drivers.
205
Page 217
Network communication Terminal 4 (192.168.1.4)
Terminal 4 is a Client with driver Y and can access all Servers with the same driver. In this example terminal 4 only has access to controller 4 only. Terminal 4 can’t access controller 1 because of different drivers and not 3 because it is not a Server. Data between the controllers can be exchanged with a small controller program or using function keys. See BDTP Client and BDTP Server.
Example 3 This Ethernet network is a normal configuration where a PC is included. This allows the computer to access any terminal in the network and transfer a project. The PC can be connected either via an Ethernet card or to one of the serial ports on one of the terminals using CAB5 or CAB6. The Ethernet card is recommended. The example assume that the same driver is used. To change PLC system we refer to the sections BDTP Client and BDTP Server. Terminal 1 192.168.1.1 Server/Klient
Terminal 2 192.168.1.2 Server/Klient
Terminal 3 192.168.1.3 Klient
Styrsystem 1
Styrsystem 2
Styrsystem 3
Terminal 4 192.168.1.4 Klient
Persondator 192.168.1.X
Terminal 1 (192.168.1.1)
Terminal 1 is a Client and can access all the Servers. It can also access its local controller 1. This means that it has access to controller 1 and 2.
206
Page 218
Network communication Terminal 2 (192.168.1.2)
Terminal 2 is a Client and can access all the Servers. It can also access its local controller 2. This means that it has access to controller 1 and 2. Terminal 3 (192.168.1.3)
Terminal 3 is a Client and can access all the Servers. It can also access its local controller 3. This means that it has access to controller 1 and 2. Terminal 4 (192.168.1.4)
Terminal 4 is a Client and can access all the Servers. This means that it has access to controller 1 and 2. Data between the controllers can be exchanged with control registers. See BDTP Client and BDTP Server. Note! When a project is transferred to a terminal this station will stop communication momentaniously. If the terminal is a Server all the clients requesting data from this Server will receive an error message.
207
Page 219
Network communication
Example 4 When only two stations are to be used a connection can be established with serial communication. This setup uses the built-in serial port to connect to the second terminal. No Ethernet card is required. One or two controller can be used with this "network". Both the controller systems in the network uses the same driver and both the terminals have access to both the controller system 1 and 2. Terminal 1 192.168.1.1 Server/Klient
Terminal 2 192.168.1.2 Server/Klient
RS-232/RS-422
Styrsystem 1
208
Styrsystem 2
Page 220
Network communication Terminal 1 (192.168.1.1)
Terminal 1 is a Client and can access the other Server. It can also access its local controller 1. This means that it has access to controller 1 and controller 2.
209