For the Beijer Electronics AB E200

Page 22

Terminal functions

3

Terminal functions

This chapter describes the different modes in the terminal, the keyboard and the information page in the terminal. Description of the different key sequences can be found in the section “Key sequences”

3.1 The operation modes, RUN, PROG and SETUP The E-terminal has three operating modes. E50 has only Run-time mode and transfer mode. – SETUP mode, where the basic settings are made such as choice of PLC system, menu language and printer settings. – Programming mode, where the terminal can be programmed and changes can be easily made at system set-up. – Run-time mode, when the terminal is running with PLC.

Switching between modes Switch between PROG and RUN Switch between programming, PROG, and run-time, RUN, by simultaneously pressing the [←] and [MAIN]. The possibility to switch between PROG and RUN from the terminal can be controlled via a password. For more information we refer to the chapter Programming using MAC Programmer+.

Switch between PROG and SETUP To switch from PROG to SETUP you press [LEAVE] until the start-up menu is displayed, then press any key. Press [LEAVE] to return to PROG.

11

Page 23

Terminal functions

Switch between RUN and SETUP Press [←] and [MAIN] simultaneously to enter programming mode, PROG. Then press any key when the start-up menu is displayed to enter the SETUP mode. To switch from SETUP mode to RUN you press [←] and [MAIN]. The following key sequences are equivalent to the key sequence [←] + [MAIN]: E100 E710

[←] + [ENTER] [F1] + [F2] + [F4]

The SETUP mode In this section we describe functions that cannot be made via MAC Programmer+. For settings via MAC Programmer+ we refer to the chapter Programming using the MAC Programmer+.

Erasing the memory In the SETUP menu in the terminal you will find the function Erase memory. The function erase the terminal’s application memory. All blocks and definitions of alarms, time channels, function keys and system signals are erased. Parameter

Description

Enter

The memory is erased. The configuration menu is shown automatically when the erasure is completed.

Prev

Return to the previous level without erasing the memory.

Note! All data stored in the terminal is lost when the memory is erased. The language parameter are not affected by this function. Other parameters are erased or allocated the default setting values.

12

Page 24

Terminal functions

Memcard maintenance Not valid for E50, E100 and E200. Under Memcard maintenance you select to format a installed PCMCIA memory card or to transfer to and from the memory card. You can format the memory card as a backup card or as an expansion card. Under MemCard transfer you select to transfer: project to memcard, project from memcard, delete memcard project, recipe to memcard, recipe from memcard and delete memcard recipes. For more information see the manual for IFC MC.

Contrast setting Not valid for E50, E100 and E200. The contrast settings can be made in setup mode in the menu Setup, Contrast settings or in run-time mode via a jump to the system block 997. Pressing the function key marked + makes the display brighter and pressing the function key marked - makes the display darker. Return to previous level by pressing EXIT.

The Prog mode The programming mode is the mode where the application can be modified. It is here you can change text- and graphic blocks, modify the time channels, alarms, recipes and function keys. We recommend that the terminal is programmed using the software MAC Programmer+. Note! Block 0 must be defined in the project in order to be able to run the application.

13

Page 25

Terminal functions

Edit Editing graphic objects

The arrow keys are used when editing a graphic object to change the size of or move the object in 8-pixel steps. Changing/moving pixelwise is done by pressing [SNAP OFF] in the help line. To move stepwise through all the objects in the editing mode press the [SELECT] key followed by [NEXTOBJ] in the help line. The object marked is inverted and the object type is shown in a square. When an object is marked press [EDITOBJ] to edit the object’s parameters, [DELOBJ] to erase the object and [LEAVE] to return. Point to an object and press [MOVE] or [SIZE] and make the changes with the arrow keys to move or change the size of the object. Editing text objects

Mark an object by moving the cursor to the object with the arrow keys and press [Next] in the help line. You can scroll the text with the arrow keys if the Text-block holds more information than can be shown on the display. Press [LEAVE] in the help line to exit from a menu. Help line

There is a help line in the terminal which contains functions linked to the function keys located directly under the line. The functions of the keys changes depending on which level is active. The help lines are only shown in the programming mode. Function

14

Description

NEXT

Used to go to the next level. Settings made are saved.

LEAVE

Return to the previous level.

TOGGLE

Switch alternately.

LIST

Show option list.

INSERT

Insert.

DELETE

Delete.

HELP OFF

Switch between showing and removing help line.

SELECT

Mark an object.

SNAP OFF/ON

SNAP ON means moving and size change in 8-pixel steps. OFF = 1-pixel steps.

NEWOBJ

Create a new object.

PREVOBJ

Show previous object.

NEXTOBJ

Show the next object.

Page 26

Terminal functions Function

Description

EDITOBJ

Edit an object.

DELOBJ

Delete an object.

MOVE

Move an object.

SIZE

Change the size of an object.

ENLARGE

Increase the character size in an object.

REDUCE

Decrease the character size in an object.

Transfer Here you manually put the terminal in transfer mode. When the terminal is in transfer mode it is possible to transfer project between the terminal and the MAC Programmer+. Using the function Automatic terminal RUN/TRANSFER switching in MAC Programmer+ the software automatically put the terminal in transfer mode. To put E50 in manual transfer mode you press the keys [F3] and [F4] simultanusly as the voltage feed is connected.

Run Run-time mode is where the application is running. When switching to run-time mode, block 0 is automatically displayed. In the terminal the built in keyboard is used to select and change values in run-time mode. An error message is shown on the display if a communication error should occur between the terminal and the PLC system, See appendix. The terminal starts automatically when communication restarts. Key sequences affecting I/O that have been pressed during a communication error are stored in the terminal buffer and will be send to the PLC system when the communication is running again. To get a watch-dog function, where the PLC system can detect if a communication error has occurred, the terminal clock continuously can be transferred to a register in the PLC system (see the section Date/Time format in the chapter Programming via MAC Programmer+). The PLC system checks if the register is updated and if not, an alarm indicating communication error can be set in the PLC system. How the different objects/functions works in run-time mode are described in respective section of this manual.

15

Page 27

Terminal functions

3.2 The terminal’s keyboard

Built in function keys

Arrow keys

Alpha/Numerical keys

Alpha/numerical keys From the alpha/numerical keyboard the following characters can be entered in dynamic text and numerical objects during run-time in the terminal. 0-9 A-Z a-z !?<>()+/*=°%#:’ National characters Note! No characters can be entered from the keyboard on E50 because it don’t have any numerical keys.

16

Page 28

Terminal functions Numeric values are entered by pressing the respective key once. A to Z are entered by pressing the respective key 2 to 5 times and the lower case (small) letters a to z are entered by pressing the respective key 6 to 9 times. The time interval between the pressing can be set (see the section Key delay time in the chapter Programming via MAC Programmer+). If the key is not pressed within the time interval the cursor is moved to the next position. Pressing the key C1-C4 two to nine times different national characters are entered. This make frequently used characters that are not standard on the alpha/numerical keyboard available in the terminal (see the section Country settings in the chapter Programming using the MAC Programmer+). Note! In MAC Programmer+ all characters in the used font table (see the section Country settings in the chapter Programming via MAC Programmer+) except reserved characters can be used as a static text. Write the wanted character by pressing the ALT key and at the same time write 0 (zero) on the numerical keyboard on the PC followed by the character code (see Font tables in the Appendix).

Numerical and alphanumerical keys in E100 To be abel to enter figures and letters in E100 you keep the NUM key pressed when you press a figure. As an alternative you can enter the command NTGL on the command line under System signals in the Setup menu. The command NTGL gives the NUM key a toggle function. This means that when you press the NUM key you activate the function for numerical entering. Now you enter figures with the keys. Inactivate entering of numerical figures by pressing the NUM key. To be abel to enter letters in for example text objects in E100 you open the object for editing by pressing Enter. Then you first press the NUM key and then the Enter key at the same time as you press the arrow keys up and down. Move the cursor position with the arrow keys left and right. You enter the sign . by pressing the 0 key twice.

Reserved characters The ASCII characters 0-31 (Hex 0-1F) are reserved for internal functions in the terminal and may not be used.

17

Page 29

Terminal functions

Arrow keys The arrow keys are used to move the cursor within a block, menu or dialog.

Built-in function keys All keys are not available on all terminals. The [↵] ([ENTER]) key is used to confirm settings made and go on to the next line/level. The [PREV] key is used to return to the previous block. If the security level is changed the [PREV] key is disabled. The [LIST] key is used to bring up the alarm list. The [ACK] key is used to acknowledge an alarm in the alarm list. The [MAIN] key is used to jump to block 0 in Run-time mode. The [←] key is used to delete the character to the left of the cursor. Note! When the main block (block number 0) has been shown the [PREV] key doesn’t work because the block historical are deleted when the main block is shown.

Note! With the expansion card IFC 128E it is possible to put all the keys on an external keyboard. For more information we refer to the IFC 128E manual.

18

Page 30

Terminal functions

Key sequences There are some key sequences in the terminal with the following functions. Not valid for E100 and E710. Key sequence

Function

[←] [MAIN]

Switch between PROG and RUN.

[←] [F1]

Hold this combination pressed during start up to activate the mode for downloading of system programs, see the Down load the system program section.

[←] [PREV]

Calls up the information page in run-time mode, see the Information page section. Hold this combination pressed during start up to activate the self test function.

The key sequences in E100 and E710 differ from the rest of the terminals and are as folows. For complete description of the functions and procedure see the table above. Function

E100

E710 v2.xx

E710 v4.xx

Switch between PROG/ RUN/SETUP.

[←] [ENTER]

[F1] + [F2] + [F4]

Sysload

[←] [F1]

[F1] + [F2] + [F8]

[F1] + [F2] + [F8]

Calls up the information page, see the Information page section.

[←]

Touch key

Touch key

Ativate the self test function.

[F1] + [F2] + [F7]

[F1] + [F2] + [F7]

Calibrate touch

[F1] + [F2] + [F5]

[F1] + [F2] + [F5]

E50 has only Run-time mode and Transfer mode. The following key sequences are valid for E50. Key sequence [F3] [F4]

Function Put the terminal in manual transfer mode. Ativate the self test function.

19

Page 31

Terminal functions

3.3 Set the real time clock Not valid for E50. The real time clock in the terminal is set under SETUP, Date/Time. Select the alternative Set Terminal clock. The date and time is now displayed. Press [SET] to change the settings. Enter required date and time. In the editing mode you move the cursor with the arrow keys. Press [NEXT] to return or interrupt the editing before [ENTER] is pressed. The real time clock can also be set in run-time mode via a maneuverable clock object.

20

Page 32

Terminal functions

3.4 Information page Not valid for E50. The terminal contains an information page. The information page is activated by simultaneously pressing the [←] and [PREV] keys in run mode. On the touch terminal a touch key can be used/configured to call up the information page. Parameter

Description

STARTS

Number of times the terminal has been started.

RUN

Number of hours the terminal has been in operation.

CFL

Number of hours the backlighting has been switched on.

DYNAMIC MEMORY

Free RAM memory (working memory) in number of bytes.

FLASH MEMORY

Free Flash memory (project memory) in number of bytes.

FLASH ERASE CNT

Number of times each sector of the Flash memory has been erased. The current spareblock always shows zero.

FLASH CACHEHITS

Percentage of Block/Allocation cachehits in the file system.

FLASH ALLOCS

Max percentage of used/active allocations per block in the file system.

ALARMS

Number of alarms and alarm groups in the application.

TRENDS

Number of trend IO and trend objects in the application.

RECIPES

Number of production methods in the application.

DIGITAL IOs

Number of digital IOs monitored continuously (static) and number in the current block (monitor).

ANALOG IOs

Number of analog IOs monitored continuously (static) and number in the current block (monitor)

IO POLL

Time in ms between two readings of the same IO.

TIMEOUT

Number of time-outs in the communication.

CHKSUM

Number of check sum errors in the communication.

BYTEERR

Number of byte errors in the communication.

FRAME

Number of framing errors in each port.

OVERRUN

Number of overrun errors in each port.

PARITY

Number of parity errors in each port. 1=RS-422 port and 2=RS-232 port.

21

Page 33

Terminal functions

3.5 “Joystick” function Not valid for E50 and E710. With this function it is possible to use the arrow keys as function keys. On the command line under System signals you enter the command AK and an address. For example you can enter AKM100 (the command AK and memory cell M100).

Then M100 is the enable signal and the following 4 memory cells are according to the following control block. Memory cell

Description

Mn0

Enable. Arrow key detection. Disable=normal function.

Mn1

Left key

Mn2

Down key

Mn3

Up key

Mn4

Right key

If you press an arrow key when the enable signal is set the memory cell corresponding to the key pressed will be set. When the enable signal is set the normal functions of the arrow keys are diabled.

22

Page 34

Terminal functions

Example The following example can be used to exit the joystick function and return to normal function. Make the following steps. – create a block with 1:st man obj defined. – enter the static text “JOYSTICK”. – create a digital object with the following settings. D.Signal: M100 Text 0 : FRÅN Text 1 : TILL Manoeuvr: JA The textblock will look like this. JOYSTICK #––

23

Page 35

Terminal functions

24