Page 10

NMQ24-MFT US

®

W171

W170

Fast acting, proportional damper actuator, non-spring return, Multi-Function Technology®

Standard Wiring - VDC

Override to zero position

24 VAC Transformer

24 VAC Transformer

1 Line Volts

Blk (1) Common

1

Red (2) + Hot

Line Volts

3

Blk (1) Common Red (2) + Hot

3

500Ω Ω 1/4 watt

3

2

Control Signal (–) 2 to 10 VDC (+)

Control Signal (–) 4 to 20 mA (+)

Wht (3) Y1 Input, 2 to 10V

2 to 10 VDC Feedback signal

CCW

Wht (3) Y1 Input, 2 to 10V

A

4

Grn (5) U Output, 2 to 10V

2

A Open = 4 mA Position A Closed = Normal Operation

CW

NMQ24-MFT US

Standard Wiring - mA

Override to 100% position

24 VAC Transformer

24 VAC Transformer 1 Line Volts

Blk (1) Common Red (2) + Hot 500Ω

3

2

Ω 1/4 watt

Blk (1) Common Red (2) + Hot

3

(–) (+)

Control Signal 4 to 20 mA

3

4

500Ω

C

CW

1/4 watt

B Closed = 20 mA Position C Closed = Normal Operation

NMQ24-MFT US

2 Wht (3) Y1 Input, 2 to 10V

4

Grn (5) U Output, 2 to 10V CCW

B

Control Signal (–) 4 to 20 mA (+)

Wht (3) Y1 Input, 2 to 10V

2 to 10 VDC Feedback signal

Ω

With a 4-20 mA Input, up to 4 actuators may be wired in parallel. A 2% shift in the signal is seen when using a 500Ω resistor. Power consumption must be observed.

Override to open or closed position

2 to 10 VDC and 4 to 20 mA Control

Response sensitivity and reverse hysteresis, for VDC applications

G20492-Subject to change. © Belimo Aircontrols (USA), Inc.

Actuator responds to a 80 mV signal when not changing direction. Control Direction

Actuator responds to a 80 mV signal when reversing direction from stop position.

Satisfied Control Position

80 mV

Minimum Reversed Control Deadband Minimum Control Resolution

80 mV Satisfied Control Position Previous Control Direction

The reverse hysteresis away from mechanical end position is 140mV

All listed mV values are converted to “degrees of rotation” for all other control modes. Available configurations for the NMQ24-MFT US Control Position feedback

Running time

Torque

P-11001

2-10 VDC 2-10 VDC

5.0 sec

35 in-lbs

Notes

P-11002

0-10 VDC 0-10 VDC

5.0 sec

35 in-lbs

1

P-11003

2-10 VDC 2-10 VDC

6.0 sec

44 in-lbs

P-11004

2-10 VDC 2-10 VDC

7.0 sec

53 in-lbs

P-11005

2-10 VDC 2-10 VDC

8.0 sec

58 in-lbs

Configuration

Input range

Motion

Start point span adjustable control input is available. Please consult Belimo for the proper configuration code. PWM and Floating point control inputs are not available with this actuator.

Run times available up to 60 sec. @ 58 in-lbs

Provide overload protection and disconnect as required.

2

Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed.

3

Actuator may also be powered by 24 VDC.

4

ZG-R01 may be used.

147

NM

1 Line Volts

Page 11

SN1, SN2 Auxiliary Switches

®

For the direct coupled actuator NM 2…

Operation The SN1 and SN2 auxiliary switches are used to indicate when a desired position of a damper is reached or to interface additional controls for a specific control sequence. They are modular units that mount directly onto the NM type actuators and held in place with a prefitted screw. A driver disk is attached to the actuator clamp and offers direct transmission of the actuator position to the microswitch operating cams. The switching points can be set over the full scale of 0 to 10 simply by adjusting the slotted discs. NOTE: will not mount to NM actuators manufactured prior to May 1994 Voltage 120 250

Resistive 6.0 A 6.0 A

Inductive 5.0 A 2.5 A

Wiring Diagrams Technical Data

SN1

SN2

No. of switches

1xSPDT

2xSPDT

Switching capacity

6 A (2.5A) 250 VAC

S2

Switching point

S3

Electrical connection adjustable over full actuator rotation 0 to 10. Pre-setting with scale possible. 3 ft. 18 GA cable [1 m long 0.75mm2]

Humidity

5 to 95% RH non-condensing

Ambient temperature

-22° F to +122° F [-30° C to +50° C]

Storage temperature

-40° F to +176° F [-40° C to +80° C]

Housing type

NEMA type 2

S1

S1 N.C. NC

N.C.

● ● ●

S2

●

S3

●

NO N.O.

●

N.O.

SN1

S4 N.C. S5

●

S6

●

●

N.O. SN2

Housing material rating UL 94-V0 (flammability rating) 4 oz [125 g]

5.6 oz [175 g]

Mounting Instructions 1. Remove pointer assembly from the actuator. Press down the manual override button and rotate the actuator fully counter-clockwise. 2. Invert SN . switch and turn the driver disk fully clockwise as indicated. 3. Slide SN . switch onto actuator and check for the correct mating of the driver disk to the universal clamp. Secure with screw. 4. Adjust switch dials as necessary.

1 5. Remount the white plastic pointer only onto SN . switch.

2 148

3

4

5

G20492-IG-Subject to change. © Belimo Aircontrols (USA), Inc.

Weight

Page 12

Installation Instructions

®

Quick-Mount Visual Instructions for Mechanical Installation mi n. 1.5 ” [3 8m m]

T- bracket

L-bracket

1

NM

3/16"

3/16"

G20492-Subject to change. © Belimo Aircontrols (USA), Inc.

L-bracket

5° T- bracket

2

3 QUICK-MOUNT VISUAL INSTRUCTIONS 1. Turn damper blades to their fully closed position. Slide actuator onto damper shaft. Tighten the nuts on the universal clamp only finger-tight at this time. 2. Slide anti-rotation mounting strap up under actuator so that it engages actuator at the center cut-out. Secure to ductwork with self-tapping screws. 3. Loosen nuts on clamp. Press manual override button. Rotate the clamp to about 5° from the closed position (1/16 to 1/8" between stop and clamp). Tighten the two nuts on the universal clamp with a 10 mm wrench using 4 to 6 ft-lb of torque. 4. Adjust end stops, if required.

4

5. Mount actuator indoors. If mounted outdoors, use approved protective enclosure. 149

Page 13

Installation Instructions

®

Mechanical Installation

General Information Preliminary steps 1. Belimo actuators should be mounted indoors in a dry, relatively clean environment free from corrosive fumes. If the actuator is to be mounted outdoors, a protective enclosure must be used to shield the actuator. 2. For new construction work, order dampers with extended shafts. Instruct the installing contractor to allow space for mounting and service of the Belimo actuator on the shaft. The damper shaft must extend at least 2" from the duct. If the shaft extends less than 2" or if an obstruction blocks access, the shaft can be extended with the AV 10-18 shaft extension or the ZG NMSA-1 for applications with minimal mounting area. For replacement of existing gear train actuators, it is best to mount the actuator on the damper shaft.

Standard Mounting

The damper is now fully closed but the actuator is 5° from fully closed. This is called “pre-loading” the actuator. When the actuator is powered and sent to the closed position: it will put its

150 full torque on the shaft compressing the edge and blade seals. This ensures that the damper will meet its leakage rating. The actuator is electronically protected from overload and will not be damaged. Adjustable stops The adjustable stops are needed when there is no damper stop or if you want the damper to halt rotating before it reaches its stops. The NM24. . actuator can be indefinitely stalled in any position without harm. 1. Loosen the two end stops with a No. 2 Phillips head screwdriver being careful not to unscrew the captive nut under the slot. 2. Move the stops to the desired position and re-tighten the screws. Manual override The Belimo NM24. . actuators have a black, half round “manual override button” located next to the cable entry. Press this button and the gear train is disengaged so the damper shaft can be moved manually. Release the button and the gear train is re-engaged. Testing the installation without power 1. Disengage the gear train with the manual override button and move the shaft from closed to open to closed. Ensure that there is no binding and that the damper goes fully open and closes with 5° of actuator stroke left. 2. Correct any problems and retest.

G20492-IG-Subject to change. © Belimo Aircontrols (USA), Inc.

1. Remove the plastic position indicator from the actuator. Slip the actuator's universal clamp over the damper shaft. Make sure that the bottom of the actuator (metal side) is toward the duct and the controls on the cover are accessible. Place the actuator in the desired mounting position. 2. Turn the damper shaft until the blades are fully closed. 3. Hand tighten the two nuts on the NM24 . . universal clamp. 4. Slide the stud of the anti-rotation bracket into the slot in the bottom of the actuator. Bend the strap as needed to support the rear of the actuator. 5. Fasten the strap to the duct with two screws. We recommend No. 8 self tapping sheet metal screws. 6. Loosen the two nuts on the universal clamp. Disengage the actuator gear train by pressing the “manual override button” (half round black button near the cable entry). Keeping the gears disengaged, and the damper fully closed, rotate the clamp until it is about 5° from the closed position or approximately 1/16 to 1/8 of an inch between the mechanical stop and the universal clamp. 7. Tighten the two nuts on the clamp with an 10 mm wrench (Belimo Tool-01). Use 4…6 ft-lb of torque.

Page 14

Installation Instructions

®

General Wiring

General Wiring Instructions WARNING The wiring technician must be trained and experienced with electronic circuits. Disconnect power supply before attempting any wiring connections or changes. Make all connections in accordance with wiring diagrams and follow all applicable local and national codes. Provide disconnect and overload protection as required. Use copper, twisted pair, conductors only. If using electrical conduit, the attachment must be made with flexible conduit.

Maximum wire length:

Always read the controller manufacturer's installation literature carefully before making any connections. Follow all instructions in this literature. If you have any questions, contact the controller manufacturer and/or Belimo.

Wire Type and Wire Installation Tips For most installations, 18 or 16 Ga. cable works well with the NM24 type actuators. Use code approved wire nuts, terminal strips or solderless connectors where wires are joined. It is good practice to run control wires unspliced from the actuator to the controller. If splices are unavoidable, make sure the splice can be reached for possible maintenance. Tape and/or wire tie the splice to reduce the possibility of the splice being inadvertently pulled apart.

G20492-Subject to change. © Belimo Aircontrols (USA), Inc.

CAUTION: It is good practice to power electronic or digital controllers from a separate power transformer than that used for actuators or other end devices. The power supply design in our actuators and other end devices use half wave rectification. Some controllers use full wave rectification. When these two different types of power supplies are connected to the same power transformer and the DC commons are connected together, a short circuit is created across one of the diodes in the full wave power supply, damaging the controller. Only use a single power transformer to power the controller and actuator if you know the controller power supply uses half wave rectification. Multiple actuators, one transformer Multiple actuators may be powered from one transformer provided the following rules are followed: 1. The TOTAL current draw of the actuators (VA rating) is less than or equal to the rating of the transformer. 2. Polarity on the secondary of the transformer is strictly followed. This means that all No. 1 wires from all actuators are connected to the common leg on the transformer and all No 2 wires from all actuators are connected to the hotleg. Mixing wire No. 1 & 2 on one leg of the transformer will result in erratic operation or failure of the actuator and or controls. Multiple actuators, multiple transformers Multiple actuators positioned by the same control signal may be powered from multiple transformers provided the following rules are followed: 1. The transformers are properly sized. 2. All No. 1 wires from all actuators are tied together and tied to the negative leg of the control signal. See wiring diagram.

Max. Feet. 2500 Ft. 1600 Ft. 1000 Ft.

Wire Size 18 Ga 20 Ga 22 Ga

Max. Feet 600 Ft. 350 Ft 175 Ft

Fig. 1

The NM24… proportional actuators have a digital circuit that is designed to ignore most unwanted input signals (pickup). In some situations the pickup may be severe enough to cause erratic running of the actuator. For example, a large inductive load (high voltage AC wires, motors, etc.) running near the power or control wiring may cause excessive pickup. To solve this problem, make one or more of the following changes: 1. Run the wire in metallic conduit. 2. Reroute the wiring away from the source of pickup. 3. Use shielded wire (Belden 8760 or equal). Ground the shield to an earth ground. Do not connect it to the actuator common. Reversing switch, “L/R” The NM24-/SR US actuators have a reversing switch on the cover labeled “L/R”. With the switch in position “L”, the actuator rotates clockwise with an increase in voltage or current. With the switch in Position “R”, the actuator rotates counterclockwise with an increase in voltage or current. The NM24 US, on-off, tri-state actuators when set for switch position “R”, rotate clockwise when power is applied to wire #3, and counterclockwise when power is applied to wire #2. During checkout, the switch position can be temporarily reversed and the actuator will reverse its direction. This allows the technician a fast and easy way to check the actuator operation without having to switch wires or change settings on the thermostat. When the check-out is complete, make sure the switch is placed back to its original position.

Wire length for NM type actuators Keep power wire runs below the limits listed in the Fig. 1. If more than one actuator is powered from the same wire run, divide the allowable wire length by the number of actuators to determine the maximum run to any single actuator. Example: 3 actuators, 16 Ga wire 1000 Ft ÷ 3 Actuators = 333 Ft. Maximum wire run. 151

NM

Transformer(s) The NM24 type actuator requires a 24 VAC class 2 transformer and draws a maximum of 4 VA per actuator. The actuator enclosure cannot be opened in the field, there are no parts or components to be replaced or repaired. – EMC directive: 89/336/EEC – Software class A: Mode of operation type 1 – Low voltage directive: 73/23/EEC

Wire Size 12 Ga 14 Ga 16 Ga

Page 15

Installation Instructions

®

Operational Information

Additional Operational Information for NM24-SR US and NM24-MFT US Proportional Actuators

Microprocessor controlled brushless DC motor An on board microprocessor monitors operation and controls a brushless DC motor. It also performs a self test upon power up. Overload protection The Belimo NM24-SR US actuator is protected from overload at all angles of rotation. The on board microprocessor constantly monitors the rotation of the DC drive motor inside the actuator and stops the pulses to the motor when it senses a stall condition. The DC motor remains energized and produces full rated torque to the load. This helps ensure that dampers are fully closed and that edge and blade seals are always properly compressed. Brushless DC motor operation Belimo's brushless DC motor spins by reversing the poles of stationary electromagnets housed inside rotating permanent magnets. The electromagnetic poles are switched by a microprocessor and a special ASIC (Application Specific Integrated Circuit) developed by Belimo. Unlike the conventional DC motor, there are no brushes to wear or commutators to foul. Motor position detection Belimo Brushless DC motors do not use potentiometers for positioning. Inside the motor are three "Hall Effect" sensors. These sensors detect the spinning rotor and send pulses to the microprocessor which counts the pulses and calculates the position. Initialization or function check When a power source is applied to terminal 1 and 2 the motor carries out an initialization of the actuator. If required, a function check can also be made after connection of the supply voltage by pressing in the manual override button and then releasing it. The purpose of this initialization is to determine the mechanical angle of rotation and to adapt the running time to the angle of rotation. The function check can also be used to verify that the damper, and linkage (if mounted) are running free and are correctly adjusted. The function check makes the motor run first to the clockwise or counter-clockwise stop, depending on the selector switch position. Thereafter it runs to the opposite stop. During this operation the output (U5) supplies 2 VDC. Re-initialization Whenever the “manual override button” is pressed and released and the actuator is powered, the microprocessor will “re-initialize”. See “Initialization or function check” above. Motor speed and run time The microprocessor also controls the speed of the motor. In a conventional DC motor, increased torque slows the motor speed. Since the microprocessor determines the total rotation during initialization, it can calculate how fast to turn the motor to insure a 150 second run time independent of the total rotation over a range of 35-95°. Below 35°, the motor runs at a constant speed and the run time is proportional to the angle.

152

Input Resolution During initialization the microprocessor determines the maximum rotation angle. It then divides this angle by the working span of the input signal and calculates how many degrees to travel for each volt change in control signal or pulse length. This means that the working span (Example: 8 V for a 2 to 10 VDC Signal) is consistent for any angle of maximum rotation down to as low as 35°. This greatly simplifies engineering and checkout when dampers have differing maximum rotations. Total Rotation 95° 75° 55°

Run Time 150 Sec. 150 Sec. 150 Sec.

Total Rotation 35° 15° 5°

Run Time 150 Sec. 64 Sec. 21 Sec.

Monitoring and self-adjustment of close-off position The purpose of this function is to correct the mechanical tolerances within 4% which can change over time. It assures that the actuator always presses the damper blade with maximum pressure onto the seal. The end positions are automatically checked as soon as the actuator position comes within 3% of the total angle of rotation, at full open or full closed. If the actuator registers a change of the end position of ≤ 4%, the angle of rotation will be modified. If the actuator registers a change of the end position > 4%, the actuator will consider it an error and not modify the angle of rotation. The actuator will self-adjust until it reaches its mechanical stops. Initialization of NM…MFT US actuators The non-spring return …MFT actuators must go through an initialization procedure to learn the zero signal position. When the power is first applied to the actuator, or the gear release button is depressed, the actuator will move to its zero signal position. After the actuator learns this, it will drive to its control position. Belimo brushless DC motors eliminate the need for potentiometers for positioning. Inside the motor are three “Hall Effect” sensors. These sensors detect the spinning rotor and send pulses to the microprocessor which counts the pulses and calculates the position to within 1/3 of a revolution of the motor.

G20492-IG-Subject to change. © Belimo Aircontrols (USA), Inc.

Controller types Belimo NM24-SR US actuator is compatible with virtually all electronic controllers using a 2 to 10 VDC control signal. And will work with a 4 to 20 mA signal with the addition of a 500Ω resistor.

Page 16

Installation Instructions

®

Control Accuracy and Stability NM24-SR US actuators have built-in brushless DC motors which provide better accuracy and longer service life. The NM24-SR US actuators are designed with a unique non-symmetrical deadband. The actuator follows an increasing or decreasing control signal with a 70 mV resolution. If the signal changes in the opposite direction, the actuator will not respond until the control signal changes by 70 mV. This allows these actuators to track even the slightest deviation very accurately, yet allowing the actuator to “wait” for a much larger change in control signal due to control signal instability. NM Actuator responds to a 70 mV signal when not changing direction from stop Satisfied Control Position

NM Actuator responds to a 70 mV signal when reversing direction from stop position. Minimum Reversed Control Deadband Prior to Normal Control

70 mV

70 mV Satisfied Control Position Minimum Control Resolution

NM

The NM24-MFT US control accuracy and stability can be found in the MFT specifications, page 187.

G20492-Subject to change. © Belimo Aircontrols (USA), Inc.

Additional accessories ZG-NMSA-1 Shaft adaptor

SGA24/SGF24

Used on 1/2" diameter shafts that are shorter than 3/4" and mounting space is minimal.

Minimum and/or manual positioner (electronic), SGA24 is enclosed in a NEMA 4 housing. The SGF24 is for flush panel mounting.

SGF24 SGA24

AV 10-18 Shaft Extension

ZG-H2 Actuator Operator Handle

For damper shafts 3/8 to 11/16 in [9.5 mm to 18 mm] dia or 3/8 to 9/16 in [9.5 mm to 14 mm] square.

Used when it is desirable to move or adjust damper by hand. Increases leverage and precision during set-up and testing.

Dimensions [All numbers in brackets are in millimeters.]

153

Page 17

Startup and Checkout

®

Instructions For NM24-SR US and NM24-MFT US + P-100…

Actuator Responds Go To Step ...

No Response Go To Step

Actuator drives to the “No Signal” position (usually closed), then to the “Maximum Signal” position (usually open) then to the “Control Signal” position.

Actuator operates properly Step 9

No response at all Step 2 Operation is reversed Step 3 Does not drive toward "Control Signal Position" Step 4

Check power wiring. Correct any problems. Note 1

Power supply rating should be ≥ the total power requirement of the actuator(s). Minimum voltage of 19.2 VAC or 21.6 VDC.

Power wiring corrected, actuator begins to drive Step 1

Power wiring corrected, actuator still does not drive Step 8

3.

Turn reversing switch to the correct position. Make sure the switch is turned all the way left or right. Press “Override Button” all the way down and release

Actuator drives to the “No Signal” position (usually closed), then to the “Maximum Signal” position (usually open) then to the “Control Signal” position.

Actuator operates properly Step 9

Does not drive toward “Control Signal Position” Step 4

4.

Make sure the control signal positive (+) is connected to Wire No 3 and control signal negative (-) is connected to wire No. 1. Most control problems are caused by reversing these two wires. Verify that the reversing switch is all the way CCW or CW.

Drives to “Control Signal” position

Actuator operates properly Step 9

Step 5

5.

Disconnect signal input from Wires No. 1 & 3

Actuator drives to the “No Signal” position

Step 6

Step 8

6.

Check input signal with a digital volt meter (DVM). Make sure the input is within the range of the actuator. For NM24-SR this is 2 to 10 VDC or 4 to 20 mA (with 500Ω resistor).

Input voltage or current should be ±1% of what controller's adjustment or programming indicate.

Controller output (actuator input) is correct. Input Polarity Correct. Step 7

Reprogram, adjust repair or replace controller as needed. Step 7

7.

Disconnect power from Wire No. 2. Reconnect signal input to Wires No. 1 & 3. Reconnect power to Wire No. 2

Actuator drives to the “No Signal” position (usually closed), then to the “Maximum Signal” position (usually open) then to the “Control Signal” position.

Actuator operates properly Step 9

Step 8

8.

Actuator does not drive

Defective actuator

9.

Actuator works properly. Test controller by following controller manufacturer's instructions.

Step

Procedure

Expected Response

1.

Connect signal Input to wires 1 & 3. Connect signal output (if used) to wires 1 & 4 Connect 24 VAC/VDC power to Wires 1 & 2

2.

Note 1

154

Replace actuator

Check that the transformer(s) are sized properly. • If a common transformer is used, make sure that polarity is observed on the secondary. This means connect all No. 1 wires to one leg of the transformer and all No. 2 wires to the other leg of the transformer. • If multiple transformers are used with one control signal, make sure all No. 1 wires are tied together and tied to control signal negative (-). • Controllers and actuators must have separate 24 VAC/VDC power sources.

G20492-IG-Subject to change. © Belimo Aircontrols (USA), Inc.

NM24-SR US and NM24-MFT US + P-100… Electrical check-out procedure