Page 11

SOLID STATE RELAYS WIRING DIAGRAM:

1 Load

AC Line (24 - 660 Vac)

SOLID STATE RELAY Smart Module Error Output (2)

(4-32 Vdc)

DC Power Supply (2)

(4-32 Vdc)

Error Indicator Input Indicator

Input

(3-32 Vdc) (1)

Ground (2)

Note: Note: 1. G480D and G575D Series DC Input Range is 4-32 Vdc 1. HV GN Series DC Input Range is 4-32 Vdc 2. Input, Outputs and DC Power Supply 2. voltages Input, Outputs and DC Supply are refered to Power the same common Ground voltages are referred to the same common Ground

Products and specifications subject to change without notice.

Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com 1/7

Page 12

DC Solid State Relays GF Series; FET output - 10A, 15 A, 30A Very low leakage current (< 10uA) Milliohm On-Resistance Minimizes voltage drop, heat dissipation 1500 VAC Optical Isolation UL/cUL recognized, Tuv approved, CE compliant

IP20

00 49 13 84

GT Series; transistor output 10A Long Life Switching of DC loads 4 kV Optical Isolation UL E46203 Available with IP20 “touch-safe” cover

IP00

Output Specifications Output Voltage range VDC Off-state leakage mA Output Current (Mounted on proper heat sink, see deratings) Minimum Current Max. 1 second surge current Max On-State Voltage Drop or On-State Resistance m Ohms Rjb (thermal res. Junction to baseplate, ºC/W) Minimum hear sink @ ambient (for max current = ºC/W & Ta)

FET 1-200 0.01 10

FET 1-100 0.01 15

FET 1-50 0.01 30

TRAN 3-60 1.0 10

0.1 60 n/a 90 4.4

0.1 120 n/a 90 4.6

0.1 160 n/a 50 2.3

10 90 n/a n/a 4.3

3.0 @ 25ºc

3.0 @ 25ºC

1.0 @ 25ºC

1.0 @ 65ºC

Part Numbers FET Output Rating 10 Amp 15 Amp 30 Amp

Output 1-200Vdc 1-100Vdc 1-50Vdc

Input 3-32Vdc 3-32Vdc 3-32Vdc

IP00 84 134 850 84 134 860 84 134 870

IP20 84 137 850 84 137 860 84 137 870

3-32Vdc

84 134 750

84 137 750

Transistor Output 10 Amp

3-60Vdc

Input Specifications Input voltage* Drop out voltage Max. input current (mA) Min. input current (for on-state) m Input Resistance Max. Turn-on time (mS) Max. Turn-off time (uS)

20 12 2 50

3-32Vdc 1Vdc 20 20 12 12 Current Regulated 2 2 50 50

14.5 9 .1 200

General Characteristics Operating Temperature (°C) Storage Temperature (°C) Input to output isolation Input/output to ground isolation Input to output capacitance Housing Material

-20 to +80 -40 to +100 4000Vrms 2500Vrms 8pF (typical) UL 94V0 (self extinguishing)

Safety and Noise Immunity Compliance CE Compliant with the LVD 73/23/EEC TUV EN60950

4

1 CONTROL CIRCUIT

3

+

+

2

Rc GT SERIES EQUIVALENT CIRCUIT

DC inductive loads must be diode suppressed to prevent damage to SSR

1

4 CONTROL CIRCUIT

+ 3

+

CURRENT REGULATOR

2

GF SERIES EQUIVALENT CIRCUIT

Products and specifications subject to change without notice.

Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com 1/8

Page 13

Dual Solid State Relays 40 amp dual AC output relays Output voltage from 24 to 280 Vac Direct bond copper substrate Back to back dual SCR output 4000 Vac optical isolation Zero crossing or random turn on UL/cUL E79183, CE Compliant

1 Part Numbers

24 - 280Vac 550 0.1

24 - 280Vac 550 0.1

Output Current (Mounted on proper heat sink, see deratings) Minimum Current (mArms) Max. 1 cycle surge current (Apk, Ta = 25°C) Max. 1 second surge current (Apk, Ta = 25°C) Forward voltage drop (Vpk @ Imax, Ta = 25°C) I2T (60Hz, 1/2 cycle) Rjb (thermal res. Junction to baseplate, °C/W) Static off-state dv/dt (Vµs, Ta = 25°C)

25

40

100 500

100 780

150

234

1.4

1.3

1041 0.6

2435 0.4

500

500

4-15Vdc 1Vdc 7.5mA 34mA 500 8.33msec 8.33msec

17-32Vdc 1Vdc 13mA 24mA 1500 8.33msec 8.33msec

Input Specifications Input voltage Drop out voltage Min. input current (for on-state) Maximum input current Input Resistance (Ohms) Turn-on time* Turn-off time *Random SSR’s turn on in less than 100µs

General Characteristics Operating Temperature (°C) Storage Temperature (°C) Input to output isolation Input/output to ground isolation Input to output capacitance Operating Frequency Housing Material

-40 to +80 -40 to +100 4000Vrms 2500Vrms 8pF (typical) 47 to 63 Hz UL 94V0 (self extinguishing)

Standards of Compliance CE Compliant with the LVD 73/23/EEC UL / cUL Recognized per UL 508 and CSA C22.2 no. 14-M91

Rating 25 Amp 25 Amp 40 Amp 40 Amp Rating 25 Amp 25 Amp 40 Amp 40 Amp 84 137 011 Combined Channel Output Current (Amperes)

Voltage range (Vrms) Peak Voltage (Vpk, t = 1 min.) Off-state leakage mArms (@ max. line voltage & Ta = 25°C)

Zero Crossing Output Output Input 24-280Vac 4-15Vdc 24-280Vac 17-32Vdc 24-280Vac 4-15Vdc 24-280Vac 17-32Vdc Random Fire Output Output Input 24-280Vac 4-15Vdc 24-280Vac 17-32Vdc 24-280Vac 4-15Vdc 24-280Vac 17-32Vdc

Part Number 84 140 000 84 140 010 84 140 200 84 140 210 Part Number 84 140 100 84 140 110 84 140 300 84 140 310

DERATE CURVE: 25 AMP GN Series Dual SSRs

Ambient Temperature (°C)

DERATE CURVE: 40 AMP GN Series Dual SSRs

Combined Channel Output Current (Amperes)

Output Specifications

▲

▲

0.375

▲

Mating Connector AMP #640441-4

▲

1.131

▲

▲

Ambient Temperature (°C)

0.175 ▲

▲

▲

1.256

0.886 ▼

▼

Products and specifications subject to change without notice.

Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com 1/9

Page 14

SOLID STATE RELAYS GA1, GA8, SERIES High Current Thyristor for 100A Surge Capability UL Recognized/Horse Power Rated (GA8) (E46203) 4KV Optical Isolation

Zero Voltage Turn-On Industry Standard Packaging, SIP or Flat Pack Form A Output CE Compliant

GA1 0.15 (3,8)

0.15 (3,8)

2(OUTPUT)1

1.2 (30,5)

1.5 (38,2)

1.1 (27,9)

4 (INPUT) 3+ 0.3 (7,6)

0.8 (20,3) 0.04 (1.0) DIA. TYP. 1.4 (35,6)

0.25 (6,4)

4

3

2

1

1.0 (25,4)

0.035 (,89)

0.245 (6,2)

0.375 (9,5)

GA8 DIMENSIONS: inches (mm) TOLERANCE: ±0.020 (±0,50)

0.042 (1,1) DIA 1.7 (43,2)

TRIGGER CIRCUIT

0.3 (7,6) 0.7 (17,8)

1

+

SNUBBER

0.1 (2,5)

0.4 (10,2)

4

2

3

1.2 (30,5) 1.4 (35,5)

DIMENSIONS: inches (mm) TOLERANCE: ±0.020 (±0,50)

GA1 & GA8 SERIES DC INPUT EQUIVALENT CIRCUIT

Products and specifications subject to change without notice.

Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com 1/10

Page 15

SOLID STATE RELAYS GA1, GA8, SERIES

1

INPUT SPECIFICATIONS: (1) Parameter Minimum Turn-On Voltage Maximum Input Voltage Drop Out Voltage Maximum Input Current (2) Nominal Input Resistance (3)

GA16B02 GA86B02 3.0 28 1.0 25 1K

GA86D05 GA86D05R 3.0 28 1.0 25 1K

Units VDC VDC VDC mADC

GA16B02 (10) GA86B02

GA86D05 GA86D05R

Units

240 24 280 ±600 200

240 24 280 ±600 200

Vrms Vrms Vrms Vpeak

GA16B02 GA86B02 4.0 .05 100 1.6

GA86D05 GA86D05R 5.0 .05 100 1.6

Units Arms Arms Apeak Vpeak

.1 1/4

.1 1/4 mArms H.P.

All Devices -30 to +80 -40 to +100 .5 4000 8 47 to 63

Units °C °C Cycle Vrms pF Hz

OUTPUT SPECIFICATIONS: Model Number Parameter Nominal Line Voltage Minimum Line Voltage Maximum Line Voltage Maximum Peak Off-State Voltage(4) Static (Off-State) dv/dt

Parameter Maximum On-State Current (5) Minimum On-State Current Maximum 1-Cycle Surge (6) On-State Voltage Drop (7) Maximum Off-State Leakage (8) 240V Models HP Rating (11)

GENERAL SPECIFICATION: (1) Parameter Operating Temperature Range Storage Temperature Range Response Time (12) Input to Output Isolation Voltage (9) Capacitance Input to Output (Typ) Line Frequency Range Note:

GA1-2B and GA1-4B have been replaced by GA1-6B GA8-2B and GA8-4B have been replaced by GA8-6B

10

5 AMP. GA8 DERATING CURVE

9 8

A rms

7 6 5 AMP.

Notes: (1) Specifications apply to Ta -30 TO +80 unless otherwise noted. (2) At maximum input voltage. (3) Does not include IRED impedance (drop). (4) One minute maximum duration when applied as a DC Voltage. (5) At Ta of 20°C, derate by 25 mA/°C to 40°C, 50 mA/°C from 40°C to 80°C. UL rating is 3.5 Arms, CSA rating is 3.0 Arms. (6) At Ta of 25°C, non-repetitive. (7) At Ta of 25°C and maximum on-state current. (8) At Ta of 25°C and maximum line voltage. (9) At Ta of 25°C, for one second. (10) Random turn-on versions available. Specify by adding suffix “R” to appropriate part number. Contact factory for additional details. (11) For GA8 only, 1/4 H.P. at 240 VAC, 1/8 HP at 120 VAC (12) AT 60 Hz 100 µS for Random Turn-on (suffix “R”) models

4 3 2 1 0 –30

–20

–10

0

10 20 30 40 50 TEMPERATURE DEGREE C

60

70

80

Products and specifications subject to change without notice.

Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com 1/11

Page 16

SOLID STATE RELAYS THREE-PHASE SOLID STATE RELAYS 10, 25 and 45 Amps Output Per Channel Available 24 to 600 VAC Output Voltage Range Suitable for Many Applications 1200 Volts Peak Blocking Voltage Helps Protect Against Transients in Harsh Electrical Environments Internal RC Snubber Network

4000 VAC Optical Isolation 4 to 32 Control Voltage for a Wide Variety of Logic Circuit Applications Zero Voltage or Random Turn-on Industry Standard Package UL Recognized (E74183) 10 hp 480 VAC, CSA Certified (LR38545) CE Compliant

CURRENT LIMITER

1

A1+ U ZERO VOLTAGE DETECTOR

OVER VOLTAGE PROTECTION

S N U B B E R

U ZERO VOLTAGE DETECTOR

OVER VOLTAGE PROTECTION

S N U B B E R

4 5 U ZERO VOLTAGE DETECTOR

A2–

OVER VOLTAGE PROTECTION

S N U B B E R

DIMENSIONS: INCHES (MILLIMETERS) TOLERANCE:+-0.020 ( +- 0.50)

0.91˝ (23.1)

1.16 (29.4)

OUTPUT TERMINALS 4.0 mm (6)

4.09 (104.0)

0.3 (7.62)

– +

4

6

1

3

5

2.89 (73.5)

A2

0.2 (5.3)

A1

1.87 (47.6) 2

INPUT TERMINALS 3.5 mm (2) 0.47 (12.1) 0.25 (6.35) 3.62 (92.0)

Products and specifications subject to change without notice.

Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com 1/12

6

OUTPUT

INPUT

2 3

Page 17

SOLID STATE RELAYS THREE-PHASE SOLID STATE RELAYS

1

INPUT SPECIFICATIONS: (1) Model Number

GA312D10R GA312D10Z GA312D25R

Parameter Voltage Range Drop Out Voltage Control Current (2)

GA312D25Z GA312D45R GA312D45Z

4.0 to 32.0 VDC 1.0 VDC 20 mA

GA312A25R GA312A25Z GA312A45R GA312A45Z 90-280 VAC 10 VAC 10 mA

OUTPUT SPECIFICATIONS: (1) Model Number

GA312D10R GA312D10Z

GA312A25R GA312A25Z GA312D25R GA312D25Z

GA312A45R GA312A45Z GA312D45R GA312D45Z

Parameter Line Voltage Range SSR Maximum Peak Off-State Voltage (3) Rated Current (4) Minimum Current Maximum Off-State Leakage (5) One Cycle Surge Current (6) l2t Fusing Current Maximum On-State Voltage Drop (7) Off-State dv/dt (8)

24 to 660 1200 10 0.2 10.0 160 128 1.6 500

24 to 660 1200 25 0.2 10.0 270 365 1.6 500

24 to 660 1200 45 0.2 10.0 450 1000 1.6 500

GA312D10R GA312D25R GA312D45R

GA312D10Z GA312D25Z GA312D45Z

GA312A25R GA312A25Z GA312A45R GA312A45Z

-30 to 80°C -40 to 100°C .20 8.33 4000 4000 8 47 to 63 450

-30 to 80°C -40 to 100°C 8.33 8.33 4000 4000 8 47 to 63 450

-30 to 80°C -40 to 100°C 20 30 4000 4000 8 47-63 450

Units VAC Vpeak Arms Arms mArms Apeak A2 Seconds Volts

GENERAL SPECIFICATIONS: (1)

Parameter Operating Temperature Range Storage Temperature Range Maximum Turn-on Time (9) Maximum Turn-off Time (10) Input/Output Isolation (11) Input/Output to Base Isolation (11) Input/Output Capacitance (typical) Line Frequency Range Weight

GA3 SERIES 3 PHASE SOLID STATE RELAY PART NUMBER SELECTION GUIDE OUTPUT RATING FUNCTION

10A

25A

45A

GA312D10R

GA312A25R

GA312A45R

GA312D25R

GA312D45R

Random Turn-on Zero Voltage Turn-on

GA312D10Z

GA312A25Z

GA312A45Z

GA312D25Z

GA312D45Z

UNITS °C °C mSec mSec VAC VAC pF Hz g

Notes: (1) Specifications apply to each phase at an ambient temperature of -20 to 80°C unless otherwise noted. (2) Input is regulated and current limited. (3) 1000 V peak with Transorb® protection. Applying 1000V or greater will increase the off-state leakage and may result in relay failure if applied for longer than 1 second. (4) See thermal dissipation/derating chart for heat sinking requirements. Catalog number HS-7 heat sink available separately for mounting GA3 series SSR’s. (5) At 480 VAC line voltage, 25°C. (6) One AC cycle maximum duration, non-repetitive, 25°C. (7) At rated output current, 25°C. (8) Minimum dv/dt per EIA/NARM RS443, method RS397, 25°C. (9) At minimum input voltage, maximum line voltage, rated output ourrent, 25°C. (10) At maximum input voltage, maximum line voltage, rated output current, 25°C. (11) At 25°C for 1 second maximum duration.

Products and specifications subject to change without notice.

Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com 1/13

Page 18

SOLID STATE RELAYS THREE-PHASE MOTOR REVERSING RELAYS Convenient Self-Contained Design Eases Installation and Wiring 24 to 600 VAC Output Voltage Range Suitable for Many Applications 1000 Volts Peak Blocking Voltage Helps Protect Against Transients in Harsh Electrical Environments 5000 VAC Isolation

3 to 32 Control Voltage for a Wide Variety of Logic Circuit Applications Compact Sealed Package with Screw Terminals Interlock Circuit Prevents Inadvertant Actuation of Both Directions UL and cUL Recognized E79183 CE Compliant

O V P O V P O V P

➝

O V P V OVER VOLTAGE PROTECTION

EQUIVALENT CIRCUIT 4.09 (104,0)

3.19 (81,0)

OUTPUT TERMINALS 4.0 mm (4)

2.4 (61,0) DIMENSIONS: INCHES (MILLIMETERS) TOLERANCE:+-0.020 ( +- 0,50) 1.6 (41,0)

0.3 (7,62) 0.82 (21,0) 1.87 (47,6) U

L2

Y

V

0.2 (5,3) 2.89 (73,5)

0.73 (18,5)

L1

0.88 (22,6)

A1F

A2

A1R

0.47 (12,1) 0.25 (6,35) INPUT TERMINALS 3.5 mm (3)

3.62 (92,0)

Products and specifications subject to change without notice.

Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com 1/14

Page 19

SOLID STATE RELAYS THREE-PHASE MOTOR REVERSING RELAYS

1

INPUT SPECIFICATIONS: (1) MODEL NUMBER Parameter Voltage Range Drop Out Voltage Control Current (2)

GA012D25 GA012D40 3.0 to 32 1.0 25

Units VDC VDC mA

GA012D25

GA012D40

24 to 660 1200 25 0.2 .25 270 365 1.6 500

24 to 660 1200 40 0.2 .25 450 1000 1.6 500

OUTPUT SPECIFICATIONS: (1) MODEL NUMBER Parameter Line Voltage Range Maximum Peak Off-State Voltage (3) Rated Current (4) Minimum Current Maximum Off-State Leakage (5) One Cycle Surge Current (6) l2t Fusing Current Maximum On-State Voltage Drop (7) Off-State dv/dt (8)

Units VAC Vpeak Arms Arms mArms Apeak A Seconds Volts peak

GENERAL SPECIFICATIONS: (1) Parameter Operating Temperature Range Storage Temperature Range Maximum Turn-on Time (9) Maximum Turn-off Time (10) Input/Output Isolation (11) Input/Output to Base Isolation (11) Input/Output Capacitance (typical) Line Frequency Range Weight Interlocking Time

All Devices -30 to 80°C -40 to 100°C 150 ms 1/2 cycle 4000 VAC 2500 VAC 8 pF 47 to 63 Hz 455 grams 100 mSec

GAO THERMAL DISSIPATION CURVES

THERMAL DISSIPATION 25 AMP GAO SERIES (ALL)

5°

1°

C/

W

80

C/

W

40

90 2° C

/W

30

100

3° C/W

20

110

10

120

NO HEATSINK

0

5 10 15 ON-STATE CURRENT (AMPS rms)

20

25

10

20

30

40

50

60

AMBIENT TEMPERATURE (°C)

70

80

BASEPLATE TEMPERATURE (°C)

POWER DISSIPATION (WATTS)

70 0.

50

Notes: (1) Specifications apply to each phase at an ambient temperature of -20 to 80°C unless otherwise noted. (2) Input is regulated and current limited. (3) Semiconductors rated at 1200 V. (4) See thermal dissipation/derating chart for heat sinking requirements. Catalog number PR250/100SE2 heat sink available separately for mounting GAO series SSR’s. (5) At maximum line voltage, 25°C. (6) One AC cycle maximum duration, non-repetitive, 25°C. (7) At rated output current, 25°C. (8) Minimum dv/dt per EIA/NARM RS443, method RS397, 25°C. (9) At minimum input voltage, maximum line voltage, rated output ourrent, 25°C. (10) At maximum input voltage, maximum line voltage, rated output current, 25°C. (11) At 25°C for 1 second maximum duration.

Products and specifications subject to change without notice.

Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com 1/15

Page 20

SOLID STATE RELAYS GZ SERIES SSR FEATURES: 12 & 20 Amp AC Output Relays Low Profile Package Economical Triac Output 4000 VAC Optical Isolation Zero Crossing or Random Turn-On UL/cUL Recognized E46203

DIMENSIONS:

DERATE CURVES: LOW CURRENT STANDARD GZ SSRs 12 AMP 12.0 11.5 11.0 10.5

Load Current (Amperes)

10.0 9.5 9.0

HEAT SINK RATINGS:

8.5

0.5°C/W 0.7°C/W 1.0°C/W 1.5°C/W 2.0°C/W

8.0 7.5 7.0 6.5 6.0 5.5 5.0 20

25

30

35

40

45

50

55

60

65

70

75

80

Ambient Temperature (°C)

DERATE CURVES: HIGH CURRENT STANDARD GZ SSRs 20 AMP 20.0 19.0 18.0

WIRING:

17.0 16.0

1

4 TRIGGER

HEAT SINK RATINGS:

14.0 13.0

0.5°C/W 0.7°C/W 1.0°C/W 1.5°C/W 2.0°C/W

12.0 11.0 10.0

CIRCUIT + 3

2 Rc

GZ SERIES DC INPUT EQUIVALENT CIRCUIT

9.0 8.0 7.0 6.0 -20

-15

-10

-5

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

Ambient Temperature (°C)

Products and specifications subject to change without notice.

Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com 1/16

SNUBBER

Load Current (Amperes)

15.0