Page 21

With the sample.820 configuration open, you should see the following screen:

This main screen is the total focal point for the configuration. All aspects of the D820 can be both viewed and controlled through this main screen through either the drop menus or the toolbar.

Getting Started User’s Guide

11

Page 22

How the Page Directory Operates

Page Controls Hardware Setup

Preview of Page Directory of Pages Data Reference Button

The Page Directory is the heart of the Micro PanelMate Configuration Editor. Once you become familiar with the fundamentals of how this directory operates creating and editing a configuration is extremely simple. The following pages will define each aspect of the Page Directory. Each topic will be broken down and demonstrated via the sample.820 application that was already opened and downloaded to your Micro PanelMate D820.

12

Getting Started User’s Guide

Page 23

Directory of Pages The Page List is located on the right side of the Page Directory. It will display, in numeric order, all pages in the configuration. This quick listing allows you to step through the pages available in your configuration without having to remember what each page number is and/or description. By double clicking on any page, you will be taken directly into the Page Editor.

Preview of Pages To enhance the Page List, the Micro PanelMate Configuration Editor also has an unique feature, page preview. As you step through the pages in the Page List, the D820 will display the actual page on the display. Therefore, instead of opening each individual page to review its contents, simply preview them via the D820’s window. Once you have found the page you would like to edit, either double click the image of the page on the D820 display, double click the actual page number in the Page List, or select the Edit button.

Hot Key for Data References Since the Micro PanelMate Series of Operator Interface Terminals utilizes a spreadsheet format for data references, the opportunity to edit these tags is available from several locations. The easiest, and most obvious, is the Data References button located on the bottom left hand corner of the Page Directory. This button will take you directly to the PLC Data Reference Editor dialog box.

Page Controls The New, Delete, Duplicate, and Edit buttons are used exclusively for the maintenance of pages. If a page is currently highlighted, such as page [001] Main Menu in the previous example, the Delete, Duplicate, and Edit buttons will bring up the associated dialog box. The New button will trigger a dialog box to create a new page with a unique page number. Prior to creating, deleting, duplicating, or editing a page, let’s explore the method of setting up the D820 and its respective data tags.

Getting Started User’s Guide

13

Page 24

How to Setup the D820 Hardware Configuration This task can be accomplished several ways. The easiest is by double clicking the picture of the D820. Keep in mind that you want to double click anywhere but the preview of the page. If you accidentally double click the preview of the page, you will be taken into the Page Editor. Although this is not a problem, this manual will not cover the Page Editor until later on. Simply close the Page Editor and double click on the D820. You may double click on the D820 or choose the D800 selection from the Setup Menu to setup the hardware. The following dialog box will appear:

This dialog box defines the serial port and the dialog file locations within the PLC data table. The Integer Triggers Reference field allows you to enter a reference in which the D820 will read and write page numbers internal to the PLC. The Command Register Reference field allows you to specify a reference location where the D820 will write the YES and NO keys. The D800 Node Address field allows you to enter the physical node address of the D820. In order to understand this dialog box, we must explore the Data Reference Editor. So click on the Data References button.

14

Getting Started User’s Guide

Page 25

How to Use the Data Reference Editor Once having clicked the Data References button, the following dialog box will appear:

The Micro PanelMate Series of Operator Interface Terminals utilizes a spreadsheet format for data tags. This matrix can be exported, imported, duplicated, etc. The advantage of this format is the fact that you can import your entire label listing directly from the GPC programming software for the D50/D300, thus eliminating the need for creating new information and doubling your development time. Let us take a look at the Edit Nodes dialog box. Setting your nodes up prior to creating your data tags on a new application will help expedite your development. Keep in mind, that since you are editing an existing configuration (sample.820), these attributes have already been set.

Getting Started User’s Guide

15

Page 26

D50/D300 Node List Editor Once you have selected the Edit Nodes button in the PLC Data Reference Editor, the following dialog box will appear:

As mentioned earlier, it is easiest to create and edit data tags if these nodes have been assigned first. The current example places the D50 PLC at node address 255. The reason for selection of this node address is because of the D50/D300 structure. An address of 255 is a global address. Therefore, if you have changed your D50/D300 address, the 255 will ignore its setting and still allow the Micro PanelMate to talk to the D50/D300 without any problems. Since the Micro PanelMate also resides on the D50/D300 network, it must also have a node address. For this example, we are using node 1. Network Tip:

If you are using multiple D50/D300 PLCs on your network and would like information from any of them, simply place them into your D50/D300 Node List Editor and reference them in your Data Reference Editor. This will allow the Micro PanelMate to gather information from all PLCs located on the network.

Select the Cancel button to return to the Data Reference Editor. If you would like additional information on the D50/D300 network, please refer to the D50/D300 Hardware Guide.

16

Getting Started User’s Guide

Page 27

Once having returned to the Data Reference Editor, you have the following options: 1. 2. 3. 4. 5. 6. 7.

Editing an Existing Reference Creating a New Reference Duplicating an Existing Reference Delete References Purging Unused References Sorting Your References Importing/Exporting References Since your demo application has already included an entire Data Reference Spreadsheet, using the Data Reference Editor in detail is not necessary. However, please feel free to navigate through this dialog box in order to familiarize yourself with its features. If you desire additional information, use the on-line help. If you click on the Node column, you will notice a dropdown listing of all the nodes available. Currently, there are the D50 PLC and the MICROPANELMATE. As mentioned in the D50/D300 Node List Editor topic, you can place as many nodes as are supported on the D50/D300 network in this listing. Select the Cancel button to return to the Cutler-Hammer D820 Properties dialog box. The values you see under the Integer Trigger and Command Word are references that are in the Data Reference Editor. The Node address is coming directly from the Node Editor. Select the Cancel button once again to return to the Page Directory screen. Your hardware configuration is complete. We are now ready to look at the pages.

Getting Started User’s Guide

17

Page 28

How to Define the Page Properties Although you have an entire configuration already loaded into your D820, let us go ahead and create a new page. Select the New button on the right hand side of the Page Directory and the following dialog box will appear:

Use a descriptive name for the Page Name field. Keep in mind that the name will appear along with the page number when we return to the Page Directory. The advantage of using a descriptive name is the fact that you will be able to easily identify it when looking at the Page List. Note that in the Page Number field, you may enter any number between 1 and 400. The Open Options fields cannot be configured for a D820 unit.

18

Getting Started User’s Guide

Page 29

The Previous Page and Next Page fields allow this page to either return to where it came from or go to another page (linking). If you choose to leave zeros in both the Previous Page and Next Page fields, the D820 will be forced to stay on that page until the D50/D300 decides to trigger another page through ladder logic. The description simply allows you to explain, in detail, what the purpose of this page is relative to the configuration. As you will see, the sample.820 has descriptions for every page. This allows you to understand each page even though you did not do the original development. In Page Name field, type: Getting Started Demo. In the Previous Page field, type: 7. In the Next Page field, type: 1. In the description field, type: Getting Started Demo Screen. Click the OK button. At this time, you should see the following dialog box:

The image of the Page Editor depicts the actual D820 screen (2 lines by 16 characters). You are allowed to place up to three objects on the page at any one time.

Getting Started User’s Guide

19

Page 30

Page Objects The three icons listed above are the tools available for the D820 for creating a page.

The arrow icon is the Select Objects tool. This allows you to select a singular object or group of objects on the page window. Use this tool when you want to move an object, edit an object, or select an object.

The “A” icon is the Static Text tool. This allows you to create text on the 2x16 display window. You are allowed to create up to three Static Text objects on one page. However, keep in mind that you can put text as one object and lay a PLC Data object on top. To place text on the screen, follow these steps: 1 Select the Static Text tool. 2 Click on the page where you wish to place the text. 3 Type the text in the Selected Object Text field as shown in the figure below. 4 Click off the edit area to close the field. NOTE:

If a space is entered as a Static Text object, the object cannot be selected or deleted.

The figure below shows you how to place two PLC Data objects on the page along with their respective Static Text descriptions without surpassing the three object limit.

Type in text, but leave gaps for the PLC data. Thus, creating only one Static Text object.

20

Getting Started User’s Guide