Page 1 of Molded Case Circuit Breakers 15-100 Amperes, Series CT G-Frame

Spec sheet · Cutler-Hammer

Molded Case Circuit Breakers 15-100 Amperes, Series CT G-Frame

Spec sheet6 pagesPDF 143 KB

Cutler-Hammer catalog pages for Series CT G-Frame molded case circuit breakers, 15 to 100 A: types GD, GB, GHB, GC and GHC, including the GHC3015.

Download the PDF143 KB

Covers · 2 models

The models it covers

Summary

What is in it

Catalog pages for Cutler-Hammer Series CT G-Frame molded case circuit breakers rated 15 to 100 amperes. They give UL489 interrupting capacity ratings, the catalog numbering system, terminal types, and catalog number tables by pole count and ampere rating for types GD, GB, GHB, GC and GHC (such as the 3-pole, 15 A GHC3015), ground fault circuit protectors, special purpose breakers with screw-type terminals, dimensions, weights and accessories.

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

Cutler-Hammer catalog pages dated March 1999 for Series CT G-Frame molded case circuit breakers, 15-100 amperes. They cover Types GD, GB, GHB, GC and GHC plus the GHBGFEP and GHCGFEP ground fault circuit protectors, and list part numbers by type, poles and ampere rating. The GHC3015 appears in the Type GHC table, with terminal types, dimensions and accessories on the following pages.

Device
Type GHC thermal-magnetic molded case circuit breaker, Series CT G-Frame, non-interchangeable trip units p. 4
Number decoded
GHC3015: Type GHC, 3 poles, 15 trip amperes p. 1, 4
Voltage
Type GHC: 277 and 480Y/277 volts p. 4
Terminals
GHC3015: .190-32 screw type clamp terminals p. 4
Common trip
All two- and three-pole breakers are common trip p. 1
Reverse feed
All G-frame breakers are suitable for reverse feed p. 1
Size, 3-pole
3.0 x 4.88 x 2.81 in (76 x 123.95 x 71.41 mm), width x height x depth p. 6
Federal class
Type GHC, 2 and 3 poles: Class 13b p. 4
Frame range
Series CT G-Frame, 15-100 amperes p. 1
HACR
HACR rated p. 1
Instruction leaflet
Type GHC: Instruction Leaflet/FRED Number 15548 p. 4
Accessories
Internal: alarm switch, auxiliary switch, shunt trip, undervoltage release mechanism; external: base mounting hardware and plate, DIN rail adapter, key operated attachment, lock dog, padlockable handle, handle mechanisms p. 6
Catalog date
March 1999, PG.74A.01.T.E p. 6

What this sheet walks you through

  • Reading G-Frame catalog numbers (type, poles, trip amperes, suffix) p. 1
  • Interrupting capacity ratings by breaker type and poles p. 1
  • Terminal types and wire ranges for line and load side p. 1
  • Choosing a Type GC or GHC breaker by poles and ampere rating p. 4
  • Choosing Type GB and GHB bolt-on panelboard breakers p. 3
  • 30mA industrial ground fault circuit protectors p. 3, 4
  • Ordering special purpose GC and GHC breakers with binding head screw terminals p. 5
  • Dimensions, shipping weights and accessories p. 6

Good to know

  • The catalog numbering chart is only an aid to understanding part numbers, not for building them. p. 1
  • For 3-phase Delta (240V) grounded B phase applications, the sheet says to refer to Cutler-Hammer. p. 1
  • The metric wire ranges given for the terminals are not UL listed sizes. p. 1
  • The special purpose screw-terminal breakers are marked as not for general use. p. 5

Questions this sheet answers

What does the part number GHC3015 mean?

Following the sheet's numbering chart: circuit breaker Type GHC, 3 poles, 15 trip amperes. p. 1, 4

What terminals does the GHC3015 breaker use?

The GHC3015 is footnoted as using .190-32 screw type clamp terminals. p. 4

Can a Cutler-Hammer G-frame breaker be reverse fed?

Yes. All G-frame circuit breakers are suitable for reverse feed use. p. 1

How big is a 3-pole G-frame breaker?

3.0 in wide, 4.88 in high and 2.81 in deep (76 x 123.95 x 71.41 mm). p. 6

Which instruction leaflet covers the Type GHC breaker?

Instruction Leaflet/FRED Number 15548. p. 4

The whole text · 1 part

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 61-6

The file

Revision and size

RevisionPG.74A.01.T.E, March 1999
PublisherCutler-Hammer
Pages6
PDF143 KB
TextText from the PDF itself.

The first pages · 4 of 6

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 6
Page 2
Page 2of 6
Page 3
Page 3of 6
Page 4
Page 4of 6