The text of a spec sheet · part 1 of 1

Molded Case Circuit Breakers 15-100 Amperes, Series CT G-Frame, pages 1 to 6

Pages 1 to 6 of 6

The original document is the PDF (143 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Cutler-Hammer GHC3015 and Eaton GHC3015

Page 1

Cutler-Hammer

Molded Case Circuit Breakers 15-100 Amperes

March 1999

25

Series CT G-Frame ■

■

■

■

All two- and three-pole circuit breakers are of the common trip type. On all 3-phase Delta (240V) Grounded B phase applications, refer to Cutler-Hammer.

Interrupting Capacity Ratings

Single-pole circuit breakers, 15 and 20 amperes. Switching duty rated (SWD) for fluorescent lighting applications.

120

UL489 Interrupting Capacity Ratings Circuit Breaker Type

All G-frame circuit breakers are suitable for reverse feed use.

Number of Poles

GD

3

Circuit Breaker Type

Number of Poles

Interrupting Capacity (Symmetrical Amperes) (kA) Volts Ac (50/60 Hz) 240

–

277

65

480

–

125

22

250➀➁

–

10

Interrupting Capacity (Symmetrical Amperes) (kA) Volts Ac (50/60 Hz) 120

HACR rated.

Page Number

Volts Dc

Page Number

Volts Dc

240

277

480Y/277

125

26

125/250

GB

1 2, 3

65 –

– 65

– –

– –

14➂ –

– 14

27 27

GHB

1 2, 3

65 –

– 65

14 –

– 14

14➂ –

– 14

27 27

GC

1 2, 3

65 –

– 65

– –

– –

14➂ –

– 14

28 28

GHC

1 2, 3

65 –

– 65

14 –

– 14

14➂ –

– 14

28 28

Catalog Numbering System

Terminal Types

This information is presented only as an aid to understanding catalog numbers. It is not to be used to build catalog numbers for circuit breakers or trip units.

For line and load-side. Terminals are UL listed as suitable for wire type and size given below.

Circuit Breaker/Frame Catalog Number GD 3 100 Circuit Breaker Type

Number of Poles

Trip Amperes

Suffix

GD GB GHB GC GHC

1: 1 Pole 2: 2 Pole 3: 3 Pole

15 20 24 30 35 40 45 50 60 70 80 90 100

K: Molded Case Switch D: Ring Type Terminals C: Steel Collars V: 50°C J01: Fungus Proofed R01: Shock Tested F01: Freeze Tested

➀ Two poles of 3-pole circuit breaker. ➁ Time constant is 8 milliseconds minimum. ➂ 15 through 70A breakers only. ➃ Not UL listed sizes.

PG.74A.01.T.E

Circuit Breaker Amperes

Terminal Type Material

Screw Head Type

Wire Type

AWG Wire Range

Metric Wire➃ Range (mm2)

Standard 15-20 25-100

Clamp (Plated Steel) Slotted Cu/Al #14-10 Pressure (Aluminum Body) Slotted Cu/Al #10-1/0

2.5-4 4-50

Optional 15-50

Pressure (Steel Body)

Slotted Cu

–

–

Page 2

Time/Current Curves, Dimension Sheets, Application Data

26

Cutler-Hammer

Molded Case Circuit Breakers 15-100 Amperes

March 1999

Series CT G-Frame

Type GD Thermal-Magnetic Circuit Breakers with Non-Interchangeable Trip-Units Maximum Continuous Ampere Rating @ 40°C

480 Vac Maximum, 250 Vdc➀

Catalog Number (Includes binding head screws)

22 kAIC @ 480 Vac Catalog Number (Includes Line and Load Terminals)

3-Pole 15 20 25 30 35 40 45 50 60 70 80 90 100

Typical Series C G-Frame Circuit Breaker

GD3015 GD3020 GD3025 GD3030 GD3035 GD3040 GD3045 GD3050 GD3060 GD3070 GD3080 GD3090 GD3100

GD3015D GD3020D GD3025D GD3030D GD3035D GD3040D GD3045D GD3050D GD3060D GD3070D GD3080D GD3090D GD3100D

Instruction Leaflet/FRED Number 29C102

Molded Case Switches Maximum Continuous Ampere Rating @ 40°C

480 Vac Maximum, 250 Vdc Catalog Number (Includes Line and Load Terminals)

3-Pole 60 100

GD3060K GD3100K

Instruction Leaflet/FRED Number 29C102

PG.74A.01.T.E

Page 3

Time/Current Curves, Dimension Sheets, Application Data

Cutler-Hammer March 1999

Molded Case Circuit Breakers 15-100 Amperes

27

Series CT G-Frame

Types GB and GHB Bolt-On Panelboard Circuit Breakers Type GB Thermal-Magnetic Circuit Breakers with Non-Interchangeable Trip Units Continuous Ampere Rating @ 40°C

120 Vac Maximum, 125 Vdc Maximum➀

240 Vac Maximum, 125/250 Vdc Maximum

240 Vac Maximum, 125/250 Vdc Maximum➁

1-Pole

2-Pole

3-Pole

Catalog Number

15 20 25 30 35 40 45 50 60 70 80 90 100

Typical GB

These breakers meet the requirements of Federal Specification W-C-375b as follows: Types GB, GHB, 120 and 240 Volts: 1 Pole: Class 11a. 2, 3 Poles: Classes 10b, 11b, 12b, 14b, 15b

GB1015➂ GB1020➂ GB1025 GB1030 GB1035 GB1040 GB1045 GB1050 GB1060 GB1070 GB1080 GB1090 GB1100

GB2015➂ GB2020➂ GB2025 GB2030 GB2035 GB2040 GB2045 GB2050 GB2060 GB2070 GB2080 GB2090 GB2100

GB3015➂ GB3020➂ GB3025 GB3030 GB3035 GB3040 GB3045 GB3050 GB3060 GB3070 GB3080 GB3090 GB3100

Type GHB Thermal-Magnetic Circuit Breakers with Non-Interchangeable Trip Units➃ Continuous Ampere Rating @ 40°C

Type GHB, 277 and 480Y/277 Volts: 1 Pole: Classes 12c, 13a 2, 3 Poles: Class 13b

277/480 Vac Maximum, 125 Vdc Maximum➀

277/480 Vac Maximum, 125/250 Vdc Maximum

277/480 Vac Maximum, 125/250 Vdc Maximum➁

1-Pole

2-Pole

3-Pole

Catalog Number

15 20 25 30 35 40 45 50 60 70 80 90 100

GHB1015➂ GHB1020➂ GHB1025 GHB1030 GHB1035 GHB1040 GHB1045 GHB1050 GHB1060 GHB1070 GHB1080 GHB1090 GHB1100

GHB2015➂ GHB2020➂ GHB2025 GHB2030 GHB2035 GHB2040 GHB2045 GHB2050 GHB2060 GHB2070 GHB2080 GHB2090 GHB2100

GHB3015➂ GHB3020➂ GHB3025 GHB3030 GHB3035 GHB3040 GHB3045 GHB3050 GHB3060 GHB3070 GHB3080 GHB3090 GHB3100

Instruction Leaflet/FRED Number 15547

Type GHBGFEP Bolt-on Panelboard 30mA Industrial Ground Fault Circuit Protectors 15-60 Amperes, 277 Volt, 50/60 Hz These circuit breakers meet the requirements of UL489 and UL1053. Operational voltage 240V to 305V. Interrupting Capacity Ratings Circuit Breaker Type

GHBGFEP

Number of Poles

2

Interrupting Capacity (Symmetrical Amperes) 277 Volts Ac (50/60 Hz)

14,000

Type GHBGFEP Bolt-on Panelboard 30mA Industrial Ground Fault Circuit Protectors with Non-Interchangeable Trip Units Continuous Ampere Rating @ 40°C

15 20 30 40 50 60

One Phase (Requires 2 Poles) 277V, 30mA Catalog Number

GHBGFEP1015 GHBGFEP1020 GHBGFEP1030 GHBGFEP1040 GHBGFEP1050 GHBGFEP1060

Instruction Leaflet/FRED Number 29C193

Single Phase (Requires 2 Poles)

PG.74A.01.T.E

➀ 15 through 70 ampere circuit breakers only. ➁ Use (2) outside poles. ➂ Uses .190-32 screw type clamp terminals. ➃ 480Y/277V, circuit breakers (Type GHB) not suitable for 3-phase Delta (480V).

Page 4

Time/Current Curves, Dimension Sheets, Application Data

28

Cutler-Hammer

Molded Case Circuit Breakers 15-100 Amperes

March 1999

Series CT G-Frame

Types GC and GHC Circuit Breakers

Type GC Thermal-Magnetic Circuit Breakers with Non-Interchangeable Trip Units

15-100 Amperes, 120, 240, 277, 480Y/277V, 50/60 Hz, 125, 125/250 Vdc, 1, 2, and 3 Poles

Continuous Ampere Rating @ 40°C

240 Vac Maximum, 125 Vdc Maximum➀

240 Vac Maximum, 125/250 Vdc Maximum

240 Vac Maximum, 125/250 Vdc Maximum➁

1-Pole

2-Pole

3-Pole

Catalog Number

15 20 25 30 35 40 45 50 60 70 80 90 100 Typical GC

These breakers meet the requirements of Federal Specification W-C-37b as follows:

GC1015➂ GC1020➂ GC1025 GC1030 GC1035 GC1040 GC1045 GC1050 GC1060 GC1070 GC1080 GC1090 GC1100

GC2015➂ GC2020➂ GC2025 GC2030 GC2035 GC2040 GC2045 GC2050 GC2060 GC2070 GC2080 GC2090 GC2100

GC3015➂ GC3020➂ GC3025 GC3030 GC3035 GC3040 GC3045 GC3050 GC3060 GC3070 GC3080 GC3090 GC3100

Type GHC Thermal-Magnetic Circuit Breakers with Non-Interchangeable Trip Units Continuous Ampere Rating @ 40°C

277 Vac Maximum, 125 Vdc Maximum➀

480Y/277 Vac Maximum, 125/250 Vdc Maximum

480Y/277 Vac Maximum, 125/250 Vdc Maximum➁

1-Pole

2-Pole

3-Pole

Catalog Number

Types GC, 120 and 240 Volts: 1 Pole: Class 11a 2, 3 Poles: Classes 10b, 11b, 12b, 14b, 15b

15 20 25 30 35 40 45 50 60 70 80 90 100

Type GHC, 277 and 480Y/277 Volts: 1 Pole: Classes 12c, 13a 2, 3 Poles: Class 13b

GHC1015➂ GHC1020➂ GHC1025 GHC1030 GHC1035 GHC1040 GHC1045 GHC1050 GHC1060 GHC1070 GHC1080 GHC1090 GHC1100

GHC2015➂ GHC2020➂ GHC2025 GHC2030 GHC2035 GHC2040 GHC2045 GHC2050 GHC2060 GHC2070 GHC2080 GHC2090 GHC2100

GHC3015➂ GHC3020➂ GHC3025 GHC3030 GHC3035 GHC3040 GHC3045 GHC3050 GHC3060 GHC3070 GHC3080 GHC3090 GHC3100

Instruction Leaflet/FRED Number 15548

Type GHCGFEP Cable In/Cable Out 30mA Industrial Ground Fault Circuit Protectors 15-60 Amperes, 277 Volt, 50/60 Hz These circuit breakers meet the requirements of UL489 and UL1053. Operational voltage 240V to 305V. Interrupting Capacity Ratings Circuit Breaker Type

GHCGFEP

Number of Poles

2

Interrupting Capacity (Symmetrical Amperes) 277 Volts Ac (50/60 Hz)

14,000

Type GHBGFEP Bolt-on Panelboard 30mA Industrial Ground Fault Circuit Protectors with Non-Interchangeable Trip Units Continuous Ampere Rating @ 40°C

15 20 30 40 50 60

One Phase (Requires 2 Poles) 277V, 30mA Catalog Number

GHBGFEP1015 GHBGFEP1020 GHBGFEP1030 GHBGFEP1040 GHBGFEP1050 GHBGFEP1060

Instruction Leaflet/FRED Number 29C193

Single Phase Requires 2 Poles)

➀ 15 through 70 ampere circuit breakers only. ➁ Use (2) outside poles. ➂ Uses .190-32 screw type clamp terminals.

PG.74A.01.T.E

Page 5

Time/Current Curves, Dimension Sheets, Application Data

Cutler-Hammer

Molded Case Circuit Breakers 15-100 Amperes

March 1999

Series CT G-Frame

Special Purpose Breakers marked “Special purpose breaker not for general use.” To order this special breaker, use the catalog number below.

These are Types GC and GHC circuit breakers with binding head screwtype terminals on line and load side. These circuit breakers with screwtype terminals (.190-32) will be

Type GC Thermal-Magnetic Circuit Breakers with Non-Interchangeable Trip Units Continuous Ampere Rating @ 40°C

120 Vac Maximum, 125 Vdc Maximum

240 Vac Maximum, 125/250 Vdc Maximum

240 Vac Maximum, 125/250 Vdc Maximum➀

1-Pole

2-Pole

3-Pole

Catalog Number

25 30 35 40 45 50 55 60

GC1025D GC1030D GC1035D GC1040D GC1045D GC1050D GC1055D GC1060D

GC2025D GC2030D GC2035D GC2040D GC2045D GC2050D GC2055D GC2060D

GC3025D GC3030D GC3035D GC3040D GC3045D GC3050D GC3055D GC3060D

Type GHC Thermal-Magnetic Circuit Breakers with Non-Interchangeable Trip Units Continuous Ampere Rating @ 40°C

277 Vac Maximum, 125 Vdc Maximum

480Y/277 Vac Maximum, 125/250 Vdc Maximum

480Y/277 Vac Maximum, 125/250 Vdc Maximum➀

1-Pole

2-Pole

3-Pole

Catalog Number

25 30 35 40 45 50 55 60

GHC1025D GHC1030D GHC1035D GHC1040D GHC1045D GHC1050D GHC1055D GHC1060D

Instruction Leaflet/FRED Number 15548

➀ Use (2) outside poles.

PG.74A.01.T.E

GHC2025D GHC2030D GHC2035D GHC2040D GHC2045D GHC2050D GHC2055D GHC2060D

GHC3025D GHC3030D GHC3035D GHC3040D GHC3045D GHC3050D GHC3055D GHC3060D

29

Page 6

30

Cutler-Hammer

Molded Case Circuit Breakers 15-100 Amperes

March 1999

Series CT G-Frame

Dimensions/Weights Dimensions, Inches (mm) Number of Poles

Width

Height

Depth

1

1.0 (25.33)

4.88 (123.95)

2.81 (71.41)

2

2.0 (50.78)

4.88 (123.95)

2.81 (71.41)

3

3.0 (76)

4.88 (123.95)

2.81 (71.41)

Approximate Shipping Weight, Lbs. (kg) Breaker Type

Number of Poles 1

2

3

GD

1.0 (.454)

1.5 (.680)

2.25 (1.021)

GHBGFEP

–

1.2 (.545)

–

GHCGFEP

–

1.1 (.499)

–

GB/GHC

Carton Quantity

GC/GHC

24

12

8

16 (7.264)

16 (7.264)

16 (7.264)

Carton Quantity

24

12

8

18 (8.172)

18 (8.172)

18 (8.172)

Accessories Internal Alarm Switch . . . . . . . . . . . . . . . . 139 Auxiliary Switch. . . . . . . . . . . . . . 142 Shunt Trip . . . . . . . . . . . . . . . . . . 147 Undervoltage Release Mechanism . . . . . . . . . . . . . . . . 153

External Base Mounting Hardware . . . . . . 163 Base Mounting Plate . . . . . . . . . . 167 DIN Rail Adapter . . . . . . . . . . . . . 167 Key Operated Attachment. . . . . . 167 Lock Dog (non-padlockable) . . . . 168 Padlockable Handle . . . . . . . . . . . 168 Handle Mechanisms . . . . . . . . . . 180

PG.74A.01.T.E