The text of a manual · part 1 of 15
Control Relays & Timers, pages 1 to 10
Pages 1 to 10 of 142
The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Cutler-Hammer D26MB and Eaton D26MB
Page 1
Control Relays & Timers
49-1
Control Relays & Timers
July 2008
Contents Description
Page
Relay Product Family Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . XR Series Terminal Block Relays Standard Terminal Block Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OptoCoupler Terminal Block Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . High Current Terminal Block Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EZ Intelligent Relays Product Family Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EZ 500/700/800/EZD Intelligent Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . EZD Controller I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EZ/EZD Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EZ/EZD Communication Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Purpose Plug-In Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D2PF Series, Full Featured . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D2PR Series, Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D3PR/D3PF Series, Standard and Full Featured . . . . . . . . . . . . . . . . . . . D4 Series, Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D5PR/D5PF Series, Standard and Full Featured . . . . . . . . . . . . . . . . . . . D7PR Series, Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D7PF Series, Full Featured . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D8 Series, Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D9 Series, Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Purpose Relays, Type AA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Machine Tool Relays D15 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BF/BFD Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AR/ARD Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D26 Series, Type M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Timing Relays TMR5 Series, Non-programmable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TR Series, Programmable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D80 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Phase Monitoring Relays D65 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current Monitoring Relays D65C Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Voltage Monitoring Relays D65V Series. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VSR Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alternating Relays D85 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ground Fault Relays and Monitors D64R Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D64L Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
49-2
Control Relays
CA08102001E
For more information visit: www.eaton.com
49-4 49-9 49-11 49-13 49-14 49-15 49-22 49-23 49-25 49-33 49-35 49-39 49-43 49-49 49-52 49-56 49-62 49-67 49-71 49-73 49-75 49-79 49-83 49-87 49-93 49-98 49-103 49-104 49-115 49-122 49-128 49-130 49-135 49-142
49
Page 2
Control Relays & Timers Relay Product Family Overview
49-2
July 2008
Control Relays & Timers Comparison Table 49-1. Selection Guide by Catalog Number Prefix Relays
Type
Mounting
Contacts
Maximum Amperage (AC)
UL
CSA
CE
Page Number
9575H3
General Purpose
Panel Mount
Fixed
40A
X
X
X
49-73
AR/ARD
Machine Tool
Panel Mount
Convertible
10A
X
X
BF/BFD
Machine Tool
Panel Mount
Fixed
10A
X
D2PF
Full Featured Plug-In
DIN Rail/Panel Mount
Fixed
10A
X
D2PR
Standard Plug-In
DIN Rail/Panel Mount/Flange
Fixed
5A
X
49-83
X X X
49-79
X
X
49-35
X
X
49-39
D3PF
Full Featured Plug-In
DIN Rail/Panel Mount
Fixed
12A
X
X
X
49-43
D3PR
Standard Plug-In
DIN Rail/Panel Mount
Fixed
12A
X
X
X
49-43
D4PR
Standard Plug-In
DIN Rail/Panel Mount
Fixed
10A
X
X
X
49-49
D5PF
Full Featured Plug-In
DIN Rail/Panel Mount
Fixed
12A
X
X
X
X
49-52
D5PR
Standard Plug-In
DIN Rail/Panel Mount/PC Board
Fixed
15A
X
X
X
49-52
D7PF
Full Featured Plug-In
DIN Rail/Panel Mount
Fixed
20A
X
X
X
X
49-62
D7PR
Standard Plug-In
DIN Rail/Panel Mount/Flange
Fixed
15A
X
X
X
49-56
D8PR
Standard Plug-In
DIN Rail/Panel Mount/Flange
Fixed
30A
X
X
X
49-67
D9PR
Standard Plug-In
Panel Mounting
Fixed
25A
X
X
D15
Machine Tool
DIN Rail/Panel Mount
Fixed
10A
X
X
D26
Machine Tool
Panel or Channel Mount
Convertible
10A
X
X
D64
Ground Fault Relays
Panel Mount
Fixed
N/A
X
X
D65
Phase Monitoring
DIN Rail/Panel Mount
Fixed
10A
X
D65C
Current Monitoring
DIN Rail/Panel Mount
Fixed
10A
D65V
Voltage Monitoring
DIN Rail/Panel Mount
Fixed
10A
D80
Timer (Pneumatic)
Panel Mount/Enclosure
Fixed
N/A
D85
Alternating Relays
DIN Rail/Panel Mount
Fixed
10A
X
EZ
Intelligent Relay
DIN Rail
Fixed
8A
X
TMR5
Timing Relay (Non-programmable)
DIN Rail/Panel Mount
Fixed
10A
X
TR
Timing Relay (Programmable)
DIN Rail/Panel Mount
Fixed
10A
VSR
Voltage Sensing
Panel Mount/Enclosure
Fixed
2A
XR
Terminal Block Relay
DIN Rail
Fixed
6A, 10A
49-71 X
49-75 49-87
X
49-135
X
X
49-104
X
X
X
49-115
X
X
X
49-122
X
X
X X X X
49-103 X
49-130
X
49-14
X
49-94
X
49-98 49-128
X
X
49-4
49
For more information visit: www.eaton.com
CA08102001E
Page 3
Control Relays & Timers Relay Product Family Overview
49-3
July 2008
Table 49-2. Selection Guide by Relay Type Type
Relays
Mounting
Contacts
Maximum Amperage (AC)
UL
CSA
CE
Page Number 49-130
Alternating Relays
D85
DIN Rail/Panel Mount
Fixed
10A
X
X
X
Current Monitoring
D65C
DIN Rail/Panel Mount
Fixed
10A
X
X
X
49-115
Full Featured Plug-In
D2PF
DIN Rail/Panel Mount
Fixed
10A
X
X
X
X
49-35
Full Featured Plug-In
D3PF
DIN Rail/Panel Mount
Fixed
12A
X
X
X
X
49-43
Full Featured Plug-In
D5PF
DIN Rail/Panel Mount
Fixed
12A
X
X
X
X
49-52
Full Featured Plug-In
D7PF
DIN Rail/Panel Mount
Fixed
20A
X
X
X
X
49-62
General Purpose
9575H3
Panel Mount
Fixed
40A
X
X
X
49-73
X
X
49-135
X
X
Ground Fault Relays
D64
Panel Mount
Fixed
N/A
Intelligent Relay
EZ
DIN Rail
Fixed
8A
Machine Tool
AR/ARD
Panel Mount
Convertible
10A
X X X X
X
49-14 49-83
Machine Tool
BF/BFD
Panel Mount
Fixed
10A
Machine Tool
D15
DIN Rail/Panel Mount
Fixed
10A
X
X
X
Machine Tool
D26
Panel or Channel Mount
Convertible
10A
X
X
X
49-87
Phase Monitoring
D65
DIN Rail/Panel Mount
Fixed
10A
X
49-104 49-39
X
X
X
49-79 49-75
Standard Plug-In
D2PR
DIN Rail/Panel Mount/Flange
Fixed
5A
X
X
X
Standard Plug-In
D3PR
DIN Rail/Panel Mount
Fixed
12A
X
X
X
49-43
Standard Plug-In
D4PR
DIN Rail/Panel Mount
Fixed
10A
X
X
X
49-49
Standard Plug-In
D5PR
DIN Rail/Panel Mount/PC Board
Fixed
13A
X
X
X
49-52
Standard Plug-In
D7PR
DIN Rail/Panel Mount/Flange
Fixed
15A
X
X
X
49-56
X
49-67
Standard Plug-In
D8PR
DIN Rail/Panel Mount/Flange
Fixed
30A
X
X
Standard Plug-In
D9PR
Panel Mounting
Fixed
25A
X
X
Terminal Block Relay
XR
DIN Rail
Fixed
6A, 10A
X
Timer (Pneumatic)
D80
Panel Mount/Enclosure
Fixed
N/A
Timing Relay (Non-programmable)
TMR5
DIN Rail/Panel Mount
Fixed
10A
Timing Relay (Programmable)
TR
DIN Rail/Panel Mount
Fixed
10A
Voltage Monitoring
D65V
DIN Rail/Panel Mount
Fixed
10A
Voltage Sensing
VSR
Panel Mount/Enclosure
Fixed
2A
X X
X
X X
X
49-71 X
X
49-4 49-103
X X
49-94 49-98
X
49-122 49-128
49
CA08102001E
For more information visit: www.eaton.com
Page 4
49-4
Control Relays & Timers XR Series Terminal Block Relays July 2008
Standard Terminal Block Relays
Contents Description
Features Page
XR Series Terminal Block Relays Standard Terminal Block Relays . . . . . . . . . . . 49-4 OptoCoupler Terminal Block Relays . . . . . . . . . . . 49-9 High Current Terminal Block Relays . . . . . . . . . . . 49-11 Accessories . . . . . . . . . . . . . 49-13
■ Gold plated contacts available ■ Equipped with a robust, miniature
■ Pluggable relay allows for field replacement ■ Functional plug-in bridges ■ Choice of screw connections or spring-cage connection ■ LED status indication ■ DIN Rail Mount ■ Only 6.2 mm wide for single pole versions, 14 mm wide for double pole ■ All common input voltages between 12V DC to 120V AC relay: ❑ IP67 protection ❑ Environmentally friendly, cadmium-free contact material ❑ Easy, cost-effective installation and replacement using the engagement lever
Standards and Certifications ■ cULus Listed ■
Product Selection Table 49-3. Standard Terminal Block Relays Product Selection Gold Plated Contacts
Rated Current
Supply Voltage
Standard Pack
Catalog Number XRU1D12
Price U.S. $
1PDT Screw Connection
Standard Terminal Block Relay
No
6A
12V DC
10
No
6A
120V AC/110V DC
10
XRU1D120U
Yes
6A
120V AC/110V DC
10
XRU1D120UG
No
6A
24V DC
10
XRU1D24
No
6A
24V AC/DC
10
XRU1D24U
Yes
6A
24V AC/DC
10
XRU1D24UG
No
6A
230V AC/220V DC
10
XRU1D230U
1PDT Spring Cage Connection
Product Description
49
The new XR Series Terminal Block Relays are ideal for applications that require a high switching capacity and long electrical service life. The relays are plug-in interfaces that connect to basic terminal blocks. The XR Series utilizes screw or spring-cage technology, as well as offers quick system wiring, superior safety features, clear labeling and a high level of modularity.
Application Description
No
6A
12V DC
10
XRP1D12
No
6A
120V AC/110V DC
10
XRP1D120U
No
6A
24V DC
10
XRP1D24
No
6A
24V AC/DC
10
XRP1D24U
No
6A
230V AC/220V DC
10
XRP1D230U
DPDT Screw Connection No
6A
12V DC
10
XRU2D12
No
6A
120V AC/110V DC
10
XRU2D120U
No
6A
24V DC
10
XRU2D24
No
6A
24V AC/DC
10
XRU2D24U
No
6A
230V AC/220V DC
10
XRU2D230U
Table 49-4. Standard Replacement Relays Rated Current
Supply Voltage
Standard Pack
Catalog Number
No
6A
12V DC
10
XRR1D12
No
6A
120V AC/110V DC
10
XRR1D120U
Yes
6A
120V AC/110V DC
10
XRR1D120UG
■ Electrical isolation between the
No
6A
24V DC
10
XRR1D24 input and output circuits ■ Independence of the type of switching current (AC and DC) ■ High short-term overload resistance in the event of short circuits or voltage peaks ■ Low switching losses ■ Ease of operation
Yes
6A
24V DC
10
XRR1D24G
No
6A
230V AC/220V DC
10
XRR1D230U
No
6A
12V DC
10
XRR2D12
No
6A
120V AC/110V DC
10
XRR2D120U
No
6A
24V DC
10
XRR2D24
No
6A
230V AC/220V DC
10
XRR2D230U
Used in automation systems, electromechanical relays guarantee a safe connection between process I/O and electronic controls. The following functions are covered by relay coupling elements:
Gold Plated Contacts
Price U.S. $
1PDT
DPDT
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1 For more information visit: www.eaton.com
CA08102001E
Page 5
Control Relays & Timers XR Series Terminal Block Relays
49-5
July 2008
Standard Terminal Block Relays
Technical Data and Specifications Table 49-5. Standard 1PDT Screw Connection Terminal Block Relays Technical Data
Table 49-6. Standard 1PDT Screw Connection Terminal Block Relays with Gold Contacts Technical Data
Catalog Number
XRU1D12 XRU1D24 XRU1D24U XRU1D120U
Catalog Number
XRU1D24UG
XRU1D120UG
Replacement Relay
XRR1D12 XRR1D24 XRR1D24
XRR1D120U
Replacement Relay
XRR1D24G
XRR1D120UG
Input Voltage
12V DC
120V AC/ 110V DC
Input Voltage
24V AC/DC
120V AC/110V DC
24V DC
24V AC/DC
Connection Data
Connection Data
26 – 14 (0.14 – 2.5)
Rigid Solid AWG (mm2)
26 – 14 (0.14 – 2.5)
Rigid Solid AWG (mm2)
26 – 14 (0.14 – 2.5)
Flexible Stranded AWG (mm2)
26 – 14 (0.14 – 2.5)
Flexible Stranded AWG (mm2)
Input Data for 1PDT Screw Connection Versions with Gold Contacts
Input Data for 1PDT Screw Connection Versions Input Voltage
12V DC
24V DC
24V AC/DC
120V AC/ 110V DC
Permissible Range See Page 49-8
See Figure 49-5
See Figure 49-7
See See Figure 49-8 Figure 49-6
Typical Input Current
15.3 mA
9 mA
11 mA (24V AC)/ 8.5 mA (24V DC)
3.5 mA (120V AC)/ 3 mA (110V DC)
Typical Response Time 5 mS
5 mS
6 mS
6 mS
Typical Release Time
8 mS
15 mS
15 mS
Input Protection
8 mS
Polarity Protection Diode, FreeWheeling Diode
Bridge Rectifier
Output Data Contact Type
1PDT
Contact Material
AgSnO
Max. Switching Voltage
250V AC/DC
Input Voltage
24V AC/DC
120V AC/110V DC
Permissible Range See Page 49-8
See Figure 49-8
See Figure 49-6
Typical Input Current
11 mA (24V AC)/ 8.5 mA (24V DC)
3.5 mA (120V AC)/ 3 mA (110V DC)
Typical Response Time
6 mS
6 mS
Typical Release Time
15 mS
15 mS
Input Protection
Bridge Rectifier
Output Data Contact Type Contact Material
1PDT AgSnO, Gold Plated
Max. Switching Voltage
30V AC/36V DC (250V AC/DC)
Min. Switching Voltage
100 mV (12V AC/DC)
Limiting Continuous Current
50 mA (6A)
Min. Switching Current
1 mA (10 mA)
Min. Switching Power
100 (120 mW)
Min. Switching Voltage
12V AC/DC
Miscellaneous Data
Limiting Continuous Current
6A
Test Voltage I/O
4 kV, 50 Hz, 1 min
50 Hz
Ambient Temp Range
-4° to 140°F (-20° to 60°C)
-40° to 131°F (-20° to 55°C)
Min. Switching Current
10 mA
Min. Switching Power
120 mW
Miscellaneous Data Test Voltage I/O
4 kV, 50 Hz, 1 min
4 kV
50 Hz
Rated Operating Mode
100% Operating Factor
Inflammability Class
V0, in Accordance with UL 94
Mechanical Service Life
2 x 107 Cycles
Ambient Temp Range
-4° to 140°F (-20° to 60°C)
The separating plate, XRAPLCESK, should be installed for voltages
Rated Operating Mode
100% Operating Factor
Inflammability Class
V0, in Accordance with UL 94
Mechanical Service Life
2 x 107 Cycles greater than 250V (L1, L2, L3) between identical terminal points of adjacent modules. Potential bridging is then possible with the XRAFBST bridge system. If the maximum values are exceeded, the gold layer is destroyed and the values in parentheses apply.
The separating plate, XRAPLCESK, should be installed for voltages greater than 250V (L1, L2, L3) between identical terminal points of adjacent modules. Potential bridging is then possible with the XRAFBST bridge system.
CA08102001E
For more information visit: www.eaton.com
49
Page 6
49-6
Control Relays & Timers XR Series Terminal Block Relays July 2008
Standard Terminal Block Relays Table 49-7. Standard 1PDT Spring Cage Terminal Block Relays Technical Data
Table 49-8. Standard DPDT Screw Connection Terminal Block Relays Technical Data
Catalog Number
XRP1D12 XRP1D24 XRP1D24U
XRP1D120U
Catalog Number
XRU2D12 XRU2D24 XRU2D24U
XRU2D120U
Replacement Relay
XRR1D12 XRR1D24 XRR1D24
XRR1D120U
Replacement Relay
XRR2D12 XRR2D24 XRR2D24
XRR2D120U
Input Voltage
12V DC
120V AC/ 110V DC
Input Voltage
12V DC
120V AC/ 110V DC
24V DC
24V AC/DC
Connection Data
24V AC/DC
Connection Data
Rigid Solid AWG (mm2)
26 – 14 (0.14 – 2.5)
Rigid Solid AWG (mm2)
26 – 14 (0.14 – 2.5)
Flexible Stranded AWG (mm2)
26 – 14 (0.14 – 2.5)
Flexible Stranded AWG (mm2)
26 – 14 (0.14 – 2.5)
Input Data for 1PDT Spring Cage Versions
Input Data
Input Voltage
12V DC
24V DC
24V AC/DC
Permissible Range See Page 49-8
See Figure 49-5
See Figure 49-7
Typical Input Current
15.3 mA
9 mA
120V AC/ 110V DC
Input Voltage
12V DC
24V DC
24V AC/DC
See See Figure 49-8 Figure 49-6
Permissible Range See Page 49-8
See Figure 49-9
See Figure 49-11
See See Figure 49-12 Figure 49-10
11 mA (24V AC)/ 8.5 mA (24V DC)
3.5 mA (120V AC)/ 3 mA (110V DC)
Typical Input Current
33 mA
18 mA
17.5 mA
4.5 mA (120V AC) 4.2 mA (110V DC)
Typical Response Time
8 mS
8 mS
8 mS
7 mS
Typical Response Time 5 mS
5 mS
6 mS
6 mS
Typical Release Time
8 mS
15 mS
15 mS
Input Protection
8 mS
Polarity Protection Diode, FreeWheeling Diode
Bridge Rectifier
Typical Release Time Input Protection
Output Data
Bridge Rectifier
1PDT
Output Data:
Contact Material
AgSnO
Contact Type
Max. Switching Voltage
250V AC/DC
Contact Material
AgNi 250V AC/DC
Min. Switching Voltage
12V AC/DC
Max. Switching Voltage
Limiting Continuous Current
6A
Min. Switching Voltage
5V
Min. Switching Current
10 mA
6A
Min. Switching Power
120 mW
Limiting Continuous Current Max. Inrush Current
15A (300 mS)
Test Voltage I/O Ambient Temp Range
4 kV, 50 Hz, 1 min
4 kV
50 Hz
-4° to 140°F (-20° to 60°C)
-4° to 131°F (-20° to 55°C)
Rated Operating Mode
100% Operating Factor
Inflammability Class
V0, in Accordance with UL 94
Mechanical Service Life
2 x 107 Cycles
The separating plate, XRAPLCESK, should be installed for voltages greater than 250V (L1, L2, L3) between identical terminal points of adjacent modules. Potential bridging is then possible with the XRAFBST bridge system.
120V AC / 110V DC
10 mS Polarity Protection Diode, FreeWheeling Diode
Contact Type
Miscellaneous Data
49
24V DC
2PDT
Single Contact, 2PDT
Min. Switching Current
10 mA
Min. Switching Power
50 mW
General Data Test Voltage I/O
4 kV, 50 Hz, 1 min /2.5 kV, 50 Hz, 1 Min. (Between the PDTs)
Ambient Temp Range
-4° to 140°F (-20° to 60°C)
Rated Operating Mode
100% Operating Factor
Inflammability Class
V0, in Accordance with UL 94
Mechanical Service Life
3 x 107 cycles
For more information visit: www.eaton.com
CA08102001E
Page 7
Control Relays & Timers XR Series Terminal Block Relays
49-7
July 2008
Standard Terminal Block Relays
Dimensions
Schematics
3.70 (94)
A2
11
A1
14
12
3.15 (80)
0.24 (6.2)
Figure 49-1. Standard 1PDT Terminal Block Relays, Approximate Dimensions in Inches (mm)
Figure 49-3. Schematics for 1PDT Terminal Block Relays
21 3.70 (94) 24
22 A2 11 A1 14 3.15 (80) 12 0.55 (14)
Figure 49-2. Standard DPDT Terminal Block Relays, Approximate Dimensions in Inches (mm)
CA08102001E
Figure 49-4. Schematic for DPDT Terminal Block Relays
For more information visit: www.eaton.com
49
Page 8
49-8
Control Relays & Timers XR Series Terminal Block Relays July 2008
Standard Terminal Block Relays
Permissible Range Diagrams 1PDT Notes: 1.4
1.4
A
1.3
1.3
1.2
1.2
U 1.1 UN 1.0
UN = 12V DC
U 1.1 UN 1.0
0.9
0.9
0.8
0.8
B 0.7 20 25 30 35 40 45 50 55 60 65 TN [°C]
Figure 49-5. Operating Range Voltage for 12V DC 1PDT Relay Module 1.4
Figure 49-7. Operating Range Voltage for 24V DC 1PDT Relay Module
A
1.3
1.2
1.2
U 1.1 UN 1.0
U 1.1 UN 1.0
0.9
UN = 24V DC
B 0.7 20 25 30 35 40 45 50 55 60 65 TN [°C]
1.4
A
1.3
A
UN = 110V DC/120V AC
0.8
General Conditions, Direct alignment in the block, all devices 100% operating factor, horizontal or vertical mounting. Curve A, Maximum permissible continuous operating voltage Umax with limiting continuous current on the contact side (see respective technical data). Curve B, Minimum permissible relay operate voltage Uop after pre-excitation (see respective technical data). Pre-excitation: Relay has been operated in a thermally steady state at the ambient temperature TU with nominal voltage UN and limiting continuous current on the contact side (see respective technical data) (warm coil). After being switched off for a short time, the relay must reliably pick up again at Uop.
UN = 24V DC/24V AC
0.9 0.8
B 0.7 20 25 30 35 40 45 50 55 60 65 TN [°C]
B 0.7 20 25 30 35 40 45 50 55 60 65 TN [°C]
Figure 49-6. Operating Range Voltage for 120V AC/110V DC 1PDT Relay Module
Figure 49-8. Operating Range Voltage for 24V AC/DC 1PDT Relay Module
DPDT 1.4
1.4
A
1.3
49
1.2
1.2
U 1.1 UN 1.0
U 1.1 UN 1.0
UN = 12V DC
0.9
0.9
0.8
0.8
B 0.7 20 25 30 35 40 45 50 55 60 65 TN [°C]
Figure 49-9. Operating Range Voltage for 12V DC DPDT Relay Module 1.4
A
1.3
B 0.7 20 25 30 35 40 45 50 55 60 65 TN [°C]
Figure 49-11. Operating Range Voltage for 24V DC DPDT Relay Module 1.4
A
1.2 UN = 120V AC UN = 110V DC
0.9 0.8
UN = 24V DC
1.3
1.2 U 1.1 UN 1.0
A
1.3
U 1.1 UN 1.0
UN = 24V DC/24V AC
0.9 B
0.8
B
0.7 20 25 30 35 40 45 50 55 60 65 TN [°C]
0.7 20 25 30 35 40 45 50 55 60 65 TN [°C]
Figure 49-10. Operating Range Voltage for 120V AC/110V DC DPDT Relay Module
Figure 49-12. Operating Range Voltage for 24V AC/DC DPDT Relay Module For more information visit: www.eaton.com
CA08102001E
Page 9
Control Relays & Timers XR Series Terminal Block Relays
49-9
July 2008
OptoCoupler Terminal Block Relays
Features
■ Wear-resistant and bounce-free
■ Pluggable relay allows for field
■ Insensitive to shock and vibration switching replacement
■ Integrated protection circuit
■ Functional plug-in bridges
■ Zero voltage switch at AC output
■ LED status indication ■ DIN Rail Mount
Standards and Certifications
■ Only 6.2 mm wide ■ Switching capacity up to 24V DC/3A
■ cULus Listed
■ IP67-protected optical electronics
■
Product Selection OptoCoupler Terminal Block Relay
Table 49-9. OptoCoupler Terminal Block Relays Product Selection Rated Current
Supply Voltage
Standard Pack
Catalog Number
2A
Product Description
2A
120V AC/110V DC
10
XRU1S120U
24V DC
10
XRU1S24
The new XR Series OptoCoupler Terminal Block Relays can be used in all applications and consist of a pluggable miniature OptoCoupler and a basic terminal block. The XR Series utilizes screw or spring-cage technology, as well as offers quick system wiring, superior safety features, clear labeling and a high level of modularity.
Table 49-10. OptoCoupler Replacement Relays Rated Current
Supply Voltage
Standard Pack
Catalog Number
2A
24V DC
18
XRR1S24
2A
120V AC/110V DC
10
XRR1S120U
Price U.S. $
Price U.S. $
Application Description The XR Series OptoCoupler relays can be used as an input or output interface. They provide the typical reliability of OptoCouplers and are especially suited for high operating frequencies.
49
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1 CA08102001E
For more information visit: www.eaton.com
Page 10
49-10
Control Relays & Timers XR Series Terminal Block Relays July 2008
OptoCoupler Terminal Block Relays
Technical Data and Specifications
Dimensions
Table 49-11. Pluggable Power OptoCoupler (Solid-State) Terminal Block Relays Technical Data Catalog Number
XRU1S24
XRU1S120U
Replacement Relay
XRR1S24
XRR1S120U
Input Voltage
24V DC
120V AC/110V DC
Connection Data Rigid Solid AWG (mm2)
26 – 14 (0.14 – 2.5)
Flexible Stranded AWG (mm2)
26 – 14 (0.14 – 2.5) 3.70 (94)
Input Data Input Voltage
24V DC
Permissible Range
0.8 – 1.2
120V AC/110V DC 0.8 – 1.1
Typical input current
9 mA
4 mA
Switching Level 1 signal (“H”)
≥ 0.8
≥ 0.8
Switching Level 0 signal (“L”)
≤ 0.4
≤ 0.25
Typical Switch-On Time
20 µS
6 mS
Typical Turn-Off Time
500 µS
10 mS
Input Protection
Polarity Protection Diode, FreeWheeling Diode
Bridge Rectifier
Max. Switching Voltage
33V DC
33V DC
Min. Switching Voltage
3V DC
3.15 (80)
0.24 (6.2)
Output Data
Limiting Continuous Current Max. Inrush Current
3V DC 3A (See Figure 49-13) 15A (10 mS)
Output Circuit
2-Conductor Floating
Output Protection
Polarity Protection, Surge Protection
Voltage Drop at Max. Limiting Continuous Current
Figure 49-14. Pluggable Power OptoCoupler (Solid-State) Terminal Block Relays, Approximate Dimensions in Inches (mm)
Schematic
≤ 200 mV
General Data Test Voltage I/O
2.5 kV, 50 Hz, 1 min
Ambient Temp Range Rated Operating Mode
100% Operating Factor
Inflammability Class
V0, in Accordance with UL 94 2 x 107 cycles
Mechanical Service Life
Load Current (A)
49
-4° to 140°F (-20° to 60°C)
A2
13+
A1
14
3 2 1 0 0
10 20 30 40 50 60
Ambient Temperature (°C)
Figure 49-15. Schematic for Pluggable Power OptoCoupler (SolidState) Terminal Block Relays
Figure 49-13. Derating Curve
For more information visit: www.eaton.com
CA08102001E