The text of a manual · part 8 of 15
Control Relays & Timers, pages 71 to 80
Pages 71 to 80 of 142
The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Cutler-Hammer D26MB and Eaton D26MB
Page 71
Control Relays & Timers General Purpose Plug-In Relays
49-71
July 2008
D9 Series, Standard
D9 Series
Features
Technical Data and Specifications
■ Ideal for 3-phase motor control applications
Table 49-88. Coil Resistance
■ No contact chattering for momen- tary voltage drops up to 50% of rated voltage ■ Push-to-test button is a standard feature to check contact operation ■ Mounting bracket is supplied with relay
Coil Voltage
Ohms mA
24V AC 120V AC 240V AC, - - 75 21.6 10.8
12V DC 24V DC 110V DC
72 288 6050
167 83 18
Standards and Certifications D9 Series Relay
File # E1491 File # LR701520
Table 49-89. Specifications D9PR NO Contacts Resistive Load (p.f. = 1)
NC Contacts Resistive Load (p.f. = 1)
Rated Load
220V AC 25A 30V DC 25A
220V AC 8A 30V DC 8A
Carry Current
25A
8A
Max. Operating Voltage
250V AC/125V DC
250V AC/125V DC
Max. Switching Current
25A
8A
Max. Switching Capacity
5500 VA 750W
1760 VA 240 W
Min. Permissible Load
100 mA @ 24V DC
100 mA @ 24V DC
Mechanical Life (min.)
1,000,000 operations
1,000,000 operations
Electrical Life @ All Contact Ratings (min.)
100,000 operations
100,000 operations
Maximum hp Ratings
1-1/2 hp (120V AC) 3 hp (240/265/277V AC) 3-Phase 3 hp (240/265/277V AC) 30,000 cycles 3-Phase 5 hp (240/265/277V AC) 30,000 cycles
1-1/2 hp (120V AC) 3 hp (240/265/277V AC) 3-Phase 3 hp (240/265/277V AC) 30,000 cycles 3-Phase 5 hp (240/265/277V AC) 30,000 cycles
Table 49-90. Coil Data Coil Voltage
Must Operate
24V DC/V AC, 12V DC, 110V DC
75% maximum
10% minimum
110%
120V AC
75V
18V
132V
240V AC
150V
36V
264V
CA08102001E
Must Release
For more information visit: www.eaton.com
Maximum Voltage
49
Page 72
49-72
Control Relays & Timers General Purpose Plug-In Relays July 2008
D9 Series, Standard
Catalog Number Structure
1.37 (35.0)
Table 49-91. D9 Series Catalog Numbering System
D9PR 8B A Family Type
Two M4 or 0.18 (4.5) Dia.
A = 120V AC B = 240V AC R1 = 12V DC T = 24V AC T1 = 24V DC
Contact Configuration 8B = 4PST-NO 9B = 3PST-NO/SPST-NC 10B = DPST-NO/DPST-NC
Two M4
0.95 (24.0)
Coil Voltage
D9PR
Mounting Holes
1.378 ± 0.004 (35.0 ± 1.0) 1.18 (30.0)
0.35 (9.0)
1.10 (28.0) 0.28 (7.0)
1.14 (29.0)
For deciphering Catalog Numbers. Do not use for ordering as not all combinations are readily available. 1.73 (44.0)
Product Selection Table 49-92. D9 Product Selection Catalog Number
Price U.S. $
0.17 (4.4)
Figure 49-111. Mounting Bracket, Approximate Dimensions in Inches (mm)
Terminal Arrangements
4PST-NO Power Relay Coil Voltage: 24V AC 120V AC 240V AC
D9PR8BT D9PR8BA D9PR8BB
24V DC
D9PR8BT1
3PST-NO/SPST-NC Power Relay 120V AC
14
13
24
23
34
33
D9PR9BA
DPST-NO/DPST-NC Power Relay Coil Voltage: 24V AC 120V AC
D9PR10BT D9PR10BA
24V DC
D9PR10BT1
44
43
A2
A1
Additional coil voltages available, consult Sales Office or Customer
D9PR8
Support Center.
49
Dimensions Screw Terminal Brackets
14
13
24
23
34
33
Ten M3.5 1.36 (34.5) Max. 0.30 (7.6)
2.17 (55.2)
0.08 (2.0)
A1
D9PR9
2.52 (64.0) Max. 1.378 ± 0.004 (35.0 ± 0.1)
2.03 (51.5) Max.
41
A2 Two M4 or 0.18 (4.5) Dia.
0.17 (4.3)
1.70 (43.2)
42
Mounting Holes (Bottom View)
Figure 49-110. D9PR, Approximate Dimensions in Inches (mm)
14
13
24
23
34
33
42
41
A2
A1
D9PR10
Figure 49-112. Terminal Arrangements Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 For more information visit: www.eaton.com
CA08102001E
Page 73
Control Relays & Timers General Purpose Relays, Type AA
49-73
July 2008
9575H Series 3000, AC and DC
9575H Series 3000, Type AA, AC and DC
■ Additional contact ratings for relays with blowout magnets: 10A @ 110V DC Resistive, 4A @ 225V DC Resistive, 2A @ 325V DC Resistive. For inductive loads, contacts must be derated accordingly. ■ Contact Material: Silver Cadmium Oxide, Gold Flashed. 5/16 inch (7.9 mm) diameter standard.
Dielectric Withstanding Voltage
Product Selection When Ordering Specify Catalog Number and Magnet Coil Code Letter. Example: for DPDT relay with Auxiliary Switch and a 120V 50/60 Hz coil, order Catalog Number 9575H3A010. Table 49-95. Type AA Relays Relay Style
Catalog Number
Relay (DPDT) Relay with Auxiliary Switch Relay with Blowout Magnets Relay with Auxiliary Switch and Blowout Magnets
9575H3_000 9575H3_010
■ Between Open Contacts: 1500 Vrms ■ All Other Mutually Insulated
Conductive Elements: 2200 Vrms
Miscellaneous 9575H Series 3000 Relay
■ Coil Terminals: 6-32 Binder Head
Screws
Product Description
■ Contact Terminals: 8-32 Binder Head
Type AA panel mounted relays are rated (each pole) 40A up to 300V AC, 50/60 Hz; 5A @ 480/600V AC, 50/60 Hz and 40A @ 28V DC.
■ Main Base Material: Molded
Application Description 9575H Series 3000 relays are ideal for applications when controlling smaller loads such as single-phase motors.
Technical Data and Specifications Relay Specifications Coil ■ Pull-In Voltage: 80% DC coils, 85%
AC coils of nominal voltage or less @ 25˚ C ■ Dropout Voltage: 10% of nominal voltage or more @ 25˚ C ■ Coil Resistance: ±10% measured @ 25˚ C ■ Max DC Coil Dissipation Capability: 4 Watts DC continuous @ 25˚ C
Contacts ■ Contact Combination: DPDT ■ Contact Rating Each Pole (Main Con- tacts): Each pole rated 40 Amps up to 300V AC, 50/60 Hz, 5 Amps @ 480/ 600V AC 50/60 Hz, 0.75pF inductive load. 1-1/2 hp motor load (each pole) @ 120 thru 600V AC 50/60 Hz. 2 hp motor load @ 200 thru 600V AC, 50/60 Hz only when using both poles to switch both sides of load, 40 Amps @ 28V DC resistive load each pole. NEMA A 600 pilot duty 50/60 Hz.
Screws Phenolic, UL recognized (QMFZ2) ■ Weight (DPDT Relay): 11 oz. (311 grams) approximately ■ Weight (DPDT Relay with Auxiliary Switch) 14.5 oz. (411 grams) approximately
Auxiliary Switch Specifications ■ Contact Combination: SPDT ■ Contact Rating: Auxiliary Switch rated 10 Amps @ 125 or 250V AC, resistive load; 1/4 hp at 125 or 250V AC, motor load; 0.4 Amps at 125V DC or 0.20 Amps at 250V DC, resistive load; 3 Amps at 125V AC lamp load. All AC ratings are 50/60 Hz. ■ Dielectric Withstanding Voltage: 500V AC RMS between open contacts, 1500V AC RMS between all other mutually insulated conductive elements. ■ Terminals: 4-40 Round Head Screws for Auxiliary Contacts standard. Table 49-93. Average Operating Times (Milliseconds) Operation Pick-Up Drop-Out
DPDT Relay
DPDT Relay with Auxiliary Switch
40 35
50 35
Table 49-94. Temperature Ranges Temperature
AC
DC
Operating Range Non-operating Range
-30°C to +50°C -30C° to +100°C
-30°C to +60°C -30C° to +100°C
Price U.S. $
9575H3_100 9575H3_110
Underscore indicates missing Code Suffix for Magnet Coil, see Selection Table below.
Table 49-96. Coil Voltage Selection Table Coil Voltage
Hz
Suffix Code
120 240 480/440
50/60 50/60 60/50
A B C
600/550 208 277
60/50 50/60 50/60
D E H
6 12 24 48
50/60 50/60 50/60 50/60
J K L M
110 220 6, P Q R
12 24 48, S T W
Volts AC
Volts DC
49
Options and Accessories Table 49-97. Enclosure Description
Catalog Number
NEMA1 Enclosure, 9575H2449
Price U.S. $
Only 9575H3 relays without an auxiliary switch should be mounted in the 9575H2449 enclosure.
Note: There are no “repair parts” available for these relays.
Standards and Certifications ■ UL listed, E1491 ■ CSA 41729 ■ CE: EN60947-4-1, EN60947-5-1
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1 CA08102001E
For more information visit: www.eaton.com
Page 74
49-74
Control Relays & Timers General Purpose Relays, Type AA July 2008
9575H Series 3000, AC and DC
Dimensions 3.31" (84.2)
Mounting Holes 0.187 (4.75) Dia. (2 Places)
1.88" (47.6)
8-32 Binder Head Machine Screw on Contact Terminals (6 Places)
0.218" (5.5) Dia.
0.56" (4.3)
0.230" (5.8) Square Hole
2.25 (58.7) Max. 3.55" (90.1) 1.87 (47.5)
0.38 (9.5)
2.50 (63.5)
1.62 (41.1)
0.159" (4) Dia. 10-32 Tap Typ. 4 Places
4.50" (114.3)
3.12 (79.2) Max. 6-32 Binder Head Machine Screw on Coil Terminals (2 Places)
5.63" (142.9)
Figure 49-113. 9575H3 DPDT Relay, Approximate Dimensions in Inches (mm) Mounting Holes 0.187 (4.75) Dia. (2 Places)
0.136" (3.4) Dia. 8-32 Tap Typ. 2 Places
0.50" (2.7)
2.00" (50.8) 0.218" (5.5) Dia. Typ. 2 Places
3.00" (76.2) 0.36" (9.1) Typ. 2 Places
8-32 Binder Head Machine Screw on Contact Terminals (6 Places)
2.25 (58.7) Max.
1.87 (47.5) 2.50 (63.5)
0.38 (9.5)
0.20" (5.1)
1.62 (41.1)
Figure 49-115. 9575H2449, Approximate Dimensions in Inches (mm)
3.12 (79.2) Max. 6-32 Binder Head Machine Screw on Coil Terminals (2 Places)
49
NC 10A 1/4HP 125 OR 250VAC .4A @ 125V DC, .2A @ 250V DC 3A 125VAC "LAMP" 278 VA 125/250 VAC P.D. NO COM
Mounting Holes (2) AUX. SWITCH MARKING SURFACE
Insulators (2 Sides)
4.44 (112.7) Max.
Screw Terminals (4-40) RHMS with External Tooth Lockwashers (3 Places)
RELAY TOP VIEW
Figure 49-114. 9575H3 DPDT Relay with Auxiliary SPDT Switch, Approximate Dimensions in Inches (mm)
For more information visit: www.eaton.com
CA08102001E
Page 75
Control Relays & Timers Machine Tool Relays
49-75
July 2008
D15 Series, Freedom 600V Multipole
Contents
Application Description
Description
Page
Machine Tool Relays Freedom 600V Multipole . . . . . . . . . . . . . Fixed Contact Industrial Control . . . . . . Convertible Contact Industrial Control . . . . . . Type M, 600V AC Multipole with Convertible Contacts . . . Type M, DC Multipole with Convertible Contacts . . .
49-75 49-79 49-83
49-87
Side-mounted contact blocks can be used to provide additional poles in applications where a pneumatic timer is installed on the front of the relay. They can also be used where panel depth is restricted. The maximum number of contacts recommended per relay is 8, 6 of which can be NC. When a pneumatic timer is used, the maximum recommended number of NC contacts is 3.
Continuous Thermal Rating: 5A
■ 600V, 10A continuous thermal current ON or OFF status
Product Description Contact poles on the D15 relay are of the fixed design and are not convertible. The basic 4-pole relay will accept a front-mounted contact pole deck and/or side-mounted contact blocks (one per side). In addition, a sidemounted solid-state timer or a frontmounted pneumatic timer can be added to the relay. Only one frontmounted attachment can be added to the basic relay.
CA08102001E
NEMA A600
Continuous Thermal Rating: 10A
Features
■ Relay base has mounting holes
4-Pole Relay with Front Contact Pole Deck Assembled
Table 49-98. Contact Ratings
AC Volts 120 240 480 600
■ State indicator visually shows relay
4-Pole Relay
Technical Data and Specifications
Relays with DC coils are supplied with a coil clearing NC contact mounted on the side of the relay.
49-90
D15 Series, Freedom 600V Multipole
Standards and Certifications on 35 x 60 mm centers, permitting direct replacement of competitive relays ■ Relay also mounts on 35 mm DIN rail as standard ■ Magnet coil has three terminals, permitting either top or diagonal wiring, easy to replace European or U.S. relays without changing wiring layout ■ Contact pole terminals have captive, backed-out, self-lifting pressure plates with ± screws, reduced wiring time ■ All terminals are shrouded or “finger-proofed” to reduce possibility of electrical shock ■ Designed to meet or exceed UL, NEMA, IEC, CSA, VDE, BS and other international standards
For more information visit: www.eaton.com
Make 60 30 15 12
Break 6.0 3.0 1.5 1.2
NEMA P300 DC Volts
Make/Break Amperes
125 250
1.1 0.55
Table 49-99. Magnet Coil Data AC Pick-Up Voltage VA Watts
Sealed VA
Watts
12 – 600V
7.5
2.4
DC Pick-Up Voltage Amps Watts
Sealed VA
Watts
12 24 48 120
0.28 0.14 0.07 0.028
3.36 3.36 3.36 3.36
80
6.4 3.2 1.6 0.64
49
76.8 76.8 76.8 76.8
49
Page 76
Control Relays & Timers Machine Tool Relays
49-76
July 2008
D15 Series, Freedom 600V Multipole
Product Selection
Accessories
When Ordering Specify
Pneumatic Timer Attachment
■ Catalog Number and Magnet Coil Code Letter. Example
Attachment mounts on top of any Freedom Series relay (topmounted auxiliary contacts can not be installed on device when timer is used). Timer unit has DPST timed contacts, circuits in each pole must be the same polarity. Units are convertible from OFF to ON Delay or vice-versa.
For a 4-pole relay having 4NO contacts with a 120V 60 Hz coil, order Catalog Number D15CR40AB. Table 49-100. Factory Assembled Multipole Relays Number of Poles
Type of Contacts
Open Type
NO
NC
Catalog
4
4 3 2 1 0
0 1 2 3 4
D15CR40_B D15CR31_B D15CR22_B D15CR13_B D15CR04_B
6 (4-Pole Relay with 2-Pole FrontMounted Deck)
6 5 4 3 2 1 0
0 1 2 3 4 5 6
D15CR60_B D15CR51_B D15CR42_B D15CR33_B D15CR24_B D15CR15_B D15CR06_B
8 (4-Pole Relay with 4-Pole FrontMounted Deck)
8 7 6 5 4 3 2
0 1 2 3 4 5 6
D15CR80_B D15CR71_B D15CR62_B D15CR53_B D15CR44_B D15CR35_B D15CR26_B
Price U.S. $
C320 Pneumatic Timer Attachment
Table 49-103. Pneumatic Timer Attachment
Table 49-101. Additional Contact Poles Price U.S. $
Front Contact Pole Deck
49
C320KGT3 C320KGT4 C320KGT5 C320KGT7
4NO 3NO-1NC 2NO-2NC 1NO-3NC 4NC
C320KGT13 C320KGT14 C320KGT15 C320KGT16 C320KGT17
Make Break
Volts AC 120
240
480
600
30 3
15 1.5
7.5 0.75
6 0.6
Finger Protection Shields Snap-on shields for both contactors and starters provide IEC Type IP20 Finger Protection. Prevents accidental contact with line/load terminals. Application
Catalog Number
D15
C320LS1
Price U.S. $
Adhesive Dust Cover These adhesive stickers come 25 to a package and provide extra protection from contaminants when applied to the sides of Freedom D15. Adhesive covers are easily applied to side opening where auxiliaries are not installed and provide extra protection from metal filings and other debris.
Side-Mounted Contact Blocks
E.C. = Early Closing
C320TP1 C320TP2
Price U.S. $
Table 49-105. Finger Protection Shields
1NO-1NC 2NO 2NC 1NO (E.C.) – 1NC (L.O.)
1NO-1NC 2NO 2NC 1NO (E.C.) – 1NC (L.O.)
0.1 to 30 Seconds 10 to 180 Seconds
Description tion Table below. Not all Suffix Codes available: consult Customer Support Center.
Catalog Number
Catalog Number
Table 49-104. Maximum Ampere Ratings
Underscore indicates missing code suffix for magnet coil, see Selec-
Description
Timing Range
C320KGS3 C320KGS4 C320KGS5 C320KGS7
Table 49-106. Adhesive Dust Cover Catalog Number
L.O. = Late Opening
Table 49-102. Magnet Coil Selection Table
Price U.S. $
C320DSTCVR (25 to a package)
AC Coils Volts and Hertz
Code Suffix
AC Coils Volts and Hertz
Code Suffix
DC Coils Volts
Code Suffix
120/60 or 110/50 240/60 or 220/50 480/60 or 440/50 600/60 or 550/50
A B C D
208/60 277/60 208 – 240/60 24/60
E H J T
12 24 48 120
R1 T1 W1 A1
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 For more information visit: www.eaton.com
CA08102001E
Page 77
Control Relays & Timers Machine Tool Relays
49-77
July 2008
D15 Series, Freedom 600V Multipole Solid-State ON DELAY Timer, Side Mounted on Freedom Series NEMA 00 – 2, D15, IEC A – K and C25D, C25E and C25F Frame This timer is designed to be wired in series with the load (typically a coil). When the START button is pushed (power applied to timer), the ON Delay timing function starts. At the completion of the set timing period, timer and series wired load will both be energized.
Metal Mounting Plate
DC/AC Interface Module
Fits all D15 Multipole Relays.
The Catalog Number C320DC Interface Module is an optically isolated solidstate switch which provides a means of operating AC coils with a 24V DC control signal. It acts as a Cat. No. C320DC space saving interposing relay which can switch a specified 50/60 Hz AC source to the contactor or starter coil.
Table 49-108. Mounting Plate Description
Catalog Number
Metal Mounting Plate
C321MP1
Price U.S. $
Mounting Channel (DIN Rail) Designed for DIN rail mounting of Freedom Series relays.
The module may be directly attached to the coil terminals of any Freedom Series contactor or starter, NEMA Sizes 00 – 3, D15, IEC Sizes A – N and lighting contactors 10 – 100A. It also has provisions for DIN rail mounting. DIN Rail
Table 49-109. Mounting Channel (DIN Rail)
Solid-State Timer
Table 49-107. Mounted Timer Timing Range 0.1 – 1.0 Seconds 1 – 30 Seconds 30 – 300 Seconds 5 – 30 Minutes
Catalog Number
Price U.S. $
C320TDN1_ C320TDN30_ C320TDN300_ C320TDN3000_
Add operating voltage Suffix to Catalog
Number. A = 120V, B = 240V, E = 208V Rated 0.5 ampere pilot duty, not to be used on larger contactors. Terminal connections are quick connects only. Two per side.
Description
Catalog Number
1 Meter Length
XBANS3575P
Price U.S.$
■ AC Operating Voltage: 24 – 240V AC
These kits limit high voltage transients produced in the control circuit when power is removed from the contactor or starter coil. There are three separate suppressors for use Cat. No. C320TS2 on 24 – 120V, 208 – 240V or 277 – 480V coils respectively. These devices mount directly to the coil terminals. Table 49-110. Transient Suppressor Kits Catalog Coil Number Voltage 50/60 Hz
Transient Suppressor
24/120V 208/240V 277/480V
Design Characteristics ■ DC Input: 24V ±10% at mA nominal
Transient Suppressor Kits
Description
The module will operate coils within the voltage ranges shown in Table 49-111.
±10% 50/60 Hz ■ AC Current Rating: 10A make
(inrush), 1A break (sealed) Table 49-111. Controller Coil Voltage Ranges Controller Catalog Number Prefix
Controller Coil Size or Range Rating Volts AC
AE16, AE17, AE56, AE57, CE15, CE55
A–F G–K L–N
24 – 240 48 – 240 110 – 240
AN16, AN56, CN15, CN55
00 – 0 1–2 3
24 _ 240 48 – 240 110 – 240
CN35
10 – 30A 60A 100A
24 – 240 48 – 240 110 – 240
Price U.S. $
C320TS1 C320TS2 C320TS3
Suppressor is compatible with coil voltages/ ranges as shown, both 50 and 60 Hz.
Contactor Coil 24V DC Input Observe Polarity on Module
24 – 240V AC 50/60 Hz
Solid-State Switch
Figure 49-116. Typical Application
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 CA08102001E
For more information visit: www.eaton.com
49
Page 78
49-78
Control Relays & Timers Machine Tool Relays July 2008
D15 Series, Freedom 600V Multipole
Terminal Marking
Dimensions
Relay terminals are identified by a two digit number in accordance with International Standards approved by CENELEC (European Committee for Electrotechnical Standardization). The number is marked on the relay and is used to identify location and status of the contacts.
Table 49-112. Approximate Dimensions in Inches (mm) and Shipping Weights.
The first digit indicates the location of the contact on the relay. The numbering begins with 1 and continues without a break from left to right.
Description
Dimension C in Inches (mm)
Shipping Weights Lbs. (kg)
Relay Only Relay with Timer Attachment Relay with Front Contact Pole Deck
3.30 (83.8) 5.55 (141.0)
1.3 (0.6) 1.5 (0.7)
4.66 (118.4)
1.7 (0.8)
The second digit indicates the status of the contacts (NO or NC). Terminal marking 1 and 2 mean NC and 3 and 4 mean NO. Example of marking with 2NO and 2NC contacts:
0.54 (13.7)
1.8 (45.7)
0.54 (13.7)
0.54 (13.7)
1.8 (45.7)
0.54 (13.7) 4.66 (118.4)
C
Location
Status (NO or NC) 13
21
31
43
2.36 Frt. (59.9) Mtd. Acc.
1.36 (34.5)
14
22
32
44
Mtg. Holes for M4 or #8 Screws
Side Mtd. Blk.
2.36 Frt. (59.9) Mtd. Acc.
2.96 (75.2) Optional Additional Contact Poles or Accessories
Side Mtd. Blk.
2.96 (75.2)
1.36 (34.5)
Optional Additional Contact Poles Mtg. Holes for M4 or #8 Screws or Accessories
D15 4-Pole Relay
D15 6- and 8-Pole Relays
Figure 49-117. Terminal Marking
Figure 49-118. Approximate Dimensions in Inches (mm)
Front-Mounted 4-Pole Deck
Side-Mounted Contact Block
4-Pole Relay with Side-Mounted Contact Block
49
For more information visit: www.eaton.com
CA08102001E
Page 79
Control Relays & Timers Machine Tool Relays
49-79
July 2008
BF/BFD Series, Fixed Contact Industrial Control
BF/BFD Series, Fixed Contact Industrial Control
Technical Data and Specifications Table 49-113. Specifications BF Relay Electrical Ratings, NEMA A300 Volts
120 240
Maximum Current Make
Break
Make
Break
10 10
60 30
6 3
7200 7200
720 720
Horsepower Ratings (UL Recognized) Phase
Type BF
Maximum VA
Cont.
DC Rating, NEMA P300
AC Volts
Volts
115
230
1/6, 1/2 1
Cont.
Maximum Current Make
Break
Max. Make or Break VA
5.0 5.0
1.1 0.55
1.1 0.55
138 138
Type BFD 1 3
Product Description Type BF is AC operated, 300V maximum, and the BFD is DC operated, 250V. Fixed contact relays are available in any combination of NO and NC from two to twelve poles. BF and BFD relays have captive clamp terminals fully accessible from the front, a molded coil with low operating temperature and silver alloy contacts suitable for low voltage circuits.
Standards and Certifications ■ UL recognized, UL File No. E19223
(AC relays only) ■ CSA certified, File No. LR39402-6,
LR28548-10, 11 (AC and DC relays)
125 250
Resistive Rating
Coil Power Requirements
125V DC: 3A 250V DC: 1.5A
AC: 72 VA open, 22 VA closed DC: 12 watts (nominal), 250V max.
Options Table 49-114. Options Description
Code Letter or
Catalog Number
FASTON Push-On Terminals Insert letter F after relay type designation in listed Catalog Number. Example: BFF20F or BFDF20S
F, Overlapping Contacts A NO contact closes before corresponding NC contact opens, supplied as NO/NC set(s). Insert letter A after relay type designation in listed Catalog Number. Example: BFA22F or BFDAF22S, NEMA 1 Enclosure for Relay Types BF, AR, all poles BFD, 4 – 8 poles ARD, 4 – 6 poles, Price U.S. $
4977D40G04 4977D40G04 4977D40G04
49
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 CA08102001E
For more information visit: www.eaton.com
Page 80
Control Relays & Timers Machine Tool Relays
49-80
July 2008
BF/BFD Series, Fixed Contact Industrial Control
Product Selection When Ordering Specify ■ Catalog Number of Basic Relay. ■ If a coil voltage other than listed is required, select the Suffix Code from the
Coil Voltage Table and substitute it for the last letter in the Catalog Number. Example: BF80V for a 110/60 AC coil. Table 49-115. Complete Relay Number of Poles
Type of Contact
BF 300V AC Basic Relays 120/60, 110/50 AC Coil NO (Form A) NC (Form B) Catalog Price Number U.S. $
BFD 250V DC Basic Relays 120 DC Coil Catalog Price Number U.S. $
2
2 1 0 3 2 1 0 4 3 2 1 0 6 5 4 3 2 0 8 7 6 5 4 0 10 8 7 6 5 4 2 12 8 7 6 5 4
BFD20S BFD11S BFD02S BFD30S BFD21S BFD12S BFD03S BFD40S BFD31S BFD22S BFD13S BFD04S BFD60S BFD51S BFD42S BFD33S BFD24S BFD06S BFD80S BFD71S BFD62S BFD53S BFD44S BFD08S BFD100S BFD82S BFD73S BFD64S BFD55S BFD46S BFD28S BFD120S BFD84S BFD75S BFD66S BFD57S BFD48S
3
4
6
8
10
49
12
0 1 2 0 1 2 3 0 1 2 3 4 0 1 2 3 4 6 0 1 2 3 4 8 0 2 3 4 5 6 8 0 4 5 6 7 8
BF20F BF11F BF02F BF30F BF21F BF12F BF03F BF40F BF31F BF22F BF13F BF04F BF60F BF51F BF42F BF33F BF24F BF06F BF80F BF71F BF62F BF53F BF44F BF08F BF100F BF82F BF73F BF64F BF55F BF46F BF28F BF120F BF84F BF75F BF66F BF57F BF48F
Consult Customer Support Center for availability.
Note: Relays listed above with equal number of NO and NC contact poles are specially priced, 1NO and 1NC pole are supplied at no additional charge.
Table 49-116. Coil Voltage Table BF Coils Volts AC
Hz
Suffix Code
12 24 48 110 110/120 208 220/240 440
60 60 60 60 50/60 60 50/60 60
H I J V F K G C
BFD Coils Volts DC
Suffix Code
6 12 24 38 48 72 95 120 130 240
C D L N M E B S U T
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1 For more information visit: www.eaton.com
CA08102001E