Page 47
FOLLOWER SCALING FORMAT (SECONDARY MODE)
To program the M-Drive’s Follower Scaling Format, enter the data as indicated below:
Code # Code Title Data to be Entered
CP-3 or Secondary Setpoint This is the desired setpoint (ratio).
CP-4
CP-62 Secondary Scaling Format 02
CP-64 Secondary Display Format 02 *
CP-37 Secondary RPM RPM of the feedback sensor shaft when operating Feedback Maximum at the maximum speed during normal operation.
CP-36 Secondary RPM Maximum RPM during normal Reference External Maximum operation of the shaft on which the external reference sensor is monitoring.
CP-21 Secondary Setpoint This is the number wanted as a setpoint if the
Eng Units Ext Ref. and feedback shafts are rotating at the speeds entered at codes CP-36 & CP-37 respectively. This number is often but not necessarily 1.000
CP-23 Secondary Display Eng The number desired to be Units displayed by the Tach when the Ext. Ref. and feedback are rotating at the speeds entered at codes CP-36 & CP-37 respectively.
CP-31 PPR Feedback This is the number of teeth on the gear or the number of lines on the encoder used for feedback.
CP-30 PPR Ext. Ref. This is the number of teeth on the gear or the number of lines on the encoder used for external reference.
* If an Engineering Unit (speed) display is desired, set CP-64 to "1."
Page 5-9
Page 48
FOLLOWER FORMAT, DEFAULT PARAMETERS (SECONDARY MODE)
When shipped from the factory, the following assumptions are mace:
There are 60 tooth gears on both the Master and Follower Motor armatures. The maximum motor RPM for both motors is 2000.
The Ratio Setpoint is scaled such that a 1.000 entry causes the Follower Motor to rotate at the same RPM as the Master Motor.
Whenever the RPM of the Follower Motor is equal to the RPM of the Master Motor, the Tach indicates 1.000.
Based on these assumptions, the M-Drive’s default programming is as follows:
ode CP-62
CP-64 CP-37 CP-36
CP-21
CP-23
CP-31 CP-30
Code Title Data to be Entered Secondary Scaling Format 02 Secondary Display Format 02 Secondary RPM Feedback Max 2000 Secondary RPM External 2000 Reference Max
Secondary Setpoint Eng 1.000 Units
Secondary Display Eng. 1.000 Units
PPR Feedback 60 PPR External Reference 60
Page 5-10
Page 49
FOLLOWER FORMAT, NON-STANDARD PARAMETERS (SECONDARY MODE)
Example:
It is desired that the Setpoint and Tach reflect the flow ratio in gallons/minute of Bto A.
The Motor/Pump combination used for Component A delivers 10 gallons/minute at 1725 motor RPM.
The Motor/Pump combination used for Component B delivers 30 gallons/minute at 1800 motor RPM.
A 60-tooth gear is used for the Ext. Ref. (Component A). A 30-tooth gear is used for follower (Component B).
Both gears mount on the motor armature.
alculation
1.
Determine the flow ratio that exists when both components are flowing at maximum rate.
Gal/Min mponent B) = 3.000 10 Gal/Min (Component A)
Code # Code Title Data to be Entered CP-62 Secondary Scaling Format 02
CP-64 Secondary Display Format 02
CP-37 Secondary RPM Feedback Max 1800
CP-36 Secondary RPM External 1725
Reference Max
CP-21 Secondary Setpoint Eng Units 3.000
CP-23 Secondary Display Eng. Units 3.000
CP-31 PPR Feedback 30
CP-30 PPR External Reference 60
Page 5-11
Page 50
TUNING
Tuning refers to the procedure of setting the tuning parameters of the control algorithm to achieve stable and optimal performance. The default tuning parameters should provide for stable operation in the majority of applications. The tuning instructions below are provided for those applications which require additional M-Drive tuning.
TUNING PROCEDURE - SPEED LOOP
65 - GAIN
To set the Gain (Proportional Band), first set the Reset (66) and Rate (67) variable to zero and the Trim Authority (68) to 100. Reduce the Gain number until the system goes unstable (erratic). This is easily tested by moving between two wide spread setpoint values while in Master Scaling Mode. When instability is reached, increase the Gain number slightly until the system stabilizes.
66 - RESET (Integral)
Using only Gain, the system will exhibit a phenomenon called proportional droop, whereby the setpoint is never reached due to system losses. Reset should be added until overshoot is exhibited (move from large numbers to small to increase the reset). Overshoot occurs when the feedback goes over the desired setpoint before settling to the desired setpoint value. It is necessary to switch between setpoints to observe overshoot.
67 - RATE (Derivative)
Rate is only required if the control is still too sluggish after setting the Gain and Reset parameters. Rate, like Gain, should be reduced up to the point of instability, then increased slightly until the system stabilizes.
To reduce Rate, move from larger to smaller numbers. To increase Rate, move from smaller to larger numbers.
Page 5-12
Page 51
68 - TRIM AUTHORITY
Trim Authority determines how much of the output is influenced by the Gain, Reset and Rate terms, and how much is determined by feedforward. If it is not possible to achieve stable operation with 100% Trim Authority, reduce this parameter and repeat the tuning procedure.
69 - RATE THRESHOLD If erratic operation is exhibited only at very low feedback frequencies, the Rate
Threshold can be increased slightly. This parameter determines the minimum amount of differential error required before the Rate term influences the control output.
TIMING 16 - ACCELERATION TIME
This parameter determines the acceleration rate of the setpoint. The number entered is the amount of time in seconds required to increase the setpoint from 0 to 2000 RPMs.
17 - DECELERATION TIME
This number determines the deceleration rate of the setpoint. The number entered is the amount of time in seconds required to decrease the setpoint from 2000 to 0 RPMs.
Page 5-13
Page 52
LIMITS AND ALARMS
The following parameters set up the control limits and alarms for the M-Drive.
10 - MINIMUM LIMIT This parameter sets the minimum level of RPMs for operation. It is possible to enter a setpoint below this level. However, the control will always attempt to maintain a speed at or above the minimum limit.
11 - MAXIMUM LIMIT This parameter sets the maximum level of RPMs for operation. It is possible to enter a setpoint above this limit. However, the control will always attempt to maintain a speed at or below the maximum limit.
12 - LOW ALARM
This parameter sets the RPM level at which the Low Alarm output is energized. The Output will energize when the feedback RPMs are at or below this level.
13 - HIGH ALARM
This parameter sets the RPM level at which the High Alarm output is energized. The output will energize when the feedback is at or above this RPM level.
14 - ERROR ALARM 1 - RAMPED ERROR
This parameter establishes the error band (Ramped Ref minus Feedback) in RPMs at which the Error Alarm 1 output is energized. Any positive or negative error at or above this level energizes the output.
15 - ERROR ALARM 2 - SCALED ERROR This parameter establishes the error band (Scaled Ref minus Feedback) in RPMs at which the Error Alarm 2 output is energized. Any positive or negative error at or above this level energizes the output.
NOTE: This alarm is useful for determining when the ultimate process speed has been reached - E.g., after an acceleration period.
Page 5-14
Page 53
PHASE CONTROL ZERO POSITION ERROR CONTROL
The M-Drive has the ability to reduce the long-term speed error to zero in Follower Scaling Mode. This is done by keeping track of the number of External Reference and Feedback pulses received. The inside speed control loop is then setpoint adjusted to reduce this error to zero.
The M-Drive Zero Error controlling parameters are defaulted to zero. Values for the following three parameters will need to be entered to invoke this feature of the M-Drive. For additional information concerning Zero Position Error Control, refer to Chapter 6, Theory of Operation.
18 - LAG PULSE LIMIT
The Lag Pulse Limit sets a maximum pulse error count for the difference between the idealized Feedback pulses minus the actual Feedback pulses. It may not always be desirable to recover all of the position error lag. Set this parameter to the desired lag pulse limit.
19 - LEAD PULSE LIMIT
The Lead Pulse Limit sets a maximum pulse error count when the Feedback pulses exceed the idealized Feedback pulse count. Set this parameter to the desired lead pulse limit.
29 - RECOVERY MULTIPLIER
The Recovery Multiplier determines the rate at which the pulse error is reduced to zero. This parameter multiplied by the pulse error count is the number by which the speed setpoint is adjusted every 100 milliseconds.
49 - PULSE ERROR COUNT (Monitor Variable)
Indicates the actual existing position error in feedback pulses.
NOTE: When the phase control feature is invoked (CP-29 does not equal zero), the Minimum Limit (CP-10) and Maximum Limit (CP-11) may be exceeded while attempting to recover position error.
Page 5-15
Page 54
FEEDBACK AND EXT. REF. SOURCES OTHER THAN GEAR AND SENSOR
In certain applications, the Feedback and External Reference signals are not generated by gears or encoders. Two examples are voltage controlled oscillators and the clocking oscillators in inverters. The basic rule for making these substitutions is to use 60 for the PPR entry and the maximum frequency for the RPM entry. This works until the frequency exceeds 9999 HZ. For frequencies from 10K to 30K HZ, use 600 for the PPR entry and maximum frequency divided by 10 for the RPM entry.
Page 5-16