Page 21
Terminal CPX-P Key features – Power supply Power supply concept General information
The use of decentralised devices on the fieldbus – particularly with high protection for direct machine mount ing – demands a flexible power supply concept. A valve terminal with CPX-P can, in principle, supply all voltages via a single connection.
A distinction is made between supply for electronics plus sensors valves plus actuators.
Connection technology: 7/8" them as well as their bus connections. Many applications require the CPX-P terminal to be segmented into voltage zones. This applies in particular to the separate disconnection of the outputs. The interlinking blocks provide either a space-saving central power supply for the entire CPX-P terminal or galvanically isolated, all-pin disconnectable potential groups/ voltage segments.
Interlinking blocks Interlinking blocks represent the backbone of the CPX-P terminal with all supply lines. They provide the power supply for the modules used on
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
21
Page 22
Terminal CPX-P Key features – Power supply Interlinking blocks With system supply CPX-M-GE-EV-S-7/8-5POL CPX-M-GE-EV-S-7/8-5POL-VL Connection technology 7/8", 5-pin
For CPX-P terminal modules and connected sensors For valves that are connected to the CPX-P terminal via a pneumatic interface
For actuators that are connected to output modules of the CPX-P terminal
Without power supply CPX-M-GE-EV
With additional power supply for outputs CPX-M-GE-EV-Z-7/8-5POL CPX-M-GE-EV-Z-7/8-5POL-VL
For actuators that are connected to output modules of the CPX-P terminal
Connection technology 7/8", 5-pin
-H- Note For 7/8": Commercially available accessories are often limited to max. 8 A
22
-H- Note Valve terminal MPA-S has either a 5-pin 7/8", 4-pin 7/8" or 3-pin M18 power supply for one or more valve voltage zones. Galvanically isolated,
è Internet: www.festo.com/catalogue/...
all pins disconnectable with voltage monitoring in the following MPA module.
Subject to change – 2018/04
Page 23
Terminal CPX-P Key features – Diagnostics Diagnostics System performance 3
1
4
2
1 Undervoltage monitoring 2 Diagnostics via bus interface 3 Diagnostic overview LED – Fieldbus status – CPX-P status 4 Status and diagnostic LED for module and I/O channels
5 Module and channel-specific diagnostics 6 Valve-specific diagnostic module and solenoid coils
The CPX-P terminal supports on-thespot diagnostics via a row of LEDs. This is separate from the connection area and therefore provides good visual access to status and diagnostic information.
Module and channel-specific diagnosis is supported, for example Undervoltage detection for outputs and valves Short circuit detection for sensors, outputs and valves Open-load detection for a missing solenoid coil Storage of the last 40 causes of errors with error start and error end
The diagnostic messages can be read out via the bus interface in the higherorder controller and visualised for the central recording and evaluation of error causes. This is done using the individual fieldbus-specific channels. The CPX-CEC also offers the option of access via the integrated Ethernet interface (remote maintenance via PC/web applications).
1 Fieldbus-specific LEDs On each bus node, a maximum of 4 fieldbus-specific LEDs display the fieldbus communication status of the CPX-P terminal with the higher-order controller.
2 CPX-P-specific LEDs A further 4 CPX-P-specific LEDs provide non-fieldbus-specific information about the status of the CPX-P terminal, for example – Power system – Power load – System fault – Modification parameters
5
Detailed diagnostic functions are needed in order to quickly locate the causes of errors in the electrical installation and therefore reduce downtimes in production plants. A basic distinction is made between on-the-spot diagnostics using LEDs or an operator unit (CPX-MMI) and diagnostics using a bus interface.
6
Overview of LEDs on the bus node 1
2
Input/output module status and diagnostic LEDs 1
2
3
2018/04 – Subject to change
1 Status LEDs for the inputs and outputs Each input and output channel is assigned a status LED.
2 Channel-oriented diagnostic LEDs Depending on the module design, another diagnostic LED is available for each I/O channel.
è Internet: www.festo.com/catalogue/...
3 Group diagnostic LEDs An LED displays the group diagnostics for each module.
23
Page 24
Terminal CPX-P Key features – Parameterisation Diagnostics Display on the operator unit (CPX-MMI) 1 LCD graphical display for on-site plain-text diagnostics – Fault location and type – Without programming
1
Display on a PC
1 3
1 CPX-P terminal with valve terminal 2 Adapter diagnostic interface to USB 3 Laptop/portable device with USB interface and installed CPX-P
Maintenance Tool (CPX-FMT) soft ware – Fault location and type – Without programming – Storing the configuration – Preparing screenshots
2
Parameterisation Changes to the application are often required during commissioning. The parameterisable characteristics of the CPX-P modules mean that functions can be very easily changed by means of configuration software. This reduces the number of modules needed and, consequently, the amount of storage space required. It is therefore possible, for example, to reduce the input debounce time for an input module – normally 3 ms – to
0.1 ms on a "fast" input module for faster processes, or to set the re sponse of a valve following a fieldbus interrupt. Depending on the modules used, parameterisation can be performed via the following interfaces: Ethernet Fieldbus Control block direct interface (programming interface) Operator unit CPX-MMI
1 2
24
è Internet: www.festo.com/catalogue/...
1 Input debounce time 3 ms 2 Input debounce time 0.1 ms
Subject to change – 2018/04
Page 25
-V- New CPX-4AE-4AA-H Terminal CPX-P Key features – Addressing Addressing The various CPX-P modules occupy a different number of I/O addresses within the CPX-P system. The maximum address space for bus nodes depends on the performance of the fieldbus systems.
Maximum system configuration: 1 bus node or control block 9 I/O modules 1 pneumatic interface (e.g. pneumatic interface MPA-S with up to 16 MPA manifold sub-bases)
The maximum system configuration can be limited in individual cases by exceeding the address space.
Overview – Allocated addresses for CPX-P modules Inputs [bit] CPX-P-8DE-N CPX-P-8DE-N (inputs configured as counter) CPX-P-8DE-N-IS CPX-P-8DE-N-IS (inputs configured as counter) CPX-8DE CPX-8NDE CPX-16DE CPX-4DA CPX-8DA CPX-4AE-U-I CPX-2AA-U-I CPX-4AE-4AA-H VMPA1-FB-EMS-8 VMPA1-FB-EMG-8 VMPA2-FB-EMS-4 VMPA2-FB-EMG-4 VMPA1-FB-EMS-D2-8 VMPA1-FB-EMG-D2-8 VMPA2-FB-EMS-D2-4 VMPA2-FB-EMG-D2-4 VMPA-FB-PS-1 VMPA-FB-PS-3/5 VMPA-FB-PS-P1 VMPA-FB-EMG-P1 1)
-V-
-H- Note Please refer to the detailed descrip tion of the configuration/addressing rules in the technical data for CPX bus nodes.
Outputs [bit]
16 80
8 16
16 80
8 16
8 8 16 – – 4 x 16 – 0, 16, 32, 48, 64, 128, 144, 160, 176, 1921) – – – – – – – – 16 16 16 16
– – – 4 8 – 2 x 16 0, 16, 32, 48, 641) 8 8 4 4 8 8 4 4 – – – 16
Dependent on the DIL switch setting on the module
Overview – Address space for CPX bus node and control block Protocol Max. total Inputs
Outputs
Max. digital Inputs
Outputs
Max. analogue Inputs Outputs
CPX-FB11 CPX-FB13 CPX-FB33
512 bits 512 bits 512 bits
512 DI 512 DI 512 DI
512 DO 512 DO 512 DO
32 AI 32 AI 32 AI
DeviceNet PROFIBUS PROFINET RT
512 bits 512 bits 512 bits
18 AO 18 AO 18 AO
-H- Note The bandwidth of the bus nodes can be restricted by the choice of module and the maximum number of modules.
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
25
Page 26
Terminal CPX-P Technical data
-K- Module width 50 mm
-H- Note The data given here apply to the CPX-P system. If components that conform to lower values are used in the system, the specification for the entire system is reduced to the values of those components.
Example Protection class IP65 applies only to the fully assembled system with fitted plugs or covers (which must also con form to IP65). If components with a lower protection class are used, the
General technical data Module No. Max. no. of modules1)
Max. address capacity Internal cycle time Configuration support LED displays
562818 Control block Bus node I/O modules Pneumatic interface Inputs Outputs
[byte] [byte] [ms]
Bus node/control block
I/O modules Pneumatic interface Diagnostics
1)
26 protection level of the entire system is reduced to the protection class of the component with the lowest protection level, for example CageClamp connec tion block with IP20 protection.
1 1 9 1 64 64 1 Fieldbus-specific Up to 4 LEDs, bus-specific 4 LEDs, CPX-P-specific PS = Power system PL = Power load SF = System fault M = Modify parameter/forcing active Min. one group diagnostic LED Channel-oriented status and diagnostic LED, depending on module One group diagnostic LED Valve status LED on valve Channel and module-oriented diagnostics for inputs/outputs and valves Detection of module undervoltage for the different potential values Storage of the last 40 errors with timestamp (acyclic access)
A maximum of 11 modules in total can be combined. (e.g. 1 control block + 9 I/O modules + 1 pneumatic interface, or 1 control block + 1 bus node + 8 I/O modules + 1 pneumatic interface)
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 27
Terminal CPX-P Technical data General technical data Module No.
562818
Parameterisation
Commissioning support Nominal operating voltage Operating voltage range Power supply
Interlinking block with system supply for electronics plus sensors actuators plus valves Additional power supply for actuators
Current consumption Power failure bridging (bus electronics only) Power supply connection Fuse concept Tests Vibration test to DIN IEC 68
[V DC] [V DC]
Module-specific and entire system, for example: Diagnostic behaviour Condition monitoring Profile of inputs Fail-safe response of outputs and valves Forcing of inputs and outputs 24 18 … 30
[A] [A]
8 8
[A]
8 Depending on system configuration 10 7/8", 5-pin Per module with electronic fuses With wall mounting: Severity level 2 With H-rail mounting: Severity level 1 With wall mounting: Severity level 2 With H-rail mounting: Severity level 1
[ms]
Shock test to DIN IEC 68 PWIS classification Interference immunity Interference emission Isolation test for galvanically isolated circuits to IEC 1131 Part 2 Galvanic isolation of electrical voltages Protection against direct and indirect contact Materials Grid dimension
[V DC] [V DC]
[mm]
Operating and environmental conditions Module No. Ambient temperature Storage temperature
2018/04 – Subject to change
PWIS-free (free of paint-wetting impairment substances) EN 61000-6-2 (industry) EN 61000-6-4 (industry) 500 80 PELV (Protective Extra-Low Voltage) End plates: Die-cast aluminium 50
562818 [°C] [°C]
–5 … +50 –20 … +70
è Internet: www.festo.com/catalogue/...
27
Page 28
Terminal CPX-P Technical data Certifications and approvals – Maximum values Module No. ATEX category for gas Explosion ignition protection type for gas Explosion-proof temperature rating CE marking (see declaration of conformity)
562818
[°C]
Protection class to EN 60529 Certification Explosion protection certification outside the EU Certificate issuing authority 1)
II 3G Ex nA IIC T4 Gc –5 ≤ Ta ≤ +50 To EU Explosion Protection Directive (ATEX) To EU EMC Directive1) IP20, IP65 cULus recognized (OL) C-Tick EPL Gc (BR) DNV 15.0193 X
For information about the applicability of the component see the manufacturer’s EC declaration of conformity at: www.festo.com/sp è Certificates. If the component is subject to restrictions on usage in residential, office or commercial environments or small businesses, further measures to reduce the emitted interference may be necessary.
-H- Note The values indicated represent the maximum performance limits that can be achieved with the fully assembled product. Depending on the individual components used, the value actually achieved for the overall product may be lower.
You can select e.g. the individual components required to achieve the ATEX category by choosing the corresponding features in the online product configurator: è Internet:cpx-p
Weight [g] Bus node
I/O module
28
FB11 FB13 FB33 CPX NAMUR HART
120.0 115.0 280.0 38.0 100.0 77.4
è Internet: www.festo.com/catalogue/...
Pneumatic interface MPA-S Connection block Metal Interlinking block, metal Without power supply System supply, 7/8", 5-pin End plate for metal Left-hand design Right-hand
238.4 175.0 162.0 187.0 113.0 113.0
Subject to change – 2018/04
Page 29
Terminal CPX-P Accessories Ordering data – Accessories Designation
Part No.
Type
Attachment for wall mounting (for long valve terminals, 2 mounting brackets and 4 screws)
550217
CPX-M-BG-RW-2x
Mounting for H-rail
526032
CPX-CPA-BG-NRH
Mounting
Interlinking block Without power supply
–
550206
CPX-M-GE-EV
With system supply
7/8" – 5-pin
550208
CPX-M-GE-EV-S-7/8-5POL
7/8" – 5-pin, for ATEX environment
8022165
CPX-M-GE-EV-S-7/8-5POL-VL
550210
CPX-M-GE-EV-Z-7/8-5POL
7/8" – 5-pin, for ATEX environment
8022158
CPX-M-GE-EV-Z-7/8-5POL-VL
Screws for mounting the bus node/ connection block on an interlinking block
Bus node/plastic connection block
550219
CPX-M-M3x22-4x
Bus node/metal connection block
550216
CPX-M-M3x22-S-4x
End plate
Right-hand
550214
CPX-M-EPR-EV
Left-hand
550212
CPX-M-EPL-EV
Plug socket for mains connection 7/8", straight, 5-pin
0.25 … 2.0 mm2
543107
NECU-G78G5-C2
Plug socket for mains connection 7/8", angled, 5-pin – open cable end, 5-pin
2m
573855
NEBU-G78W5-K-2-N-LE5
Inscription labels 6x10 mm, 64 pieces, in frames
18576
IBS-6x10
With additional power supply for outputs 7/8" – 5-pin
Mounting accessories
End plates
Power supply
Inscription labels
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
29
Page 30
Terminal CPX-P Accessories Ordering data – Accessories Designation
Part No.
Type
572256
CAFC-X1-S
572257
CAFC-X1-BE
Hood Mounting rail for securing the hood
1,000 mm
Mounting kit for CPX hood
Hood section for CPX-P terminal including mounting attachments for connecting several hood sections in series
200 mm
572258
CAFC-X1-GAL-200
300 mm
572259
CAFC-X1-GAL-300
CPX-P System Manual
German English Spanish French Italian German English French Italian Spanish
526445 526446 526447 526448 526449 534824 534825 534827 534828 534826
P.BE-CPX-SYS-DE P.BE-CPX-SYS-EN P.BE-CPX-SYS-ES P.BE-CPX-SYS-FR P.BE-CPX-SYS-IT P.BE-CPX-MMI-1-DE P.BE-CPX-MMI-1-EN P.BE-CPX-MMI-1-FR P.BE-CPX-MMI-1-IT P.BE-CPX-MMI-1-ES
User documentation
Operator unit CPX-MMI-1
30
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04