Page 31

Terminal CPX-P Accessories User documentation Comprehensive user manuals are vital for the fast and reliable use of fieldbus components. The manuals provided by Festo contain step-by-step instructions for using the CPX-P terminal: 1. Installation 2. Commissioning and parameterisation 3. Diagnostics

Application-oriented explanations are provided for integration of the CPX-P terminal in the programming and configuration software of the various controller manufacturers. Use the order code to select the language you want. The manual for the configuration you have ordered is supplied automatically.

Device description files and icons are used to explain the integration of the CPX-P terminal in the config­ uration software of the various controller manufacturers.

Overview – User documentation Type

Title

Description

Pneumatic components P.BE-MPA-…

Valve terminals with MPA-S pneumatics

Instructions on assembly, installation, commissioning and diagnostics of the MPA-S pneumatic components.

System description, installation and commissioning

Overview of the design, components and mode of operation of the CPX-P terminal; installation and commissioning instructions as well as basic principles of parameterisation. Connection technology and assembly, installation and commissioning instructions for digital input and output modules of the type CPX-… and MPA pneumatic interface. Connection technology and assembly, installation and commissioning instructions for digital input and output modules of the type CPX-P-…. Connection technology and assembly, installation and commissioning instructions for analogue input and output modules of the type CPX-… Instructions on assembly, installation, commissioning and diagnostics of the relevant bus node. Instructions on assembly, installation, commissioning and diagnostics of the relevant bus node. Instructions on assembly, installation, commissioning and diagnostics of the CPX operator unit.

Electronic components P.BE-CPX-SYS-…

P.BE-CPX-EA-…

CPX-P-EA modules, digital

P.BE-CPX-P-EA-…

CPX-P-EA modules, NAMUR sensors

P.BE-CPX-AX-…

CPX-P-EA modules, analogue

P.BE-CPX-FB…

CPX bus node

P.BE-CPX-PNIO…

CPX bus node for PROFINET

P.BE-CPX-MMI-1-…

Universal handheld type CPX-MMI-1

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

The documents can be downloaded quickly and easily from the Festo website. è www.festo.com

31

Page 32

Terminal CPX-P Technical data – Operator unit CPX-MMI-1

-K- Width

81 mm

The operator unit is a small, conveni­ ent commissioning and service device for the CPX-P terminal. It provides data polling, configuration and diag­ nostic functions for CPX-P terminals. Its extremely flexible application range means that data can be read in or out at any location. IP65 compati­ bility makes it suitable for use in harsh industrial environments.

Application Functions Advance commissioning through the monitoring/forcing of inputs and outputs without fieldbus master/PLC Test function for parameter settings, for example fail-safe of the outputs or switch-on delay of the inputs Plain-text diagnostics of module and channel-oriented errors Condition monitoring: preselection/loading of counters, activation of the channels to be monitored Display of the last 40 error occurrences with timestamp Identification of sporadic causes of errors through display of the diagnostic history Password protection

Connection The operator unit is connected to the CPX bus nodes or control block, as appropriate, using a pre-assembled M12 cable. The voltage for the operator unit is supplied by the CPX-P component

32

è Internet: www.festo.com/catalogue/...

Communication Once connected to the CPX-P terminal, the operator unit loads the available configuration for the I/O modules, valves, etc. This ensures the availability of up-todate texts, messages, menus and displays. Status information, diagnostic messages and parameter bits are then exchanged during operation.

Assembly A mounting bracket for the operator unit offers the option of wall or H-rail mounting. The mounting bracket also has an option for temporary mounting using a hanging device.

Subject to change – 2018/04

Page 33

Terminal CPX-P Technical data – Operator unit CPX-MMI-1 Connection The operator unit is connected to the CPX-P terminal using pre-assembled cables.

Function examples System overview Overview of configured modules and current diagnostic messages

Diagnostics Fast access to the diagnostic history and the modules with diagnostic messaging Display of the last 40 diagnostic messages with timestamp Display of the current diagnostic message for a module

Commissioning Selection of module-specific data and parameters Display and modification of the current status of the inputs and outputs of a module Display and modification of the current settings for module-specific parameters

Setup Setting of access permission (password) Contrast setting of the display

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

33

Page 34

Terminal CPX-P Technical data – Operator unit CPX-MMI-1 General technical data Type

CPX-MMI-1

Data interface Display component Control elements Electromagnetic compatibility Nominal operating voltage Operating voltage range Current consumption Protection class to IEC 60529 Relative air humidity Vibration resistance

[V DC] [V DC] [mA] [%]

Shock resistance

Materials Dimensions (W x H x D) Product weight

[mm] [g]

RS232 interface, 57.6 kBaud, M12 socket, 4-pin LCD graphical display with background illumination (128 x 64 pixels) 7 keys: 4 arrow keys and 3 function keys, touch-sensitive keypad Interference emission tested to DIN EN 61000-6-4, industry Interference immunity tested to DIN EN 61000-6-2, industry 24, supplied by the connected device 18 … 30 50 … 60 IP65 90, non-condensing Tested to DIN/IEC 68/EN 60068, Part 2-6 With wall mounting: Severity level 2 With H-rail mounting: Severity level 1 Tested to DIN/IEC68/EN60068, Part 2-27 With wall mounting: Severity level 2 With H-rail mounting: Severity level 1 Reinforced PA 81 x 137 x 28 150

Operating and environmental conditions Ambient temperature CE marking (see declaration of conformity)

[°C]

ATEX category

Gas Dust Gas Dust [°C]

Ex ignition protection type ATEX temperature rating 1)

0 … 50 To EU EMC Directive1) To EU Explosion Protection Directive (ATEX) II 3 G II 3 D Ex nA IIC T6 X Gc Ex tc IIIC T60°C X Dc IP65 –5 <= Ta <= +50

For information about the applicability of the component see the manufacturer’s EC declaration of conformity at: www.festo.com/sp è Certificates. If the component is subject to restrictions on usage in residential, office or commercial environments or small businesses, further measures to reduce the emitted interference may be necessary.

-H- Note When operating device combinations in hazardous areas, the lowest common zone, temperature class and ambient temperature of the individual devices determine the possible use of the entire module.

Connection and display components

1

2 3 4

34

1 2 3 4

Display (LCD display) Function keys Arrow keys M12 interface

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 35

Terminal CPX-P Technical data – Operator unit CPX-MMI-1 Download CAD data è www.festo.com

Dimensions CPX-MMI-1

CPX-MMI-1-H

1 Bracket CPX-MMI-1-H, mounted on top

2 Bracket CPX-MMI-1-H, mounted underneath

1 H-rail

2 H-rail mounting CPX-MMI-1-NRH

Type

B1

B2

H1

H2

L1

L2

CPX-MMI-1 CPX-MMI-1-H

31.4 10.6

28 –

162 92

137 –

81 84.3

84.3 –

Ordering data Designation

Part No.

Type

Provides data polling, configuration and diagnostic functions for CPX-P terminals

529043

CPX-MMI-1

Connecting cable M12-M12, specially for CPX-MMI

1.5 m

529044

KV-M12-M12-1,5

3.5 m

530901

KV-M12-M12-3,5

Bracket

534705

CPX-MMI-1-H

Mounting for H-rail

536689

CPX-MMI-1-NRH

534824 534825 534827 534828 534826

P.BE-CPX-MMI-1-DE P.BE-CPX-MMI-1-EN P.BE-CPX-MMI-1-FR P.BE-CPX-MMI-1-IT P.BE-CPX-MMI-1-ES

Operator unit

Connecting cable

Mounting

User documentation User documentation for operator unit CPX-MMI-1

2018/04 – Subject to change

German English French Italian Spanish

è Internet: www.festo.com/catalogue/...

35

Page 36

Terminal CPX-P Technical data – CPX Maintenance Tool Function CPX-P Maintenance Tool (CPX-FMT) combines service software with a con­ necting adapter. The service software is a tool for the design, parameterisa­ tion and online diagnostics of the CPX-P terminal. The USB-to-M12 adapter features built-in galvanic isolation (between CPX-P and PC) and enables a PC to be connected to the diagnostic interface of the CPX-P terminal.

Adapter Software on CD-ROM

Application Only from Festo The CPX-FMT software enables access to CPX-P valve terminals via Ethernet with the control block CPX-CEC and the bus nodes PROFINET (FB 33, FB 34, FB 35). The bus nodes or control block can be connected directly to the PC via a USB adapter from Festo. Similar to the operator unit (CPX-MMI), diagnostic data such as the error trace or module diagnostics can be read out and parameters can be modified in plain text. In contrast to the operator unit (CPX-MMI), the data can be used directly on a PC. There is an option, for example, to send screenshots of a configuration or the current error trace directly via e-mail. In addition, CPX-P configurations can also be saved and

General technical data Type System requirements controller infrastructure. It must be noted that with both the CPX-P Maintenance Tool (CPX-FMT) and the operator unit (CPX-MMI), only local parameters on the CPX-P valve terminal can be changed and saved. The configuration of the networks or controller software cannot be influenced.

NEFC-M12G5-0.3-U1G5 PC Drive Interfaces Operating system

IBM-compatible CD-ROM USB port (specification USB 1.1 or higher) Microsoft Windows 2000 or XP Configuration and parameterisation Reading out of system, module, channel diagnostics and error trace Saving of the configuration as a project Integration of plug-ins/links to self-executing programs

Functional range

Scope of delivery Type of mounting Electrical connection Adapter cable composition Cable length Protection class to EN 60529 CE marking (see declaration of conformity) Ambient temperature Material Housing Cable sheath Pin contact Note on materials

36 archived directly as a CPX-FMT project. Undocumented changes can subsequently be identified using the online/offline comparison function. On-site tests such as the actuation of valves or the emulation of sensor feedback (in both cases called "forcing"), for example, can be performed without an existing

[m]

[°C]

è Internet: www.festo.com/catalogue/...

Adapter M12, 5-pin to mini USB socket CD-ROM with installation program Screw-in Plug M12x1, 5-pin 4 x 0.34 mm2 0.3 IP20 To EU EMC Directive –5 … +50 ABS PUR Gold-plated brass RoHS-compliant

Subject to change – 2018/04

Page 37

Terminal CPX-P Technical data – CPX Maintenance Tool Display components Creating a device configuration using the editor 1

2

The device configuration can be con­ veniently generated, parameterised and saved using the drag & drop feature. You can insert and move modules. 1 Module numbers from the graphic system overview 2 Catalogue for selecting required modules

Module overview for a selected module Displays important module data as well as the number of allocated inputs and outputs.

Diagnostic memory Faults which occur during operation are entered in a diagnostic memory. The first or the last 40 entries are saved, as well as the respective time measured from the moment the power supply was switched on.

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

37

Page 38

Terminal CPX-P Technical data – CPX Maintenance Tool Download CAD data è www.festo.com

Dimensions Adapter

1 Mini B 5P USB port 2 Plug M12x1, 5-pin

Ordering data Designation CPX-P Maintenance Tool (CPX-FMT), software and USB-to-M12 adapter

38

è Internet: www.festo.com/catalogue/...

Part No.

Type

547432

NEFC-M12G5-0.3-U1G5

Subject to change – 2018/04

Page 39

Terminal CPX-P Technical data – Bus node CPX-FB11 Bus node for handling communication between the electrical CPX-P terminal and a DeviceNet network. The bus node is provided with system supply via the interlinking block and processes communication with the I/O modules. The status of the CPX-P terminal is displayed as a common message via four CPX-P-specific LEDs. The fieldbus communication status is displayed via the three DeviceNetspecific LEDs.

Application Bus connection The bus connection can be selected when ordering, either Micro Style as 2xM12 round connectors or Open­ Style as a terminal strip with IP20 protection.

Both connection types have the func­ tion of an integrated T-distributor with incoming and outgoing bus line.

DeviceNet implementation The CPX-FB11 operates with the "Predefined Master/Slave Connection Set" as a "Group 2 Only Server". The polled I/O, change of state or cyclic method is used for the trans­ mission of cyclic I/O data. The type of transmission can be selected in the network configuration.

The device diagnostics for all bus nodes CPX-FB11 is effectively gathered via strobed I/O and displayed in the input table of the controller. In addition to cyclic data transmis­ sion, acyclic communication is sup­ ported through explicit messaging, which enables detailed device diagnostics and parameterisation.

A comprehensive EDS file supports the display of acyclic data. It is also possible to display system informa­ tion and assign parameters while the controller is running via the user program or the configuration software.

An example of this is access to the in­ tegrated diagnostic memory function, i.e. storage of the last 40 errors with timestamp, module, channel and error type. With its address capacity of 64 byte inputs and 64 byte outputs, the CPX-FB11 supports any configuration of I/O modules, including pneumatic interface.

In this case, the bus node only provides the communication interface to the PLC. Communication between the control block and CPX-P bus node is established by interlinking the CPX-P modules and occupies the following address capacity in the CPX-P system: 8 byte outputs 8 byte inputs

The remaining address capacity of the control block or CPX-P system for actuating the peripherals is: 56 byte inputs 56 byte outputs

Points to note in connection with CPX-CEC When a bus node is combined with a control block (CPX-CEC, in the fieldbus remote controller operating mode), the connected I/Os and/or valves, sensors and actuators are controlled via the CPX-P control block.

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

39

Page 40

Terminal CPX-P Technical data – Bus node CPX-FB11 General technical data Type

CPX-FB11

Fieldbus interface

[mm] [mm] [g]

Either Micro Style bus connection: 2xM12 with IP65/IP67 protection Open Style bus connection: 5-pin terminal strip, IP20 125, 250, 500 0 … 63 Set using DIL switch Communication adapter (12 dec.) 4554 dec. Polled I/O, change of state/cyclic, strobed I/O and explicit messaging EDS file and bitmaps 64 64 MS = Module status NS = Network status IO = I/O status Module and channel-oriented diagnostics by means of manufacturer-specific diagnostic object Module and system parameterisation via configuration interface in plain text (EDS) Online in run or program mode Storage of the last 40 errors with timestamp (access via EDS) 8-bit system status in image table for inputs 2-byte inputs and 2-byte outputs, system diagnostics in image table DIL switch 24 18 … 30 10 Typically 200 IP65, IP67 –5 … +50 –20 … +70 PA-reinforced PC 50 50 x 107 x 50 120

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Baud rate Addressing range Product Communication types Configuration support Max. address capacity

[kbps]

Type Code

Inputs Outputs

[byte] [byte]

Nominal value Permissible range Power failure buffering

[V DC] [V DC] [ms] [mA]

Operation Storage/transport

[°C] [°C]

LED displays (bus-specific)

Device-specific diagnostics Parameterisation

Additional functions

Control elements Operating voltage

Current consumption Protection class to EN 60529 Temperature range

Materials Grid dimension Dimensions (incl. interlinking block) W x L x H Product weight

-H- Note Please observe the general limits and guidelines for the system when configuring the electrical modules.

40